# Data center UPS: from a 60 kW edge room to 12 MW at 480 V

A data center UPS carries the IT load from the utility's failure until the generator holds it, and keeps doing so with one of its parts out for service. AEC answers by load band: lithium towers and RADIANT at 208 V for edge rooms, CIRRO and INFINITE frames at 480 V, and INFINITE 1.5MW, 1,500 kVA per frame, up to 8 frames in parallel.

By load band N+1, 2N or three systems [Every modular frame](https://www.aecups.com/us/products/modular-ups/)

By load band

## Which AEC architecture fits which room

One load worked in each band with N+1 and the 80% rule of the RADIANT-IB manual: the frame, the modules installed and each module's share in normal running. Floor: the UPS frames only.

**AEC UPS for data centers by load band, US catalog 2026**

| Band | AEC ranges | Load worked | Frame and modules, N+1 | Floor |
| --- | --- | --- | --- | --- |
| Edge and network rooms | ETHERNO towers, 10–30 kVA with lithium inside; RADIANT (15 kVA modules) and RADIANT-IB (batteries inside), 208Y/120 V. | 60 kW | [RADIANT 90](https://www.aecups.com/us/products/radiant/): 6 × 15 kVA in 6 slots, each at 67%, 94% | 4 ft² |
| Server rooms and small halls | CIRRO-IB and CIRRO at 480Y/277 V; INFINITE at 480 V 3-wire, up to 3 frames, 600 kVA. | 250 kW | [CIRRO 600](https://www.aecups.com/us/products/cirro/): 5 × 100 kVA in 6 slots, each at 50%, 96.9%or 2 × [INFINITE 200](https://www.aecups.com/us/products/infinite/): 5 × 100 kVA in 6 slots, each at 50%, 97.3% | 8.6 ft² |
| Colocation and enterprise halls | CIRRO 800 to 1600 (N+1 up to 1,500 kW in one frame) or INFINITE 1.5MW (1,375 kW N+1 per frame). | 900 kW | [INFINITE 1.5MW](https://www.aecups.com/us/products/infinite-1-5mw/): 10 × 125 kVA in 12 slots, each at 72%or [CIRRO 1600](https://www.aecups.com/us/products/cirro/): 13 × 100 kVA in 16 slots, each at 69%, 97% | 19.4 ft² |
| Megawatt blocks | INFINITE 1.5MW, up to 8 frames in parallel: 12 MW; CIRRO 1600, up to 8: 12.8 MW. | 4,000 kW | 4 × [INFINITE 1.5MW](https://www.aecups.com/us/products/infinite-1-5mw/): 41 × 125 kVA in 48 slots, each at 78%or 4 × [CIRRO 1600](https://www.aecups.com/us/products/cirro/): 51 × 100 kVA in 64 slots, each at 78%, 97% | 77.5 ft² |

Below the modular range: [ETHERNO](https://www.aecups.com/us/products/etherno/) 10–30 kVA with 50 Ah lithium modules inside the tower, and LUMINA 1–3 kVA in a 2U rack for a single rack. Other loads: [the frame for each load](https://www.aecups.com/us/products/modular-ups/#pick).

Redundancy, counted

## One 1,000 kW load, three ways

The same critical load at 480 V, each scheme with the 80% rule on what has to carry it after a failure. More modules in all means each one runs lighter, so the efficiency on the curve moves with the scheme.

### CIRRO, 100 kVA modules, 480Y/277 V 4-wire

**1,000 kW on AEC CIRRO frames: N+1, 2N and three shared systems**

| Scheme | Frames | Modules in all | Each module, normal running | Efficiency, heat at 1,000 kW | Frames: floor, weight | Survives |
| --- | --- | --- | --- | --- | --- | --- |
| N+1 in one system | 1 × [CIRRO 1600](https://www.aecups.com/us/products/cirro/), 14 modules each | 14 | 71% | 97%, 31.1 kW | 17.2 ft², 3,589 lb | one power module out or failed |
| 2N: two systems, each for the whole load | 2 × [CIRRO 1600](https://www.aecups.com/us/products/cirro/), 13 modules each | 26 | 38% | 96.6%, 35.4 kW | 34.5 ft², 6,971 lb | a whole system, its bypass or its feed out (dual-corded loads) |
| Three systems, any two carry the load | 3 × [CIRRO 800](https://www.aecups.com/us/products/cirro/), 7 modules each | 21 | 48% | 96.8%, 32.7 kW | 25.9 ft², 5,396 lb | a whole system out; the other two take its share (dual-corded loads or static transfer switches) |

### INFINITE 1.5MW, 125 kVA silicon carbide modules, 480 V 3-wire

**1,000 kW on AEC INFINITE 1.5MW frames: N+1, 2N and three shared systems**

| Scheme | Frames | Modules in all | Each module, normal running | Efficiency, heat at 1,000 kW | Frames: floor, weight | Survives |
| --- | --- | --- | --- | --- | --- | --- |
| N+1 in one system | 1 × [INFINITE 1.5MW](https://www.aecups.com/us/products/infinite-1-5mw/), 11 modules each | 11 | 73% | — | 19.4 ft², 5,983 lb | one power module out or failed |
| 2N: two systems, each for the whole load | 2 × [INFINITE 1.5MW](https://www.aecups.com/us/products/infinite-1-5mw/), 10 modules each | 20 | 40% | — | 38.8 ft², 11,728 lb | a whole system, its bypass or its feed out (dual-corded loads) |
| Three systems, any two carry the load | 3 × [INFINITE 1.5MW](https://www.aecups.com/us/products/infinite-1-5mw/), 6 modules each | 18 | 44% | — | 58.1 ft², 16,163 lb | a whole system out; the other two take its share (dual-corded loads or static transfer switches) |

Efficiency in double conversion on the CIRRO 600–1600 curve of the 2026 catalog; INFINITE 1.5MW has no published curve, its catalog gives up to 97.5% AC/AC. Weights: the frames and their modules, without batteries. 2N and three-system schemes need loads with two cords or static transfer switches downstream; the UPS does not make that choice.

480 V or 208 V

## What the voltage does to the copper

At the same power, 480 V carries 43% of the current of 208 V. A 1,500 kVA INFINITE 1.5MW frame at full load: about 1,804 A per phase; the same power at 208 V would be 4,164 A. That is why the data center ranges above 150 kVA are 480 V only, and why 208 V stops at the edge room: RADIANT-IB at 100 kVA already carries about 278 A per phase at its output.

4-wire or 3-wire decides the series: CIRRO and CIRRO-IB need the neutral of 480Y/277 V; INFINITE and INFINITE 1.5MW take 480 V delta. [208 V or 480 V UPS](https://www.aecups.com/us/blog/208v-vs-480v-ups/)

Battery

## Minutes, floor and fire code

**Lithium.** INFINITE 1.5MW takes 4, 6 or 8 L6 cabinets: 80, 120 or 160 modules of 50 Ah, 10 kW each, so 4 cabinets carry up to 800 kW and 6 up to 1,200 kW (2026 catalog). On INFINITE, one cabinet of 20 modules runs 200 kW for 15 minutes. A full cabinet weighs 2,171.6 lb on 23.6 × 33.5 in, about 396 lb/ft² for the structural engineer. The 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested: the module, not a UL 9540 listing of the cabinet or the system. [Lithium UPS and the fire code](https://www.aecups.com/us/blog/lithium-ups-fire-code/)

**Lead-acid.** CIRRO and INFINITE run on an external VRLA bank, 40 blocks of 12 V by default; the series pages list the cabinets and strings for 5 to 30 minutes. [INFINITE with L6 cabinets](https://www.aecups.com/us/products/infinite-l6-lithium/) sets each lithium set beside the lead-acid bank for the same minutes.

In service

## Where AEC UPS protect servers

[A resort in the Dominican Republic](https://www.aecups.com/us/projects/lumina-radiant-dominican-resort/): 10 parallel pairs of RADIANT-IB 20 kVA, 208 V, for its servers and payment systems, with 44 LUMINA lithium rack UPS. [MARTA, Atlanta](https://www.aecups.com/us/projects/lumina-ferrus-sp-marta-atlanta/): 56 LUMINA 2 kVA and 11 FERRUS SP 10 kVA for its data rooms, all on the network. More in [projects](https://www.aecups.com/us/projects/).

Before the order

## Check it on your own room

[Room fit](https://www.aecups.com/us/tools/room-fit/) places the frames and the battery cabinets on your floor plan · [the 3D viewers](https://www.aecups.com/us/3d/) open INFINITE 1.5MW in X-ray · [UPS sizing](https://www.aecups.com/us/tools/ups-sizing/) · [battery runtime](https://www.aecups.com/us/tools/battery-runtime/) · [containerized UPS](https://www.aecups.com/us/products/containerized-ups/), INFINITE, L6 and switchgear in one container · [example designs](https://www.aecups.com/us/example-designs/) · [the data center UPS guide](https://www.aecups.com/us/blog/data-center-ups/)

The ranges

## The data center series

### CIRRO

4-wire · 3P+N VRLA

60–1,600 kVA · 480 V 4-wire · 3P+N

Modular online UPS with N+X redundancy for three-phase 480 V, 4-wire loads from 60 to 1,600 kVA, with an external VRLA battery bank.

View series

### INFINITE

3-wire · Delta Lithium or VRLA

100–600 kVA · 480 V 3-wire · Delta

Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 100 to 600 kVA, with external lithium battery cabinets.

View series

### INFINITE 1.5MW

3-wire · Delta Lithium or VRLA

750–1,500 kVA · 480 V 3-wire · Delta

Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 750 to 1,500 kVA, with external lithium battery cabinets.

View series

Data center UPS

## Questions people ask

#### What size UPS does a data center need?

The IT load in kW at full build-out, the redundancy the design asks for, and the minutes to carry it until the generator holds the load. The UPS's rating is then the load divided by the share each system may carry: all of it in N+1, all of it on each side of 2N, half of it in each of three shared systems.

#### N+1 or 2N?

N+1 covers a power module: one can fail or be serviced and the load stays on the inverter. It does not cover what the modules share, the frame's bypass, output and feed. 2N does, with two complete systems feeding dual-corded loads; it takes about twice the modules.

#### What is distributed redundancy?

Three or more UPS systems share the load so that, if one stops, the others carry its share. With three systems, each is sized for half the load and runs at a third of it: for 1,000 kW, three CIRRO 800 frames of 7 modules, 21 modules in all against 26 for 2N.

#### Can a data center UPS run on lithium?

Yes: INFINITE and INFINITE 1.5MW run on L6 lithium cabinets of 50 Ah modules. A full cabinet holds 57.6 kWh nominal and weighs 2,171.6 lb, about 396 lb/ft² on its footprint. The 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested.

#### Which AEC data center UPS is UL listed?

INFINITE 1.5MW: [UL 1778](https://www.shopulstandards.com/ProductDetail.aspx?productId=UL1778) listed, UL file E543003 (AEC UPS USA LLC). CIRRO and INFINITE 100–600: built to UL 1778, as the legal notice states; "built to" means the series follows the standard without carrying a listing mark.

#### How fast can a data center UPS grow?

By module, with the load on: a CIRRO 1600 goes from 2 to 16 modules in one frame, an INFINITE 1.5MW from 6 to 12; then frames in parallel, up to 8 of each.

## Size the UPS for your data hall

Send the IT load today and at build-out, the redundancy, the supply and the minutes: we answer with the frames, the modules and the batteries.

[Send your project](https://www.aecups.com/us/contacts/#form) [+1 786 553 2100](tel:+17865532100)