## Choosing, sizing and ordering 2 questions

#### What sizes does RADIANT come in?

15 to 90 kVA, in 6 models of the 2026 catalog for the US, from the RAD90-1X15 (15 kVA) to the RAD90-6X15 (90 kVA). The datasheet on this page gives every one.

Answered on [RADIANT](https://www.aecups.com/us/products/radiant/)

#### What supply does RADIANT need?

208/120 V three-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on [RADIANT](https://www.aecups.com/us/products/radiant/)

## Runtime and batteries 1 question

#### What batteries does RADIANT use?

External VRLA (battery bank sized separately). The battery bus is 240 V DC on every model.

Answered on [RADIANT](https://www.aecups.com/us/products/radiant/)

## Installation, size and connections 3 questions

#### What is the output current of each RADIANT model?

At full load, from the rating and the voltage:

| Model | Output current | Worked out as |
| --- | --- | --- |
| [RAD90-1X15](https://www.aecups.com/us/products/radiant/rad90-1x15/) | 41.6 A per phase | 15 kVA ÷ (√3 × 208 V) |
| [RAD90-2X15](https://www.aecups.com/us/products/radiant/rad90-2x15/) | 83.3 A per phase | 30 kVA ÷ (√3 × 208 V) |
| [RAD90-3X15](https://www.aecups.com/us/products/radiant/rad90-3x15/) | 124.9 A per phase | 45 kVA ÷ (√3 × 208 V) |
| [RAD90-4X15](https://www.aecups.com/us/products/radiant/rad90-4x15/) | 166.5 A per phase | 60 kVA ÷ (√3 × 208 V) |
| [RAD90-5X15](https://www.aecups.com/us/products/radiant/rad90-5x15/) | 208.2 A per phase | 75 kVA ÷ (√3 × 208 V) |
| [RAD90-6X15](https://www.aecups.com/us/products/radiant/rad90-6x15/) | 249.8 A per phase | 90 kVA ÷ (√3 × 208 V) |

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

#### How much heat does each RADIANT model give off?

At full load, model by model:

| Model | Heat | BTU/h | Efficiency |
| --- | --- | --- | --- |
| [RAD90-1X15](https://www.aecups.com/us/products/radiant/rad90-1x15/) | 991 W | 3,380 | 93.8% |
| [RAD90-2X15](https://www.aecups.com/us/products/radiant/rad90-2x15/) | 2.0 kW | 6,770 | 93.8% |
| [RAD90-3X15](https://www.aecups.com/us/products/radiant/rad90-3x15/) | 3.0 kW | 10,150 | 93.8% |
| [RAD90-4X15](https://www.aecups.com/us/products/radiant/rad90-4x15/) | 4.0 kW | 13,530 | 93.8% |
| [RAD90-5X15](https://www.aecups.com/us/products/radiant/rad90-5x15/) | 5.0 kW | 16,910 | 93.8% |
| [RAD90-6X15](https://www.aecups.com/us/products/radiant/rad90-6x15/) | 5.9 kW | 20,300 | 93.8% |

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

#### Which RADIANT models fit through a standard door?

A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:

| Model | Upright through the door | Narrow side, height |
| --- | --- | --- |
| [RAD90-1X15](https://www.aecups.com/us/products/radiant/rad90-1x15/) | Yes | 17.4 in (442 mm) across, 59.4 in (1,510 mm) high |
| [RAD90-2X15](https://www.aecups.com/us/products/radiant/rad90-2x15/) | Yes | 17.4 in (442 mm) across, 59.4 in (1,510 mm) high |
| [RAD90-3X15](https://www.aecups.com/us/products/radiant/rad90-3x15/) | Yes | 17.4 in (442 mm) across, 59.4 in (1,510 mm) high |
| [RAD90-4X15](https://www.aecups.com/us/products/radiant/rad90-4x15/) | Yes | 17.4 in (442 mm) across, 59.4 in (1,510 mm) high |
| [RAD90-5X15](https://www.aecups.com/us/products/radiant/rad90-5x15/) | Yes | 17.4 in (442 mm) across, 59.4 in (1,510 mm) high |
| [RAD90-6X15](https://www.aecups.com/us/products/radiant/rad90-6x15/) | Yes | 17.4 in (442 mm) across, 59.4 in (1,510 mm) high |

On the way in, check corridors, elevators and the floor load (size section of each model's page).

Each model's own page, linked in the table, gives its full answer and data.

## Communication and monitoring 1 question

#### How is RADIANT monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on [RADIANT](https://www.aecups.com/us/products/radiant/)

## Warranty, service and maintenance 1 question

#### What warranty does RADIANT have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.