title: "90 kVA 480V three-phase UPS: AEC CIRRO-IB CIRIB150-3X30"
url: https://www.aecups.com/us/products/cirro-ib/cirib150-3x30/
description: "AEC CIRRO-IB CIRIB150-3X30: 90 kVA / 90 kW online UPS for 480 V three-phase, built on three 30 kVA power modules, with VRLA batteries on internal trays."
language: en-US
---

CIRRO-IB · 480V three-phase UPS

# CIRIB150-3X30 CIRRO-IB 90 kVA, 480V three-phase UPS

VRLA 90 kVA Online double conversion

The AEC CIRRO-IB CIRIB150-3X30 is a 90 kVA / 90 kW online double-conversion UPS for 480 V three-phase loads, built on three 30 kVA power modules, with VRLA batteries on internal trays. Kept at 80 % of its rating, it carries loads up to 72 kW.

Three of the frame's five module slots are fitted and two are free; with one module held as a spare (N+1) it carries 60 kVA. As configured it weighs 2,295.8 lb (1,041.4 kg) net.

4-wire · 3P+N 480 V 4-wire, wye: three phases, neutral and ground (277/480 V)

**90 kVA / 90 kW** Rating

**23.6 × 39.3 × 78.7 in** W × D × H

**2,295.8 lb** Weight

**VRLA, internal** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_CIRRO_IB_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20CIRIB150-3X30%20(CIRRO-IB)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/cirib/v57/#cirib150-3)

Series picture.

Drag to turn

In 3D

## Look around the CIRIB150-3X30

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/cirib/v57/#cirib150-3)

The turntable shows the 150 kVA · 5 modules configuration; the full 3D view opens on this model.

The same on every CIRRO-IB: [The CIRRO-IB display](https://www.aecups.com/us/products/cirro-ib/#display)

Load by load

## The CIRIB150-3X30 at 25, 50, 75 and 100 % load.

Its 90 kW rating in four steps, worked out from its own catalog figures.

**At 25, 50, 75 and 100 % load**

| Load | Output current per phase, at 480 V | Load on each of its 3 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
| --- | --- | --- | --- | --- | --- |
| 25 % of the CIRIB150-3X30, 23 kW | 27.1 A per phase | 25 % on each module | 95.0 % efficient | 1.2 kW of heat | 4,040 BTU/h to cool |
| 50 % of the CIRIB150-3X30, 45 kW | 54.1 A per phase | 50 % on each module | 95.9 % efficient | 1.9 kW of heat | 6,560 BTU/h to cool |
| 75 % of the CIRIB150-3X30, 68 kW | 81.2 A per phase | 75 % on each module | 96.0 % efficient | 2.8 kW of heat | 9,600 BTU/h to cool |
| 100 % of the CIRIB150-3X30, 90 kW | 108 A per phase | 100 % on each module | 95.8 % efficient | 3.9 kW of heat | 13,460 BTU/h to cool |

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

## What is the CIRIB150-3X30?

The code CIRIB150-3X30 orders these catalog items, shipped in 28 cartons:

- 1 × CIRIB-FRAME: 150 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
- 3 × CIRIB-PWR-30: 30 kVA hot-swappable power module, 52 lb (23.6 kg) each
- 24 × CIRIB-BATTR-10x9A: battery tray of 10 × 12 V 9 Ah VRLA blocks, 63.5 lb (28.8 kg) each
- Architecture: 3 × 30 kVA hot-swappable power modules in a 150 kVA / 150 kW frame (scalable to 5 modules / 150 kVA); parallel up to 3 cabinets.

The lines every CIRRO-IB shares, from technology to warranty, are in the [CIRRO-IB key facts](https://www.aecups.com/us/products/cirro-ib/#overview) and in the datasheet below.

3 × 30 kVA power modules fitted in a 5-slot frame: 2 free slots to grow or add redundancy.

Size and floor

## How big it is

23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 2,295.8 lb (1,041.4 kg) net.

**6.4 ft²** footprint (0.60 m²)

**356 lb/ft²** floor load of the cabinet alone

**Modular** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## CIRIB150-3X30 datasheet.

The CIRIB150-3X30 in the AEC 2026 catalog, figure by figure. [Compare it with every CIRRO-IB model](https://www.aecups.com/us/products/cirro-ib/#datasheet).

**CIRIB150-3X30 datasheet**

| Parameter | CIRIB150-3X30 |
| --- | --- |
| Power |  |
| Rated power (kVA) | 90 |
| Active power (kW) | 90 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 96% |
| Battery DC bus | 480 V DC |
| Battery and runtime |  |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal Tray System |
| Runtime at 50 % load | 10.5 min |
| Runtime at 100 % load | 3 min |
| Mechanical |  |
| Form factor | Modular |
| Dimensions W × D × H | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) |
| Net weight | 2,295.8 lb (1,041.4 kg) |
| Footprint | 6.4 ft² (0.60 m²) |
| Shipping |  |
| Cartons | 28 |
| Common to every CIRRO-IB |  |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger |
| Battery, CIRIB150-3X30 | internal hot-swappable VRLA, up to 240 × 12V 9Ah (240 pcs) |
| Display | 7-inch color touchscreen |
| Comms | RS-232, EPO and USB, standard |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## CIRIB150-3X30: what people ask

#### What is the output current of the CIRIB150-3X30?

108.3 A per phase at full load: 90 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIRIB150-3X30 from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the CIRIB150-3X30 give off?

About 3.9 kW, 13,460 BTU/h, at full load, where it is 95.8% efficient. Plan the room's cooling for a little more than that: the CIRIB150-3X30 is less efficient at part load and while its battery recharges.

#### Will the CIRIB150-3X30 fit through a standard door?

Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIRIB150-3X30 (size section above).

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

CIRRO-IB

## Other CIRRO-IB models

[The CIRRO-IB series, with pictures](https://www.aecups.com/us/products/cirro-ib/#models)

By power, the CIRIB150-3X30 is number 3 of 5 in the CIRRO-IB series, which runs from 30 to 150 kVA. One size down is the [CIRIB150-2X30](https://www.aecups.com/us/products/cirro-ib/cirib150-2x30/) (30 kVA less and 52 lb lighter). One size up is the [CIRIB150-4X30](https://www.aecups.com/us/products/cirro-ib/cirib150-4x30/) (30 kVA more and 52 lb heavier).

#### Every CIRRO-IB model side by side (5)

**CIRRO-IB models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
| --- | --- | --- | --- | --- | --- |
| [CIRIB150-1X30](https://www.aecups.com/us/products/cirro-ib/cirib150-1x30/) | 30 kVA | 60 kVA less | 2,192 lb | 104 lb lighter | 45 min at 50 % load |
| [CIRIB150-2X30](https://www.aecups.com/us/products/cirro-ib/cirib150-2x30/) | 60 kVA | 30 kVA less | 2,244 lb | 52 lb lighter | 14 min at 50 % load |
| **CIRIB150-3X30** | 90 kVA | this page | 2,296 lb | this page | 10.5 min at 50 % load |
| [CIRIB150-4X30](https://www.aecups.com/us/products/cirro-ib/cirib150-4x30/) | 120 kVA | 30 kVA more | 2,348 lb | 52 lb heavier | 6 min at 50 % load |
| [CIRIB150-5X30](https://www.aecups.com/us/products/cirro-ib/cirib150-5x30/) | 150 kVA | 60 kVA more | 2,400 lb | 104 lb heavier | 6 min at 50 % load |

Install and run it: [CIRRO-IB installation and operation manual](https://www.aecups.com/us/support/guides/cirro-ib-manual/) [RADIANT and CIRRO touch screen guide](https://www.aecups.com/us/support/guides/radiant-cirro/)

## The CIRIB150-3X30 for your project

Send the load, the voltage and the minutes you need from the CIRIB150-3X30. We reply with the configuration, the batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20CIRIB150-3X30%20(CIRRO-IB)%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)