title: "1.5 kVA UPS, rack/tower, 4 × 9 Ah VRLA: AEC FERRUS RT"
url: https://www.aecups.com/us/products/ferrus-rt/fer1500rt-4x9/
description: "AEC FERRUS RT FER1500RT-4X9: 1.5 kVA / 1.5 kW online UPS for 120 V single-phase, internal VRLA batteries."
language: en-US
---

FERRUS RT · 120V single-phase UPS

# FER1500RT-4X9 FERRUS RT 1.5 kVA, 120V single-phase UPS

VRLA 1.5 kVA Online double conversion

The AEC FERRUS RT FER1500RT-4X9 is a 1.5 kVA / 1.5 kW online double-conversion UPS for 120 V single-phase loads, with internal VRLA batteries. Kept at 80 % of its rating, it carries loads up to 1.2 kW.

**1.5 kVA / 1.5 kW** Rating

**17.3 × 17.3 × 3.4 in** W × D × H

**48.5 lb** Weight

**VRLA, internal** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_FERRUS_RT_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20single-phase&msg=About%20the%20FER1500RT-4X9%20(FERRUS%20RT)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/ferrt/v47/#fer1-5)

Drag to turn

In 3D

## Look around the FER1500RT-4X9

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/ferrt/v47/#fer1-5)

The turntable shows the 3K configuration; the full 3D view opens on this model.

Load by load

## The FER1500RT-4X9 at 25, 50, 75 and 100 % load.

Its 1.5 kW rating in four steps, worked out from its own catalog figures.

**At 25, 50, 75 and 100 % load**

| Load | Output current, at 120 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
| --- | --- | --- | --- | --- |
| 25 % of the FER1500RT-4X9, 375 W | 3.1 A at the output | 89.2 % efficient | 45 W of heat | 150 BTU/h to cool |
| 50 % of the FER1500RT-4X9, 750 W | 6.3 A at the output | 92.5 % efficient | 61 W of heat | 210 BTU/h to cool |
| 75 % of the FER1500RT-4X9, 1.1 kW | 9.4 A at the output | 93.0 % efficient | 85 W of heat | 290 BTU/h to cool |
| 100 % of the FER1500RT-4X9, 1.5 kW | 12.5 A at the output | 92.8 % efficient | 116 W of heat | 400 BTU/h to cool |

Current = kVA × load ÷ volts.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

## What is the FER1500RT-4X9?

- Output: 1,500 VA / 1,500 W (unity power factor, kVA = kW).
- Battery: internal VRLA, 4 × 12 V 9 Ah (48 Vdc).
- Outlets: 8× NEMA 5-20R.

The lines every FERRUS RT shares, from technology to warranty, are in the [FERRUS RT key facts](https://www.aecups.com/us/products/ferrus-rt/#overview) and in the datasheet below.

Size and floor

## How big it is

17.3" W × 17.3" D × 3.4" H (439 × 439 × 86 mm); 48.5 lb (22 kg) net.

**2.1 ft²** footprint (0.19 m²)

**23 lb/ft²** floor load of the cabinet alone

**Rack 19"** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## FER1500RT-4X9 datasheet.

The FER1500RT-4X9 in the AEC 2026 catalog, figure by figure. [Compare it with every FERRUS RT model](https://www.aecups.com/us/products/ferrus-rt/#datasheet).

**FER1500RT-4X9 datasheet**

| Parameter | FER1500RT-4X9 |
| --- | --- |
| Power |  |
| Rated power (kVA) | 1.5 |
| Active power (kW) | 1.5 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 120 V single-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 93% |
| Battery DC bus | 48 V DC |
| Battery and runtime |  |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal |
| Runtime at 50 % load | 14.3 min |
| Runtime at 100 % load | 6 min |
| Mechanical |  |
| Form factor | Rack 19" |
| Dimensions W × D × H | 17.3 × 17.3 × 3.4 in (439 × 439 × 86 mm) |
| Net weight | 48.5 lb (22 kg) |
| Footprint | 2.1 ft² (0.19 m²) |
| Common to every FERRUS RT |  |
| Technology | 3-level IGBT; 8 A settable charger |
| Display | color LCD |
| Comms | RS-232, EPO and USB, standard |
| Battery, FER1500RT-4X9 | internal VRLA, 4 × 12V 9Ah (48 Vdc) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## FER1500RT-4X9: what people ask

#### What is the output current of the FER1500RT-4X9?

12.5 A at 120 V at full load: 1.5 kVA ÷ 120 V. Size the input breaker and the cables of the FER1500RT-4X9 from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the FER1500RT-4X9 give off?

About 116 W, 400 BTU/h, at full load, where it is 92.8% efficient. Plan the room's cooling for a little more than that: the FER1500RT-4X9 is less efficient at part load and while its battery recharges.

#### How many rack units does the FER1500RT-4X9 take?

2U of a 19-inch rack: 3.4 in high, 17.3 in deep. Check the rack's usable depth, rails and rear clearance for the cables.

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

FERRUS RT

## Other FERRUS RT models

[The FERRUS RT series, with pictures](https://www.aecups.com/us/products/ferrus-rt/#models)

By power, the FER1500RT-4X9 is number 2 of 4 in the FERRUS RT series, which runs from 1 to 3 kVA. One size down is the [FER1000RT-2X9](https://www.aecups.com/us/products/ferrus-rt/fer1000rt-2x9/) (0.5 kVA less and 7 lb lighter). One size up is the [FER2000RT-4X9](https://www.aecups.com/us/products/ferrus-rt/fer2000rt-4x9/) (0.5 kVA more and 3 lb heavier).

#### Every FERRUS RT model side by side (4)

**FERRUS RT models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
| --- | --- | --- | --- | --- | --- |
| [FER1000RT-2X9](https://www.aecups.com/us/products/ferrus-rt/fer1000rt-2x9/) | 1 kVA | 0.5 kVA less | 42 lb | 7 lb lighter | 10 min at 50 % load |
| **FER1500RT-4X9** | 1.5 kVA | this page | 49 lb | this page | 14.3 min at 50 % load |
| [FER2000RT-4X9](https://www.aecups.com/us/products/ferrus-rt/fer2000rt-4x9/) | 2 kVA | 0.5 kVA more | 52 lb | 3 lb heavier | 10 min at 50 % load |
| [FER3000RT-6X9](https://www.aecups.com/us/products/ferrus-rt/fer3000rt-6x9/) | 3 kVA | 1.5 kVA more | 62 lb | 13 lb heavier | 10 min at 50 % load |

## The FER1500RT-4X9 for your project

Send the load, the voltage and the minutes you need from the FER1500RT-4X9. We reply with the configuration, the batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20single-phase&msg=About%20the%20FER1500RT-4X9%20(FERRUS%20RT)%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)