title: "AEC AUREON UPS guide specification, CSI 26 33 53"
url: https://www.aecups.com/us/products/aureon-guide-specification/
description: "Three-part CSI 26 33 53 guide specification for the AEC AUREON UPS, from the catalog data: ratings, battery, models, installation. Download for Word."
language: en-US
---

For specifiers · CSI 26 33 53

# AEC AUREON guide specification

A three-part specification for Section 26 33 53, Static Uninterruptible Power Supply, written from the AUREON catalog data. Download it for Word, or copy it from this page and edit it to your project.

Reviewed by **[Bruno Grosso](https://www.aecups.com/us/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/us/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

[Download (RTF, opens in Word)](https://www.aecups.com/us/downloads/AEC-aureon-26-33-53.rtf) [AUREON series](https://www.aecups.com/us/products/aureon/)

## SECTION 26 33 53 – STATIC UNINTERRUPTIBLE POWER SUPPLY: AEC AUREON

### PART 1 – GENERAL

#### 1.1 SUMMARY

- A. This Section specifies an online double-conversion uninterruptible power supply (UPS) system, AEC AUREON series, 10 to 30 kVA, 208 V three-phase, 4-wire (3P+N), complete with valve-regulated lead-acid (VRLA) batteries, controls, monitoring and accessories.
- B. Related requirements: Division 26 sections for wiring, grounding and overcurrent protection; the battery and the UPS installation per the manufacturer's instructions.

#### 1.2 REFERENCES

- A. [NFPA 70](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70), National Electrical Code (NEC), for the installation.
- B. The manufacturer's published product data, user manual and single-line diagram, current edition.

#### 1.3 SUBMITTALS

- A. Product data: the manufacturer's catalog sheet for the selected model, with rating, efficiency, dimensions and weight.
- B. Battery runtime at the project load, from the manufacturer's published runtime data.
- C. Operation and maintenance data: the manufacturer's user manual.

#### 1.4 QUALITY ASSURANCE

- A. Source qualifications: AEC, the UPS brand of the AEC Group. Parent company: Allis Electric Co., Ltd., in power equipment since 1968, listed on the Taiwan Stock Exchange as 1514; the group's quality management system is certified to ISO 9001:2015 (SGS).
- B. Sales and service in the United States: AEC UPS USA, Miami, Florida, warehouse in Doral, Florida.

#### 1.5 WARRANTY

- A. Manufacturer's standard warranty: 3 years on UPS · 2 years on VRLA batteries.

### PART 2 – PRODUCTS

#### 2.1 MANUFACTURERS

- A. Basis-of-design product: AEC AUREON series (AEC, the UPS brand of the AEC Group), supplied in the United States by AEC UPS USA (https://www.aecups.com).
- B. Substitutions: as permitted by Division 01.

#### 2.2 SYSTEM DESCRIPTION

- A. Topology: Online Double Conversion. The load is supplied by the inverter in normal operation, with automatic static bypass and a manual maintenance bypass.
- B. Ratings: 10 kVA, 20 kVA, 30 kVA; output power factor 1.0 (kVA = kW where the factor is 1.0).
- C. Input and output: 208 V three-phase, 4-wire (3P+N).
- D. Efficiency: up to 94% (manufacturer's published figure).
- E. Battery: VRLA batteries.
- F. Network card: SNMP-L (SNMP).
- G. Certification: [UL 1778](https://www.shopulstandards.com/ProductDetail.aspx?productId=UL1778) listed, UL file E543003 (AEC UPS USA LLC).
- H. Quality system: ISO 9001:2015, the group's quality system (SGS).

#### 2.3 BATTERY

- A. Type: VRLA (sealed lead-acid), internal. Frames without batteries (AUR-10, AUR-20, AUR-30) take the battery separately.
- B. Nominal DC bus: 240 V DC.
- C. Runtime: per the manufacturer's published runtime data for the selected model at the project load.

#### 2.4 MODELS

- AUR-10: 10 kVA; 10 kW; VRLA (sealed lead-acid); 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm); 231 lb (104.8 kg).
- AUR10-40X9A: 10 kVA; 10 kW; VRLA (sealed lead-acid); 25 min at 50 % load; 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm); 465 lb (210.9 kg).
- AUR10-80X9A: 10 kVA; 10 kW; VRLA (sealed lead-acid); 60 min at 50 % load; 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm); 699 lb (317.1 kg).
- AUR-20: 20 kVA; 20 kW; VRLA (sealed lead-acid); 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm); 258 lb (117 kg).
- AUR20-60X9A: 20 kVA; 20 kW; VRLA (sealed lead-acid); 13.5 min, AEC estimate at 50 % load; 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm); 609 lb (276.2 kg).
- AUR20-80X9A: 20 kVA; 20 kW; VRLA (sealed lead-acid); 20 min, AEC estimate at 50 % load; 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm); 726 lb (329.3 kg).
- AUR-30: 30 kVA; 30 kW; VRLA (sealed lead-acid); 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm); 282 lb (127.9 kg).
- AUR30-80X9A: 30 kVA; 30 kW; VRLA (sealed lead-acid); 14 min at 50 % load; 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm); 750 lb (340.2 kg).

### PART 3 – EXECUTION

#### 3.1 INSTALLATION

- A. Install according to the manufacturer's instructions and NFPA 70, with the clearances the manufacturer's manual gives for service access and airflow.
- B. Provide input, bypass, output and battery overcurrent protection and conductors sized to the selected model and the manufacturer's data.

#### 3.2 FIELD QUALITY CONTROL AND START-UP

- A. Start-up by a technician authorized by the manufacturer: check of wiring and grounding, battery connection, operating modes and alarms.
- B. Record the readings at start-up and hand them over with the operation and maintenance data.

#### 3.3 DEMONSTRATION

- A. Train the owner's personnel in normal operation, transfer to and from bypass and maintenance bypass, alarms and the battery.

Edit to the project. Product figures from the AEC 2026 catalog. END OF SECTION 26 33 53.