title: "10 kVA 208V three-phase UPS, VRLA frame only: AEC AUR-10"
url: https://www.aecups.com/us/products/aureon/aur-10/
description: "AEC AUREON AUR-10: 10 kVA / 10 kW online UPS for 208 V three-phase, frame only, no batteries included: up to 80 internal 12 V 9 Ah VRLA blocks."
language: en-US
---

AUREON · 208V three-phase UPS

# AUR-10 AUREON 10 kVA, 208V three-phase UPS

VRLA 10 kVA Online double conversion

The AEC AUREON AUR-10 is a 10 kVA / 10 kW online double-conversion UPS for 208 V three-phase loads, with no batteries included: the frame takes up to 80 internal 12 V 9 Ah VRLA blocks, in 20, 40, 60 or 80. Kept at 80 % of its rating, it carries loads up to 8 kW.

**10 kVA / 10 kW** Rating

**14.9 × 39.1 × 49.2 in** W × D × H

**231 lb** Weight

**VRLA, up to 80 inside, not included** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_AUREON_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20AUR-10%20(AUREON)%3A%20%0AQuantity%3A%20#form)

Series picture.

Load by load

## The AUR-10 at 25, 50, 75 and 100 % load.

Its 10 kW rating in four steps, worked out from its own catalog figures.

**At 25, 50, 75 and 100 % load**

| Load | Output current per phase, at 208 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
| --- | --- | --- | --- | --- |
| 25 % of the AUR-10, 2.5 kW | 6.9 A per phase | 92.5 % efficient | 203 W of heat | 690 BTU/h to cool |
| 50 % of the AUR-10, 5.0 kW | 13.9 A per phase | 93.9 % efficient | 325 W of heat | 1,110 BTU/h to cool |
| 75 % of the AUR-10, 7.5 kW | 20.8 A per phase | 94.0 % efficient | 479 W of heat | 1,630 BTU/h to cool |
| 100 % of the AUR-10, 10 kW | 27.8 A per phase | 93.8 % efficient | 661 W of heat | 2,260 BTU/h to cool |

Current = kVA × load ÷ (√3 × volts).

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

## What is the AUR-10?

- Technology: 3-level IGBT; unity power factor (kVA = kW).
- Efficiency: up to 94%. 4.3" touch screen color display; cold start and self-cleaning functions.
- Comms: Modbus and dry contact standard.

The lines every AUREON shares, from technology to warranty, are in the [AUREON key facts](https://www.aecups.com/us/products/aureon/#overview) and in the datasheet below.

Size and floor

## How big it is

14.9" W × 39.1" D × 49.2" H (378 × 993 × 1,250 mm); 231 lb (104.8 kg) net.

**4.0 ft²** footprint (0.38 m²)

**57 lb/ft²** floor load of the cabinet alone

**Tower** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## AUR-10 datasheet.

The AUR-10 in the AEC 2026 catalog, figure by figure. [Compare it with every AUREON model](https://www.aecups.com/us/products/aureon/#datasheet).

**AUR-10 datasheet**

| Parameter | AUR-10 |
| --- | --- |
| Power |  |
| Rated power (kVA) | 10 |
| Active power (kW) | 10 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online Double Conversion |
| Efficiency, up to | 94% |
| Battery DC bus | 240 V DC |
| Battery and runtime |  |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80) |
| Mechanical |  |
| Form factor | Tower |
| Dimensions W × D × H | 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm) |
| Net weight | 231 lb (104.8 kg) |
| Footprint | 4.0 ft² (0.38 m²) |
| Common to every AUREON |  |
| Battery | VRLA batteries |
| Network card | SNMP-L (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Certification | [UL 1778](https://www.shopulstandards.com/ProductDetail.aspx?productId=UL1778) listed, UL file E543003 (AEC UPS USA LLC) |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## AUR-10: what people ask

#### What is the output current of the AUR-10?

27.8 A per phase at full load: 10 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the AUR-10 from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the AUR-10 give off?

About 661 W, 2,260 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the AUR-10 is less efficient at part load and while its battery recharges.

#### Will the AUR-10 fit through a standard door?

Yes: 14.9 in (378 mm) across its narrow side and 49.2 in (1,250 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the AUR-10 (size section above).

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

AUREON

## Other AUREON models

[The AUREON series, with pictures](https://www.aecups.com/us/products/aureon/#models)

By power, the AUR-10 is the smallest in the AUREON series, which runs from 10 to 30 kVA. One size up are the [AUR-20](https://www.aecups.com/us/products/aureon/aur-20/), [AUR20-60X9A](https://www.aecups.com/us/products/aureon/aur20-60x9a/) and [AUR20-80X9A](https://www.aecups.com/us/products/aureon/aur20-80x9a/), all 10 kVA more. The same 10 kVA also comes as the [AUR10-40X9A](https://www.aecups.com/us/products/aureon/aur10-40x9a/) and [AUR10-80X9A](https://www.aecups.com/us/products/aureon/aur10-80x9a/): the table below gives each one's weight and battery.

#### Every AUREON model side by side (8)

**AUREON models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load | Battery configuration |
| --- | --- | --- | --- | --- | --- | --- |
| **AUR-10** | 10 kVA | this page | 231 lb | this page | — | Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80) |
| [AUR10-40X9A](https://www.aecups.com/us/products/aureon/aur10-40x9a/) | 10 kVA | the same power | 465 lb | 234 lb heavier | 25 min at 50 % load | Internal |
| [AUR10-80X9A](https://www.aecups.com/us/products/aureon/aur10-80x9a/) | 10 kVA | the same power | 699 lb | 468 lb heavier | 60 min at 50 % load | Internal |
| [AUR-20](https://www.aecups.com/us/products/aureon/aur-20/) | 20 kVA | 10 kVA more | 258 lb | 27 lb heavier | — | Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80) |
| [AUR20-60X9A](https://www.aecups.com/us/products/aureon/aur20-60x9a/) | 20 kVA | 10 kVA more | 609 lb | 378 lb heavier | 13.5 min at 50 % load, AEC estimate | Internal |
| [AUR20-80X9A](https://www.aecups.com/us/products/aureon/aur20-80x9a/) | 20 kVA | 10 kVA more | 726 lb | 495 lb heavier | 20 min at 50 % load, AEC estimate | Internal |
| [AUR-30](https://www.aecups.com/us/products/aureon/aur-30/) | 30 kVA | 20 kVA more | 282 lb | 51 lb heavier | — | Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80) |
| [AUR30-80X9A](https://www.aecups.com/us/products/aureon/aur30-80x9a/) | 30 kVA | 20 kVA more | 750 lb | 519 lb heavier | 14 min at 50 % load | Internal |

Install and run it: [Guide specification, CSI 26 33 53](https://www.aecups.com/us/products/aureon-guide-specification/)

## The AUR-10 for your project

Send the load, the voltage and the minutes you need from the AUR-10. We reply with the configuration, the batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20AUR-10%20(AUREON)%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)