title: "10 kVA 120/240V UPS, 16 × 9 Ah VRLA: AEC FERRUS SP"
url: https://www.aecups.com/us/products/ferrus-sp/fersp10000-16x9/
description: "AEC FERRUS SP FERSP10000-16X9: 10 kVA / 10 kW online UPS for 120/240 V split-phase, internal VRLA batteries."
language: en-US
---

FERRUS SP · 120/240V split-phase UPS

# FERSP10000-16X9 FERRUS SP 10 kVA, 120/240V split-phase UPS

VRLA 10 kVA Online double conversion

The AEC FERRUS SP FERSP10000-16X9 is a 10 kVA / 10 kW online double-conversion UPS for 120/240 V split-phase loads, with internal VRLA batteries. Kept at 80 % of its rating, it carries loads up to 8 kW.

**10 kVA / 10 kW** Rating

**9.9 × 23.6 × 29 in** W × D × H

**235.9 lb** Weight

**VRLA, internal** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_FERRUS_SP_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20split-phase&msg=About%20the%20FERSP10000-16X9%20(FERRUS%20SP)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/fersp/v53/#fersp10)

Drag to turn

In 3D

## Look around the FERSP10000-16X9

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/fersp/v53/#fersp10)

The same on every FERRUS SP: [The FERRUS SP display](https://www.aecups.com/us/products/ferrus-sp/#display)

Load by load

## The FERSP10000-16X9 at 25, 50, 75 and 100 % load.

Its 10 kW rating in four steps, worked out from its own catalog figures.

**At 25, 50, 75 and 100 % load**

| Load | Output current on each leg | Efficiency | Heat to remove | Heat to remove (BTU/h) |
| --- | --- | --- | --- | --- |
| 25 % of the FERSP10000-16X9, 2.5 kW | 10.4 A on each leg | 90.8 % efficient | 253 W of heat | 860 BTU/h to cool |
| 50 % of the FERSP10000-16X9, 5.0 kW | 20.8 A on each leg | 92.8 % efficient | 388 W of heat | 1,320 BTU/h to cool |
| 75 % of the FERSP10000-16X9, 7.5 kW | 31.3 A on each leg | 93.0 % efficient | 565 W of heat | 1,930 BTU/h to cool |
| 100 % of the FERSP10000-16X9, 10 kW | 41.7 A on each leg | 92.8 % efficient | 776 W of heat | 2,650 BTU/h to cool |

Current = kVA × load ÷ volts.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

## What is the FERSP10000-16X9?

- Output: 10,000 VA / 10,000 W (unity power factor, kVA = kW).
- Battery: internal VRLA, 16 × 12 V 9 Ah.

The lines every FERRUS SP shares, from technology to warranty, are in the [FERRUS SP key facts](https://www.aecups.com/us/products/ferrus-sp/#overview) and in the datasheet below.

Size and floor

## How big it is

9.9" W × 23.6" D × 29" H (252 × 599 × 738 mm); 235.9 lb (107 kg) net. It ships in one carton of 15.4 × 28.3 × 37 in, 264.6 lb (120 kg) gross.

**1.6 ft²** footprint (0.15 m²)

**145 lb/ft²** floor load of the cabinet alone

**Tower** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## FERSP10000-16X9 datasheet.

The FERSP10000-16X9 in the AEC 2026 catalog, figure by figure. [Compare it with every FERRUS SP model](https://www.aecups.com/us/products/ferrus-sp/#datasheet).

**FERSP10000-16X9 datasheet**

| Parameter | FERSP10000-16X9 |
| --- | --- |
| Power |  |
| Rated power (kVA) | 10 |
| Active power (kW) | 10 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 120/240 V split-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 93% |
| Battery DC bus | 192 V DC |
| Battery and runtime |  |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal |
| Runtime at 50 % load | 7.5 min |
| Runtime at 100 % load | 3.2 min |
| Mechanical |  |
| Form factor | Tower |
| Dimensions W × D × H | 9.9 × 23.6 × 29 in (252 × 599 × 738 mm) |
| Net weight | 235.9 lb (107 kg) |
| Footprint | 1.6 ft² (0.15 m²) |
| Shipping |  |
| Cartons | 1 |
| Shipping weight | 264.6 lb |
| Common to every FERRUS SP |  |
| Comms | RS-232, EPO and USB, standard |
| Battery, FERSP10000-16X9 | internal VRLA, 16 × 12V 9Ah |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## FERSP10000-16X9: what people ask

#### What is the output current of the FERSP10000-16X9?

41.7 A on each line at 240 V at full load: 10 kVA ÷ 240 V. Size the input breaker and the cables of the FERSP10000-16X9 from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the FERSP10000-16X9 give off?

About 776 W, 2,650 BTU/h, at full load, where it is 92.8% efficient. Plan the room's cooling for a little more than that: the FERSP10000-16X9 is less efficient at part load and while its battery recharges.

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

FERRUS SP

## Other FERRUS SP models

[The FERRUS SP series, with pictures](https://www.aecups.com/us/products/ferrus-sp/#models)

By power, the FERSP10000-16X9 is number 2 of 3 in the FERRUS SP series, which runs from 6 to 20 kVA. One size down is the [FERSP6000-16X9](https://www.aecups.com/us/products/ferrus-sp/fersp6000-16x9/) (4 kVA less and 40 lb lighter). One size up is the [FERSP20000-40X9](https://www.aecups.com/us/products/ferrus-sp/fersp20000-40x9/) (10 kVA more and 216 lb heavier).

#### Every FERRUS SP model side by side (3)

**FERRUS SP models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
| --- | --- | --- | --- | --- | --- |
| [FERSP6000-16X9](https://www.aecups.com/us/products/ferrus-sp/fersp6000-16x9/) | 6 kVA | 4 kVA less | 196 lb | 40 lb lighter | 14.3 min at 50 % load |
| **FERSP10000-16X9** | 10 kVA | this page | 236 lb | this page | 7.5 min at 50 % load |
| [FERSP20000-40X9](https://www.aecups.com/us/products/ferrus-sp/fersp20000-40x9/) | 20 kVA | 10 kVA more | 452 lb | 216 lb heavier | 10 min at 50 % load |

Install and run it: [FERRUS SP operating guide](https://www.aecups.com/us/support/guides/ferrus-sp/)

## The FERSP10000-16X9 for your project

Send the load, the voltage and the minutes you need from the FERSP10000-16X9. We reply with the configuration, the batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20split-phase&msg=About%20the%20FERSP10000-16X9%20(FERRUS%20SP)%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)