---
title: "600 kVA 480V three-phase UPS: AEC CIRRO CIR600-6X100"
url: https://www.aecups.com/us/products/cirro/cir600-6x100/
description: "AEC CIRRO CIR600-6X100: 600 kVA / 600 kW online UPS for 480 V three-phase, built on six 100 kVA power modules, with external battery cabinets."
language: en-US
---

CIRRO · 480V three-phase UPS

# CIR600-6X100 CIRRO 600 kVA, 480V three-phase UPS

VRLA 600 kVA Online double conversion

The AEC CIRRO CIR600-6X100 is a 600 kVA / 600 kW online double-conversion UPS for 480 V three-phase loads, built on six 100 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 480 kW.

All six module slots are fitted, so the frame is at its full 600 kVA; with one module held as a spare (N+1) it carries 500 kVA. As configured it weighs 1,514.5 lb (687 kg) net.

4-wire · 3P+N 480 V 4-wire, wye: three phases, neutral and ground (277/480 V)

**600 kVA / 600 kW** Rating

**31.5 × 39.4 × 78.7 in** W × D × H

**1,514.5 lb** Weight

**VRLA, external** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_CIRRO_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20CIR600-6X100%20(CIRRO)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/cir/v52/#cir600)

Drag to turn

In 3D

## Look around the CIR600-6X100

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/cir/v52/#cir600)

The same on every CIRRO: [The CIRRO display](https://www.aecups.com/us/products/cirro/#display)

Load by load

## The CIR600-6X100 at 25, 50, 75 and 100 % load.

Its 600 kW rating in four steps, worked out from its own catalog figures.

**At 25, 50, 75 and 100 % load**

| Load | Output current per phase, at 480 V | Load on each of its 6 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
| --- | --- | --- | --- | --- | --- |
| 25 % of the CIR600-6X100, 150 kW | 180 A per phase | 25 % on each module | 96.2 % efficient | 5.9 kW of heat | 20,220 BTU/h to cool |
| 50 % of the CIR600-6X100, 300 kW | 361 A per phase | 50 % on each module | 96.9 % efficient | 9.6 kW of heat | 32,750 BTU/h to cool |
| 75 % of the CIR600-6X100, 450 kW | 541 A per phase | 75 % on each module | 97.0 % efficient | 14 kW of heat | 47,490 BTU/h to cool |
| 100 % of the CIR600-6X100, 600 kW | 722 A per phase | 100 % on each module | 96.8 % efficient | 20 kW of heat | 67,680 BTU/h to cool |

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

## What is the CIR600-6X100?

The code CIR600-6X100 orders these catalog items:

- 1 × CIR600-FRAME: 600 kVA frame, without power modules, 31.5 × 39.4 × 78.7 in (800 × 1,001 × 1,999 mm)
- 6 × CIR-PWR-100: 100 kVA hot-swappable power module, 103.6 lb (47 kg) each
- Architecture: 6 × 100 kVA hot-swappable power modules in a 600 kVA / 600 kW frame (6 slots, scalable to 6 modules / 600 kVA); parallel up to 8 units.
- Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole).
- Switchgear: 4 breakers included in the frame — main input, output, bypass input, maintenance bypass.
- Efficiency: up to 97%.

The lines every CIRRO shares, from technology to warranty, are in the [CIRRO key facts](https://www.aecups.com/us/products/cirro/#overview) and in the datasheet below.

6 × 100 kVA power modules fitted in a 6-slot frame: the frame is full.

Size and floor

## How big it is

31.5" W × 39.4" D × 78.7" H (800 × 1,001 × 1,999 mm); 1,514.5 lb (687 kg) net.

**8.6 ft²** footprint (0.80 m²)

**176 lb/ft²** floor load of the cabinet alone

**Modular** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## CIR600-6X100 datasheet.

The CIR600-6X100 in the AEC 2026 catalog, figure by figure. [Compare it with every CIRRO model](https://www.aecups.com/us/products/cirro/#datasheet).

**CIR600-6X100 datasheet**

| Parameter | CIR600-6X100 |
| --- | --- |
| Power |  |
| Rated power (kVA) | 600 |
| Active power (kW) | 600 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 97% |
| Battery DC bus | 480 V DC |
| Battery and runtime |  |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical |  |
| Form factor | Modular |
| Dimensions W × D × H | 31.5 × 39.4 × 78.7 in (800 × 1,001 × 1,999 mm) |
| Net weight | 1,514.5 lb (687 kg) |
| Footprint | 8.6 ft² (0.80 m²) |
| Common to every CIRRO |  |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 80 A settable charger |
| Display | personalized AEC red color touchscreen |
| Comms | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start |
| Battery, CIR600-6X100 | external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## CIR600-6X100: what people ask

#### What is the output current of the CIR600-6X100?

721.7 A per phase at full load: 600 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR600-6X100 from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the CIR600-6X100 give off?

About 20 kW, 67,680 BTU/h, at full load, where it is 96.8% efficient. Plan the room's cooling for a little more than that: the CIR600-6X100 is less efficient at part load and while its battery recharges.

#### Will the CIR600-6X100 fit through a standard door?

Yes: 31.5 in (800 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIR600-6X100 (size section above).

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

CIRRO

## Other CIRRO models

[The CIRRO series, with pictures](https://www.aecups.com/us/products/cirro/#models)

By power, the CIR600-6X100 is number 11 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the [CIR600-5X100](https://www.aecups.com/us/products/cirro/cir600-5x100/) (100 kVA less and 104 lb lighter). One size up is the [CIR800-7X100](https://www.aecups.com/us/products/cirro/cir800-7x100/) (100 kVA more and 284 lb heavier).

#### Every CIRRO model side by side (21)

**CIRRO models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model |
| --- | --- | --- | --- | --- |
| [CIR360-1X60](https://www.aecups.com/us/products/cirro/cir360-1x60/) | 60 kVA | 540 kVA less | 636 lb | 878 lb lighter |
| [CIR600-1X100](https://www.aecups.com/us/products/cirro/cir600-1x100/) | 100 kVA | 500 kVA less | 997 lb | 518 lb lighter |
| [CIR360-2X60](https://www.aecups.com/us/products/cirro/cir360-2x60/) | 120 kVA | 480 kVA less | 727 lb | 788 lb lighter |
| [CIR360-3X60](https://www.aecups.com/us/products/cirro/cir360-3x60/) | 180 kVA | 420 kVA less | 817 lb | 697 lb lighter |
| [CIR600-2X100](https://www.aecups.com/us/products/cirro/cir600-2x100/) | 200 kVA | 400 kVA less | 1,100 lb | 414 lb lighter |
| [CIR360-4X60](https://www.aecups.com/us/products/cirro/cir360-4x60/) | 240 kVA | 360 kVA less | 908 lb | 607 lb lighter |
| [CIR360-5X60](https://www.aecups.com/us/products/cirro/cir360-5x60/) | 300 kVA | 300 kVA less | 998 lb | 517 lb lighter |
| [CIR360-6X60](https://www.aecups.com/us/products/cirro/cir360-6x60/) | 360 kVA | 240 kVA less | 1,088 lb | 426 lb lighter |
| [CIR600-4X100](https://www.aecups.com/us/products/cirro/cir600-4x100/) | 400 kVA | 200 kVA less | 1,307 lb | 207 lb lighter |
| [CIR600-5X100](https://www.aecups.com/us/products/cirro/cir600-5x100/) | 500 kVA | 100 kVA less | 1,411 lb | 104 lb lighter |
| **CIR600-6X100** | 600 kVA | this page | 1,515 lb | this page |
| [CIR800-7X100](https://www.aecups.com/us/products/cirro/cir800-7x100/) | 700 kVA | 100 kVA more | 1,799 lb | 284 lb heavier |
| [CIR800-8X100](https://www.aecups.com/us/products/cirro/cir800-8x100/) | 800 kVA | 200 kVA more | 1,902 lb | 388 lb heavier |
| [CIR1200-9X100](https://www.aecups.com/us/products/cirro/cir1200-9x100/) | 900 kVA | 300 kVA more | 2,308 lb | 794 lb heavier |
| [CIR1200-10X100](https://www.aecups.com/us/products/cirro/cir1200-10x100/) | 1,000 kVA | 400 kVA more | 2,412 lb | 897 lb heavier |
| [CIR1200-11X100](https://www.aecups.com/us/products/cirro/cir1200-11x100/) | 1,100 kVA | 500 kVA more | 2,515 lb | 1,001 lb heavier |
| [CIR1200-12X100](https://www.aecups.com/us/products/cirro/cir1200-12x100/) | 1,200 kVA | 600 kVA more | 2,619 lb | 1,104 lb heavier |
| [CIR1600-13X100](https://www.aecups.com/us/products/cirro/cir1600-13x100/) | 1,300 kVA | 700 kVA more | 3,485 lb | 1,971 lb heavier |
| [CIR1600-14X100](https://www.aecups.com/us/products/cirro/cir1600-14x100/) | 1,400 kVA | 800 kVA more | 3,589 lb | 2,074 lb heavier |
| [CIR1600-15X100](https://www.aecups.com/us/products/cirro/cir1600-15x100/) | 1,500 kVA | 900 kVA more | 3,693 lb | 2,178 lb heavier |
| [CIR1600-16X100](https://www.aecups.com/us/products/cirro/cir1600-16x100/) | 1,600 kVA | 1,000 kVA more | 3,796 lb | 2,282 lb heavier |

Install and run it: [RADIANT and CIRRO operating guide](https://www.aecups.com/us/support/guides/radiant-cirro/)

## The CIR600-6X100 for your project

Send the load, the voltage and the minutes you need from the CIR600-6X100. We reply with the configuration, the batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20CIR600-6X100%20(CIRRO)%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)
