# ETHERNO online UPS, 10–30 kVA, 208 V, hot-swappable lithium modules

Lithium Online double conversion Tower

ETHERNO is AEC's online double-conversion UPS for three-phase 208 V loads from 10 to 30 kVA, in a tower cabinet, with hot-swappable 50 Ah lithium modules. Each 50 Ah module adds minutes: at full load the 10 kVA model runs 14, 27 or 41 minutes with one, two or three modules.

**10–30** kVA

**94%** Efficiency, up to

**1.0** Power factor

**5 yr** Warranty

Datasheet Manuals and catalogs [Guide specification (CSI)](https://www.aecups.com/us/products/etherno-guide-specification/) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20ETHERNO%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/eth/v59/)

Drag to turn

In 3D

## Look around the ETHERNO

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/eth/v59/)

Rendered from AEC's 3D model of the ETHERNO 10–30 kVA. The full 3D view zooms in, opens the unit and names every part.

Hands on

## Open the ETHERNO 30 kVA yourself.

Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.

[Every part in 3D](https://www.aecups.com/assets/models3d/eth/v59/)

Efficiency

## How efficient is the ETHERNO at your load?

The ETHERNO in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.

**—** %

**Load**: —

**Lost as heat**: —

**Heat to remove**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at per kWh**: —

Runtime

## How long does each ETHERNO model run at your load?

From the 2026 catalog's runtime tables, new batteries. Drag the load, type it in kW, or move along the chart. Click a model for its page.

50 %

ETHERNO 10 kVA · 1 lithium module and 2 more, same minutes ETHERNO 10 kVA · 2 lithium modules ETHERNO 10 kVA · 3 lithium modules ETHERNO 20 kVA · 3 lithium modules

At 50 % of the rating

ETHERNO 10 kVA

[**1 lithium module **27 min**](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) [**2 lithium modules **55 min**](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) [**3 lithium modules **82 min**](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/)

ETHERNO 20 kVA

[**2 lithium modules **27 min**](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) [**3 lithium modules **41 min**](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/)

ETHERNO 30 kVA

[**3 lithium modules **27 min**](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/)

#### Table: every model at 25, 50, 75 and 100 % load

| Model | 25% load | 50% load | 75% load | 100% load |
| --- | --- | --- | --- | --- |
| [ETHERNO 10 kVA · 1 lithium module](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) ETH10-1X50A-LI | 55 min | 27 min | 17.5 min | 14 min |
| [ETHERNO 10 kVA · 2 lithium modules](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) ETH10-2X50A-LI | 111 min | 55 min | 35 min | 27 min |
| [ETHERNO 10 kVA · 3 lithium modules](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/) ETH10-3X50A-LI | 166 min | 82 min | 53 min | 41 min |
| [ETHERNO 20 kVA · 2 lithium modules](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) ETH20-2X50A-LI | 55 min | 27 min | 17.5 min | 14 min |
| [ETHERNO 20 kVA · 3 lithium modules](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/) ETH20-3X50A-LI | 84 min | 41 min | 26.5 min | 20 min |
| [ETHERNO 30 kVA · 3 lithium modules](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/) ETH30-3X50A-LI | 55 min | 27 min | 17.5 min | 14 min |

The display

## The ETHERNO display.

The real touchscreen, from the user manual: pick a UPS state (normal, battery, bypass) or a main page, or touch the screen as on the UPS.

UPS state

ETHERNO · the real screen

### Normal

Normal: the rectifier and inverter carry the load and charge the lithium modules.

**Main pages**

**ETHERNO in 3D, the display** The camera moves in to the display. · 0:06

What is what

## Inside the ETHERNO, part by part.

Each number is named in the list under its picture: the front with its door open and the rear, side by side.

### Front, door open

1. **4.3-inch touchscreen and ON/OFF keys** On the upper front, above the door.
2. **Front breakers** Behind the door, above the lithium modules.
3. **50 Ah lithium modules, up to three** LiFePO4, 37 kg each. They slide out from the front while the UPS keeps the load on.

### Rear

1. **Slot 1 and slot 2** Option cards: the SNMP network card in slot 1; a dry-contact kit, a Modbus protocol kit or a second SNMP card in slot 2.
2. **Parallel port** Up to four ETHERNO in parallel, for redundancy or more power, with the parallel kit.
3. **Communication terminals** RS485 Modbus (A+ / B−), five dry-contact outputs, one settable input and the EPO input. Standard.
4. **Cooling fans** Front-to-back airflow; the UPS runs its self-cleaning fan cycles on its own.
5. **Bypass breaker** The static bypass supply.
6. **Output breaker** To the load.
7. **BATT. Start** Cold start: powers the UPS up from the lithium modules when there is no mains.
8. **Maintenance bypass** Under its cover. Taking the cover off moves the UPS to bypass by itself; then the manual breaker feeds the load while the UPS is serviced.
9. **Input breaker** The rectifier's mains supply, 208 V three-phase.
10. **Wiring box** Input, bypass, output and ground terminals behind a bolted cover.

Hands on

## Open the ETHERNO.

The catalog's own photos: click the door, take modules out and put them back.

Click the door · drag to turn

ETHERNO · 208 V three-phase · lithium

### Lithium modules behind the door, hot-swappable.

Power

Model **—**

Lithium modules **—**

Load **—**

Runtime **—**

The modules are LiFePO4, 50 Ah and 37 kg each. They slide out from the front while the UPS keeps the load on, and the runtime follows the modules left inside.

[Try its display](https://www.aecups.com/us/tools/simulators/#panel-etherno)

Overview

## Key facts

**Power range**: 10–30 kVA

**Input / Output**: 208 V three-phase

**Technology**: 3-level IGBT; cold start, self-cleaning and smart functions

**Display**: 4.3-inch color touchscreen

**Comms**: Modbus and dry contacts, standard

**Battery**: hot-swappable 50 Ah lithium modules

**Power factor**: 1.0 (kVA = kW)

**Network card**: SNMP-L (SNMP)

**Warranty**: 5 years

**Certification**: [UL 1778](https://www.shopulstandards.com/ProductDetail.aspx?productId=UL1778) listed, UL file E543003 (AEC UPS USA LLC)

**Quality system**: ISO 9001:2015, the group's quality system (SGS)

Inside the module

## The 50 Ah LiFePO4 module, opened: its cells, its BMS and why every module works on its own.

[Open the module](https://www.aecups.com/us/products/lithium-batteries/#lithium-module)

Models

## Which ETHERNO fits your load?

9 models for the US market, from the 2026 catalog. Pick the power, open a model for its full datasheet.

[**ETH10** 10 kVA · 10 kW lithium frame only **216 lb** net weight **Lithium modules inside, ordered separately** batteries Details and datasheet](https://www.aecups.com/us/products/etherno/eth10/) [**ETH10-1X50A-LI** 10 kVA · 10 kW 1 × 50 Ah lithium **27 min** at 50 % load **297.6 lb** net weight Details and datasheet](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) [**ETH10-2X50A-LI** 10 kVA · 10 kW 2 × 50 Ah lithium **55 min** at 50 % load **379.2 lb** net weight Details and datasheet](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) [**ETH10-3X50A-LI** 10 kVA · 10 kW 3 × 50 Ah lithium **82 min** at 50 % load **460.8 lb** net weight Details and datasheet](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/) [**ETH20** 20 kVA · 20 kW lithium frame only **227 lb** net weight **Lithium modules inside, ordered separately** batteries Details and datasheet](https://www.aecups.com/us/products/etherno/eth20/) [**ETH20-2X50A-LI** 20 kVA · 20 kW 2 × 50 Ah lithium **27 min** at 50 % load **390.2 lb** net weight Details and datasheet](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) [**ETH20-3X50A-LI** 20 kVA · 20 kW 3 × 50 Ah lithium **41 min** at 50 % load **471.8 lb** net weight Details and datasheet](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/) [**ETH30** 30 kVA · 30 kW lithium frame only **240.2 lb** net weight **Lithium modules inside, ordered separately** batteries Details and datasheet](https://www.aecups.com/us/products/etherno/eth30/) [**ETH30-3X50A-LI** 30 kVA · 30 kW 3 × 50 Ah lithium **27 min** at 50 % load **485 lb** net weight Details and datasheet](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/)

### Options and parts for ETHERNO

- **ETH-50-LI** Lithium Module 50 Ah — ETHERNO 8.8" W × 26.2" D × 6" H (223 × 665 × 152 mm) · 81.6 lb (37 kg)

Datasheet

## ETHERNO datasheet.

Every model side by side. Filter by power, keep only what differs, print it or take it as CSV.

**ETHERNO datasheet, 9 models**

| Model | [ETH10](https://www.aecups.com/us/products/etherno/eth10/) | [ETH10-1X50A-LI](https://www.aecups.com/us/products/etherno/eth10-1x50a-li/) | [ETH10-2X50A-LI](https://www.aecups.com/us/products/etherno/eth10-2x50a-li/) | [ETH10-3X50A-LI](https://www.aecups.com/us/products/etherno/eth10-3x50a-li/) | [ETH20](https://www.aecups.com/us/products/etherno/eth20/) | [ETH20-2X50A-LI](https://www.aecups.com/us/products/etherno/eth20-2x50a-li/) | [ETH20-3X50A-LI](https://www.aecups.com/us/products/etherno/eth20-3x50a-li/) | [ETH30](https://www.aecups.com/us/products/etherno/eth30/) | [ETH30-3X50A-LI](https://www.aecups.com/us/products/etherno/eth30-3x50a-li/) |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| Power |  |  |  |  |  |  |  |  |  |
| Rated power (kVA) | 10 | 10 | 10 | 10 | 20 | 20 | 20 | 30 | 30 |
| Active power (kW) | 10 | 10 | 10 | 10 | 20 | 20 | 20 | 30 | 30 |
| Output power factor | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
| Electrical |  |  |  |  |  |  |  |  |  |
| Input / output | 208 V three-phase | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online Double Conversion | Online Double Conversion | Online Double Conversion | Online Double Conversion | Online Double Conversion | Online Double Conversion | Online Double Conversion | Online Double Conversion | Online Double Conversion |
| Efficiency, up to | 94% | 94% | 94% | 94% | 94% | 94% | 94% | 94% | 94% |
| Battery DC bus | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC |
| Battery and runtime |  |  |  |  |  |  |  |  |  |
| Battery type | Not included, ordered separately | Lithium LiFePO4 | Lithium LiFePO4 | Lithium LiFePO4 | Not included, ordered separately | Lithium LiFePO4 | Lithium LiFePO4 | Not included, ordered separately | Lithium LiFePO4 |
| Battery configuration | Lithium modules inside, ordered separately | Internal | Internal | Internal | Lithium modules inside, ordered separately | Internal | Internal | Lithium modules inside, ordered separately | Internal |
| Runtime at 50 % load | — | 27 min | 55 min | 82 min | — | 27 min | 41 min | — | 27 min |
| Runtime at 100 % load | — | 14 min | 27 min | 41 min | — | 14 min | 20 min | — | 14 min |
| Mechanical |  |  |  |  |  |  |  |  |  |
| Form factor | Tower | Tower | Tower | Tower | Tower | Tower | Tower | Tower | Tower |
| Dimensions W × D × H | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) |
| Net weight | 216 lb (98 kg) | 297.6 lb (135 kg) | 379.2 lb (172 kg) | 460.8 lb (209 kg) | 227 lb (103 kg) | 390.2 lb (177 kg) | 471.8 lb (214 kg) | 240.2 lb (109 kg) | 485 lb (220 kg) |
| Footprint | 3.4 ft² (0.32 m²) | 3.4 ft² (0.32 m²) | 3.4 ft² (0.32 m²) | 3.4 ft² (0.32 m²) | 3.4 ft² (0.32 m²) | 3.4 ft² (0.32 m²) | 3.4 ft² (0.32 m²) | 3.4 ft² (0.32 m²) | 3.4 ft² (0.32 m²) |
| Shipping |  |  |  |  |  |  |  |  |  |
| Cartons | 1 | 2 | 3 | 4 | 1 | 3 | 4 | 1 | 4 |
| Shipping weight | 268.9 lb | 356.9 lb | 444.9 lb | 532.9 lb | 279.9 lb | 455.9 lb | 543.9 lb | 293.1 lb | 557.1 lb |

From the AEC 2026 catalog. Efficiency is the catalog's “up to” figure; runtimes are AEC's runtime tables with new batteries; weights are the unit alone, without batteries outside it. Figures can change: the order confirmation rules.

Install and run it: [ETHERNO operating guide](https://www.aecups.com/us/support/guides/etherno/) [Guide specification, CSI 26 33 53](https://www.aecups.com/us/products/etherno-guide-specification/)

Plan it: [Size it for your load](https://www.aecups.com/us/tools/ups-sizing/) [Battery runtime](https://www.aecups.com/us/tools/battery-runtime/) [Room fit](https://www.aecups.com/us/tools/room-fit/) [ETHERNO compared with other makers](https://www.aecups.com/us/comparisons/three-phase-ups-10-30-kva-208v/) [Warranty terms](https://www.aecups.com/us/warranty/)

Replacing another brand's UPS? [Type its model number: the AEC match](https://www.aecups.com/us/cross-reference/)

ETHERNO: quick answers

## Questions people ask

#### How long does ETHERNO run on battery at 20 kVA?

At a full 20 kW load, the ETH20-2X50A-LI (two 50 Ah lithium modules) runs 14 min and the ETH20-3X50A-LI (three 50 Ah lithium modules) runs 20 min; at half load, 27 min and 41 min. Figures from the 2026 catalog runtime tables, with new batteries.

#### Can the ETHERNO lithium modules be changed with the load on?

Yes. ETHERNO takes hot-swappable 50 Ah lithium modules: a module comes out and goes back in while the UPS carries the load. The catalog sets it up with one, two or three modules at 10 kVA; two or three modules at 20 kVA; three modules at 30 kVA.

#### What supply does ETHERNO need?

208 V three-phase, 4-wire (3P+N), for every model from 10 to 30 kVA. Its power factor is 1.0 (kVA = kW), so the 20 kVA model delivers 20 kW.

#### What warranty does ETHERNO have?

5 years, lithium modules included, from start-up. Register the UPS with AEC after start-up.

[How long does each ETHERNO model run on battery?](https://www.aecups.com/us/faq/etherno/#q1) [What is the output current of each ETHERNO model?](https://www.aecups.com/us/faq/etherno/#q2) [How much heat does each ETHERNO model give off?](https://www.aecups.com/us/faq/etherno/#q3) [All 8 questions](https://www.aecups.com/us/faq/etherno/)

Also in 208V three-phase UPS: [AUREON](https://www.aecups.com/us/products/aureon/) [RADIANT](https://www.aecups.com/us/products/radiant/) [RADIANT-IB](https://www.aecups.com/us/products/radiant-ib/) [Compare the range](https://www.aecups.com/us/products/three-phase-ups-208v/)

Read next: [Lithium UPS fire code: NFPA 855, UL 9540A and 20 kWh](https://www.aecups.com/us/blog/lithium-ups-fire-code/) [Modular vs monolithic UPS, 208 V: space, N+1, service](https://www.aecups.com/us/blog/modular-vs-monolithic-ups/) [How long will a UPS run? Battery runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/)

## The ETHERNO for your project

Send the load, the voltage and the minutes. We reply with the ETHERNO model that fits, its batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20ETHERNO%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)