title: "UPS batteries: 12 V AGM VRLA, battery packs, cabinets | AEC"
url: https://www.aecups.com/us/products/batteries/
description: "Sealed AGM VRLA batteries for UPS, battery packs and cabinets for FERRUS, FERRUS SP and modular UPS: design life 10–12 years (EUROBAT)."
language: en-US
---

12 V AGM · battery packs · cabinets

# VRLA batteries and cabinets

Sealed lead-acid batteries made for UPS duty: AGM technology with oxygen recombination, no liquid to add for their whole life, and a design life of 10 to 12 years by the EUROBAT guide.

[Size a battery bank](https://www.aecups.com/us/contacts/?interest=Sizing%20help#form) [Lithium instead](https://www.aecups.com/us/products/lithium-batteries/)

AGM VRLA

## Made for UPS duty.

Oxygen recombination, sealed, maintenance-free.

**Sealed** Valve-regulated: a pressure valve keeps the gases of charging inside, with no emission in normal use.

**AGM** The electrolyte is held in an absorbent glass-fiber mat, so there is no acid to spill or top up.

**Strong plates** Plates welded with special alloys for high mechanical strength.

**Design life** 10 to 12 years by the EUROBAT guide, the class of long-life UPS batteries.

**Delivered charged** Recharge fully after every discharge and during long storage, and have them checked by a qualified technician.

Heat and battery life

## Every degree counts.

Slide the room temperature. A common rule of thumb for VRLA: life halves for about every 8 °C (14 °F) above 25 °C (77 °F).

30 °C 86 °F

Expected life of a 10–12 year AGM block

Also shortened by: Charging with an unsuitable charger · Maintenance by non-specialists · Deep discharges left uncharged.

Battery cabinets

## Runtime, extended.

A battery cabinet extends the runtime of the UPS. Each UPS has its own cabinet, sized to the number of blocks the model takes, and AEC adapts it to the project.

Cabinets and packs for [FERRUS](https://www.aecups.com/us/products/ferrus/), [FERRUS RT](https://www.aecups.com/us/products/ferrus-rt/), [FERRUS SP](https://www.aecups.com/us/products/ferrus-sp/) and [FERRUS SP RT](https://www.aecups.com/us/products/ferrus-sp-rt/).

**Steel, IP20**: A solid steel housing as standard.

**Up to IP44**: Higher protection, aluminum alloys or stainless steel when the site asks for it.

**Disconnectors**: Two- or three-pole, up to 1,000 A.

**Ventilation**: Automatic fans available inside the cabinet.

FERRUS battery cabinet, tower

FERRUS RT battery cabinet, rack

BB4US cabinet, open

FERRUS SP RT battery rack, 3U

Range

## Batteries and cabinets for the US market.

From the 2026 catalog.

| Model | Description | For | Size (W × D × H) | Weight |
| --- | --- | --- | --- | --- |
| **BAT0424** | Battery Cabinet Tower 24Vdc | FERRUS | 5.6" W × 8.6" D × 9.4" H (142 × 218 × 239 mm) | 31.4 lb (14.2 kg) |
| **BAT0848** | Battery Cabinet Tower 48Vdc | FERRUS | 5.6" W × 8.6" D × 17.3" H (142 × 218 × 439 mm) | 58.8 lb (26.7 kg) |
| **BAT1272** | Battery Cabinet Tower 72Vdc | FERRUS | 5.6" W × 8.6" D × 25.1" H (142 × 218 × 638 mm) | 86.2 lb (39.1 kg) |
| **BAT0424RT** | Battery Cabinet Rack 24Vdc | FERRUS RT | 17.3" W × 17.3" D × 3.4" H (439 × 439 × 86 mm) | 35.4 lb (16.1 kg) |
| **BAT0848RT** | Battery Cabinet Rack 48Vdc | FERRUS RT | 17.3" W × 17.3" D × 5.2" H (439 × 439 × 132 mm) | 64.8 lb (29.4 kg) |
| **BAT1272RT** | Battery Cabinet Rack 72Vdc | FERRUS RT | 17.3" W × 22.8" D × 7" H (439 × 579 × 178 mm) | 94.2 lb (42.7 kg) |
| **BB4US** | Battery Cabinet Tower 192Vdc, empty | FERRUS SP | 9.8" W × 33.5" D × 28.5" H (250 × 852 × 725 mm) | 110 lb (49.9 kg) |
| **BAT16192RT** | Battery Cabinet Rack 192Vdc | FERRUS SP RT | 17.3" W × 25" D × 5.2" H (439 × 635 × 132 mm) | 123.6 lb (56.1 kg) |
| **RADIB-BATTR-EMPTY** | Battery Tray empty | RADIANT-IB | not published | 5 lb (2.3 kg) |
| **RADIB-BATTR-10x9A** | Battery Tray incl. 10x 12V/9Ah | RADIANT-IB | not published | 63.5 lb (28.8 kg) |
| **CIRIB-BATTR-10x9A** | Battery Tray incl. 10x 12V/9Ah | CIRRO-IB | not published | 63.5 lb (28.8 kg) |
| **CIRIB-BATTR-EMPTY** | Battery Tray empty | CIRRO-IB | not published | 5 lb (2.3 kg) |
| **AGM-12V-9AH** | AGM 12V 9Ah VRLA | — | 5.9" W × 2.6" D × 3.7" H (151 × 65 × 93 mm) | 5.5 lb (2.5 kg) |

Questions

## Questions people ask

#### Which battery cabinets and packs fit the FERRUS?

BAT0424, 31.4 lb; BAT0848, 58.8 lb; BAT1272, 86.2 lb, from the AEC 2026 catalog. AEC sizes the number of cabinets for the load and the minutes.

#### Which battery cabinets and packs fit the FERRUS RT?

BAT0424RT, 35.4 lb; BAT0848RT, 64.8 lb; BAT1272RT, 94.2 lb, from the AEC 2026 catalog. AEC sizes the number of cabinets for the load and the minutes.

#### Which battery cabinets and packs fit the FERRUS SP?

BB4US, 110 lb, from the AEC 2026 catalog. AEC sizes the number of cabinets for the load and the minutes.

#### Which battery cabinets and packs fit the FERRUS SP RT?

BAT16192RT, 123.6 lb, from the AEC 2026 catalog. AEC sizes the number of cabinets for the load and the minutes.

#### Which battery cabinets and packs fit the RADIANT-IB?

RADIB-BATTR-EMPTY, 5 lb; RADIB-BATTR-10x9A, 63.5 lb, from the AEC 2026 catalog. AEC sizes the number of cabinets for the load and the minutes.

#### Which battery cabinets and packs fit the CIRRO-IB?

CIRIB-BATTR-10x9A, 63.5 lb; CIRIB-BATTR-EMPTY, 5 lb, from the AEC 2026 catalog. AEC sizes the number of cabinets for the load and the minutes.

#### How long does a VRLA battery last in a UPS?

AEC's AGM blocks have a design life of 10–12 years at 77 °F (25 °C). A common rule of thumb for VRLA: life halves for about every 14 °F (8 °C) above 77 °F, so the battery room's temperature matters as much as the block.

## Size a battery bank

Tell us the UPS, the load and the minutes. We size the blocks and the cabinet.

[Send your project](https://www.aecups.com/us/contacts/#form) [+1 786 553 2100](tel:+17865532100)