title: "20 kVA 208V UPS, 3 × 50 Ah lithium: AEC ETH20-3X50A-LI"
url: https://www.aecups.com/us/products/etherno/eth20-3x50a-li/
description: "AEC ETHERNO ETH20-3X50A-LI: 20 kVA / 20 kW online UPS for 208 V three-phase, three 50 Ah lithium modules. 20 min at full load, 41 min at half load."
language: en-US
---

ETHERNO · 208V three-phase UPS

# ETH20-3X50A-LI ETHERNO 20 kVA, 208V three-phase UPS

Lithium 20 kVA Online double conversion

The AEC ETHERNO ETH20-3X50A-LI is a 20 kVA / 20 kW online double-conversion UPS for 208 V three-phase loads, with three 50 Ah lithium modules: 20 minutes at full load, 41 at half load. Kept at 80 % of its rating, it carries loads up to 16 kW.

**20 kVA / 20 kW** Rating

**12.6 × 39.1 × 49.2 in** W × D × H

**471.8 lb** Weight

**Lithium, internal** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_ETHERNO_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20ETH20-3X50A-LI%20(ETHERNO)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/eth/v59/#eth20-3)

Series picture.

Drag to turn

In 3D

## Look around the ETH20-3X50A-LI

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/eth/v59/#eth20-3)

The turntable shows the 30K · 3 modules configuration; the full 3D view opens on this model.

The same on every ETHERNO: [Open the ETHERNO: modules and door, from the catalog's photos](https://www.aecups.com/us/products/etherno/#explore) [The ETHERNO display](https://www.aecups.com/us/products/etherno/#display)

Runtime

## ETHERNO 20 kVA · 3 lithium modules at your load.

The same chart as the [ETHERNO page](https://www.aecups.com/us/products/etherno/#runtime): this model in bold, the other set-ups faded behind it to compare. 2026 catalog, new batteries.

50 %

ETHERNO 10 kVA · 1 lithium module and 2 more, same minutes ETHERNO 10 kVA · 2 lithium modules ETHERNO 10 kVA · 3 lithium modules ETHERNO 20 kVA · 3 lithium modules

At 50 % of the rating

ETHERNO 20 kVA

**This model 3 lithium modules **41 min**

ETHERNO 10 kVA

[**1 lithium module **27 min**](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) [**2 lithium modules **55 min**](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) [**3 lithium modules **82 min**](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/)

ETHERNO 20 kVA

[**2 lithium modules **27 min**](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/)

ETHERNO 30 kVA

[**3 lithium modules **27 min**](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/)

#### Table: this model at 25, 50, 75 and 100 % load

| Model | 25% load | 50% load | 75% load | 100% load |
| --- | --- | --- | --- | --- |
| **ETHERNO 20 kVA · 3 lithium modules** ETH20-3X50A-LI | 84 min | 41 min | 26.5 min | 20 min |

[Every ETHERNO set-up in one table](https://www.aecups.com/us/products/etherno/#runtime)

From the 2026 catalog

## What is the ETH20-3X50A-LI?

The code ETH20-3X50A-LI orders these catalog items, shipped in 4 cartons:

- 1 × [ETH20](https://www.aecups.com/us/products/etherno/eth20/): 20 kVA tower, without batteries, 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm), 227 lb (103 kg)
- 3 × ETH-50-LI: 50 Ah LiFePO4 lithium module, 81.6 lb (37 kg) each
- Output: 20,000 VA / 20,000 W (unity power factor, kVA = kW).
- Battery: 3 × hot-swappable LiFePO4 50 Ah lithium modules; 15-year module life; recharge < 2 h.

The lines every ETHERNO shares, from technology to warranty, are in the [ETHERNO key facts](https://www.aecups.com/us/products/etherno/#overview) and in the datasheet below.

Size and floor

## How big it is

12.6" W × 39.1" D × 49.2" H (320 × 993 × 1,250 mm); 471.8 lb (214 kg) net. It ships in 4 cartons, 543.9 lb (246.7 kg) gross in all.

**3.4 ft²** footprint (0.32 m²)

**138 lb/ft²** floor load of the cabinet alone

**Tower** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## ETH20-3X50A-LI datasheet.

The ETH20-3X50A-LI in the AEC 2026 catalog, figure by figure. [Compare it with every ETHERNO model](https://www.aecups.com/us/products/etherno/#datasheet).

**ETH20-3X50A-LI datasheet**

| Parameter | ETH20-3X50A-LI |
| --- | --- |
| Power |  |
| Rated power (kVA) | 20 |
| Active power (kW) | 20 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online Double Conversion |
| Efficiency, up to | 94% |
| Battery DC bus | 240 V DC |
| Battery and runtime |  |
| Battery type | Lithium LiFePO4 |
| Battery configuration | Internal |
| Runtime at 50 % load | 41 min |
| Runtime at 100 % load | 20 min |
| Mechanical |  |
| Form factor | Tower |
| Dimensions W × D × H | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) |
| Net weight | 471.8 lb (214 kg) |
| Footprint | 3.4 ft² (0.32 m²) |
| Shipping |  |
| Cartons | 4 |
| Shipping weight | 543.9 lb |
| Common to every ETHERNO |  |
| Technology | 3-level IGBT; cold start, self-cleaning and smart functions |
| Display | 4.3-inch color touchscreen |
| Comms | Modbus and dry contacts, standard |
| Battery, ETH20-3X50A-LI | 3 × hot-swappable LiFePO4 50 Ah lithium modules; 15-year module life; recharge < 2 h |
| Network card | SNMP-L (SNMP) |
| Warranty | 5 years |
| Certification | [UL 1778](https://www.shopulstandards.com/ProductDetail.aspx?productId=UL1778) listed, UL file E543003 (AEC UPS USA LLC) |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## ETH20-3X50A-LI: what people ask

#### How long does the ETH20-3X50A-LI run on battery?

20 min at 100 % load (20 kW), 41 min at 50 % load (10 kW), 3 h 19 min at 10 % load (2.0 kW), from the catalog runtime table at the start of battery life. Runtime falls faster than the load rises, so the ETH20-3X50A-LI chart above gives the minutes at any load in between.

#### What is the output current of the ETH20-3X50A-LI?

55.5 A per phase at full load: 20 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the ETH20-3X50A-LI from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the ETH20-3X50A-LI give off?

About 1.3 kW, 4,510 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the ETH20-3X50A-LI is less efficient at part load and while its battery recharges.

#### Will the ETH20-3X50A-LI fit through a standard door?

Yes: 12.6 in (320 mm) across its narrow side and 49.2 in (1,250 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the ETH20-3X50A-LI (size section above).

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

ETHERNO

## Other ETHERNO models

[The ETHERNO series, with pictures](https://www.aecups.com/us/products/etherno/#models)

By power, the ETH20-3X50A-LI is number 2 of 3 in the ETHERNO series, which runs from 10 to 30 kVA. One size down are the [ETH10](https://www.aecups.com/us/products/etherno/eth10/), [ETH10-1X50A-LI](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/), [ETH10-2X50A-LI](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) and [ETH10-3X50A-LI](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/), all 10 kVA less. One size up are the [ETH30](https://www.aecups.com/us/products/etherno/eth30/) and [ETH30-3X50A-LI](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/), all 10 kVA more. The same 20 kVA also comes as the [ETH20](https://www.aecups.com/us/products/etherno/eth20/) and [ETH20-2X50A-LI](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/): the table below gives each one's weight and battery.

#### Every ETHERNO model side by side (9)

**ETHERNO models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load | Battery configuration |
| --- | --- | --- | --- | --- | --- | --- |
| [ETH10](https://www.aecups.com/us/products/etherno/eth10/) | 10 kVA | 10 kVA less | 216 lb | 256 lb lighter | — | Lithium modules inside, ordered separately |
| [ETH10-1X50A-LI](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) | 10 kVA | 10 kVA less | 298 lb | 174 lb lighter | 27 min at 50 % load | Internal |
| [ETH10-2X50A-LI](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) | 10 kVA | 10 kVA less | 379 lb | 93 lb lighter | 55 min at 50 % load | Internal |
| [ETH10-3X50A-LI](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/) | 10 kVA | 10 kVA less | 461 lb | 11 lb lighter | 82 min at 50 % load | Internal |
| [ETH20](https://www.aecups.com/us/products/etherno/eth20/) | 20 kVA | the same power | 227 lb | 245 lb lighter | — | Lithium modules inside, ordered separately |
| [ETH20-2X50A-LI](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) | 20 kVA | the same power | 390 lb | 82 lb lighter | 27 min at 50 % load | Internal |
| **ETH20-3X50A-LI** | 20 kVA | this page | 472 lb | this page | 41 min at 50 % load | Internal |
| [ETH30](https://www.aecups.com/us/products/etherno/eth30/) | 30 kVA | 10 kVA more | 240 lb | 232 lb lighter | — | Lithium modules inside, ordered separately |
| [ETH30-3X50A-LI](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/) | 30 kVA | 10 kVA more | 485 lb | 13 lb heavier | 27 min at 50 % load | Internal |

Install and run it: [ETHERNO operating guide](https://www.aecups.com/us/support/guides/etherno/) [Guide specification, CSI 26 33 53](https://www.aecups.com/us/products/etherno-guide-specification/)

## The ETH20-3X50A-LI for your project

Send the load, the voltage and the minutes you need from the ETH20-3X50A-LI. We reply with the configuration, the batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20ETH20-3X50A-LI%20(ETHERNO)%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)