title: "20 kVA 120/240V UPS, 40 × 9 Ah VRLA: AEC FERRUS SP"
url: https://www.aecups.com/us/products/ferrus-sp/fersp20000-40x9/
description: "AEC FERRUS SP FERSP20000-40X9: 20 kVA / 20 kW online UPS for 120/240 V split-phase, internal VRLA batteries."
language: en-US
---

FERRUS SP · 120/240V split-phase UPS

# FERSP20000-40X9 FERRUS SP 20 kVA, 120/240V split-phase UPS

VRLA 20 kVA Online double conversion

The AEC FERRUS SP FERSP20000-40X9 is a 20 kVA / 20 kW online double-conversion UPS for 120/240 V split-phase loads, with internal VRLA batteries. Kept at 80 % of its rating, it carries loads up to 16 kW.

**20 kVA / 20 kW** Rating

**15.8 × 28.7 × 38.7 in** W × D × H

**452 lb** Weight

**VRLA, internal** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_FERRUS_SP_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20split-phase&msg=About%20the%20FERSP20000-40X9%20(FERRUS%20SP)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/fersp/v53/#fersp20)

Drag to turn

In 3D

## Look around the FERSP20000-40X9

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/fersp/v53/#fersp20)

The same on every FERRUS SP: [The FERRUS SP display](https://www.aecups.com/us/products/ferrus-sp/#display)

Load by load

## The FERSP20000-40X9 at 25, 50, 75 and 100 % load.

Its 20 kW rating in four steps, worked out from its own catalog figures.

**At 25, 50, 75 and 100 % load**

| Load | Output current on each leg | Efficiency | Heat to remove | Heat to remove (BTU/h) |
| --- | --- | --- | --- | --- |
| 25 % of the FERSP20000-40X9, 5.0 kW | 20.8 A on each leg | 90.8 % efficient | 507 W of heat | 1,730 BTU/h to cool |
| 50 % of the FERSP20000-40X9, 10 kW | 41.7 A on each leg | 92.8 % efficient | 776 W of heat | 2,650 BTU/h to cool |
| 75 % of the FERSP20000-40X9, 15 kW | 62.5 A on each leg | 93.0 % efficient | 1.1 kW of heat | 3,850 BTU/h to cool |
| 100 % of the FERSP20000-40X9, 20 kW | 83.3 A on each leg | 92.8 % efficient | 1.6 kW of heat | 5,290 BTU/h to cool |

Current = kVA × load ÷ volts.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

## What is the FERSP20000-40X9?

- Output: 20,000 VA / 20,000 W (unity power factor, kVA = kW).
- Battery: internal VRLA, 40 × 12 V 9 Ah.

The lines every FERRUS SP shares, from technology to warranty, are in the [FERRUS SP key facts](https://www.aecups.com/us/products/ferrus-sp/#overview) and in the datasheet below.

Size and floor

## How big it is

15.8" W × 28.7" D × 38.7" H (401 × 729 × 983 mm); 452 lb (205 kg) net.

**3.1 ft²** footprint (0.29 m²)

**144 lb/ft²** floor load of the cabinet alone

**Tower** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## FERSP20000-40X9 datasheet.

The FERSP20000-40X9 in the AEC 2026 catalog, figure by figure. [Compare it with every FERRUS SP model](https://www.aecups.com/us/products/ferrus-sp/#datasheet).

**FERSP20000-40X9 datasheet**

| Parameter | FERSP20000-40X9 |
| --- | --- |
| Power |  |
| Rated power (kVA) | 20 |
| Active power (kW) | 20 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 120/240 V split-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 93% |
| Battery DC bus | 240 V DC |
| Battery and runtime |  |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal |
| Runtime at 50 % load | 10 min |
| Runtime at 100 % load | 3 min |
| Mechanical |  |
| Form factor | Tower |
| Dimensions W × D × H | 15.8 × 28.7 × 38.7 in (401 × 729 × 983 mm) |
| Net weight | 452 lb (205 kg) |
| Footprint | 3.1 ft² (0.29 m²) |
| Common to every FERRUS SP |  |
| Comms | RS-232, EPO and USB, standard |
| Battery, FERSP20000-40X9 | internal VRLA, 40 × 12V 9Ah |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## FERSP20000-40X9: what people ask

#### What is the output current of the FERSP20000-40X9?

83.3 A on each line at 240 V at full load: 20 kVA ÷ 240 V. Size the input breaker and the cables of the FERSP20000-40X9 from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the FERSP20000-40X9 give off?

About 1.6 kW, 5,290 BTU/h, at full load, where it is 92.8% efficient. Plan the room's cooling for a little more than that: the FERSP20000-40X9 is less efficient at part load and while its battery recharges.

#### Will the FERSP20000-40X9 fit through a standard door?

Yes: 15.8 in (401 mm) across its narrow side and 38.7 in (983 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the FERSP20000-40X9 (size section above).

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

FERRUS SP

## Other FERRUS SP models

[The FERRUS SP series, with pictures](https://www.aecups.com/us/products/ferrus-sp/#models)

By power, the FERSP20000-40X9 is the largest in the FERRUS SP series, which runs from 6 to 20 kVA. One size down is the [FERSP10000-16X9](https://www.aecups.com/us/products/ferrus-sp/fersp10000-16x9/) (10 kVA less and 216 lb lighter).

#### Every FERRUS SP model side by side (3)

**FERRUS SP models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
| --- | --- | --- | --- | --- | --- |
| [FERSP6000-16X9](https://www.aecups.com/us/products/ferrus-sp/fersp6000-16x9/) | 6 kVA | 14 kVA less | 196 lb | 256 lb lighter | 14.3 min at 50 % load |
| [FERSP10000-16X9](https://www.aecups.com/us/products/ferrus-sp/fersp10000-16x9/) | 10 kVA | 10 kVA less | 236 lb | 216 lb lighter | 7.5 min at 50 % load |
| **FERSP20000-40X9** | 20 kVA | this page | 452 lb | this page | 10 min at 50 % load |

Install and run it: [FERRUS SP operating guide](https://www.aecups.com/us/support/guides/ferrus-sp/)

## The FERSP20000-40X9 for your project

Send the load, the voltage and the minutes you need from the FERSP20000-40X9. We reply with the configuration, the batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20split-phase&msg=About%20the%20FERSP20000-40X9%20(FERRUS%20SP)%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)