title: "100 kVA 480V three-phase UPS: AEC INFINITE INF-100"
url: https://www.aecups.com/us/products/infinite/inf-100/
description: "AEC INFINITE INF-100: 100 kVA / 100 kW online UPS for 480 V three-phase, built on one 100 kVA power module, with external VRLA or lithium cabinets."
language: en-US
---

INFINITE · 480V three-phase UPS

# INF-100 INFINITE 100 kVA, 480V three-phase UPS

Lithium or VRLA 100 kVA Online double conversion

The AEC INFINITE INF-100 is a 100 kVA / 100 kW online double-conversion UPS for 480 V three-phase loads, built on one 100 kVA power module, with external VRLA or lithium cabinets. Kept at 80 % of its rating, it carries loads up to 80 kW.

3-wire · Delta 480 V 3-wire, delta: three phases and ground, no neutral

**100 kVA / 100 kW** Rating

**23.6 × 39.4 × 81.4 in** W × D × H

**452.2 lb** Weight

**VRLA or lithium, external** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_INFINITE_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20INF-100%20(INFINITE)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/inf/v48/#inf100)

Drag to turn

In 3D

## Look around the INF-100

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/inf/v48/#inf100)

The same on every INFINITE: [Open the INFINITE: modules and door, from the catalog's photos](https://www.aecups.com/us/products/infinite/#explore) [The INFINITE display](https://www.aecups.com/us/products/infinite/#display)

Runtime

## The INF-100 with its batteries, at your load.

The INF-100 has no batteries of its own: the chart draws in bold the catalog set-ups built on it, the other INFINITE set-ups faded behind. The same chart as the [INFINITE page](https://www.aecups.com/us/products/infinite/#runtime). 2026 catalog, new batteries.

50 %

INFINITE 100 kVA N+1 · 1 L6 cabinet, 20 lithium modules · INFINITE 100 kVA · 1 L6 cabinet, 20 lithium modules INFINITE 100 kVA · half L6 cabinet, 10 modules and 4 more, same minutes

At 50 % of the rating

INFINITE 100 kVA N+1

[**1 L6 cabinet, 20 lithium modules **60 min**](https://www.aecups.com/us/products/infinite/inf-100-1-l6-cab-20x50li/)

INFINITE 100 kVA

[**half L6 cabinet, 10 modules **30 min**](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) [**1 L6 cabinet, 20 lithium modules **60 min**](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/)

INFINITE 200 kVA N+1

[**1 L6 cabinet, 20 lithium modules **30 min**](https://www.aecups.com/us/products/infinite/inf-200-1-l6-cab-20x50li/)

INFINITE 200 kVA

[**1 L6 cabinet, 20 lithium modules **30 min**](https://www.aecups.com/us/products/infinite/inf-200-l6-cab-20x50li/)

INFINITE 400 kVA

[**2 L6 cabinets, 40 lithium modules **30 min**](https://www.aecups.com/us/products/infinite/inf-400-2xl6-cab-20x50li/)

INFINITE 600 kVA

[**3 L6 cabinets, 60 lithium modules **30 min**](https://www.aecups.com/us/products/infinite/inf-600-3xl6-cab-20x50li/)

#### Table: this model at 25, 50, 75 and 100 % load

| Model | 25% load | 50% load | 75% load | 100% load |
| --- | --- | --- | --- | --- |
| [INFINITE 100 kVA N+1 · 1 L6 cabinet, 20 lithium modules](https://www.aecups.com/us/products/infinite/inf-100-1-l6-cab-20x50li/) INF-100+1+L6-CAB-20x50LI | 120 min | 60 min | 40 min | 30 min |
| [INFINITE 100 kVA · half L6 cabinet, 10 modules](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) INF-100+L6-CAB-10x50LI | 60 min | 30 min | 20 min | 15 min |
| [INFINITE 100 kVA · 1 L6 cabinet, 20 lithium modules](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/) INF-100+L6-CAB-20x50LI | 120 min | 60 min | 40 min | 30 min |

[Every INFINITE set-up in one table](https://www.aecups.com/us/products/infinite/#runtime)

From the 2026 catalog

## What is the INF-100?

The code INF-100 orders these catalog items:

- 1 × INF-FRAME-100: 100 kVA frame, without power modules, 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm)
- 1 × INFINITE-PWR-100: 100 kVA hot-swappable power module, 119 lb (54 kg)
- Architecture: 1 × 100 kVA hot-swappable power module in a 100 kVA frame.
- Technology: Silicon-Carbide (SiC) semiconductors; unity power factor; 120 A settable charger; up to 3 frames in parallel (600 kVA).
- Input / Output: 480 V three-phase, 3-wire.
- Efficiency: up to 97.3%.
- Display: 7-inch color touchscreen.
- Comms: RS232, RS485/Modbus, EPO and dry contacts standard; SNMP card optional.
- Battery: external, lead-acid (30–50 blocks) or AEC L6 lithium cabinets.
- Warranty: 3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries.

Size and floor

## How big it is

23.6" W × 39.4" D × 81.4" H (600 × 1,000 × 2,068 mm); 452.2 lb (205.1 kg) net.

**6.5 ft²** footprint (0.60 m²)

**70 lb/ft²** floor load of the cabinet alone

**Modular** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## INF-100 datasheet.

The INF-100 in the AEC 2026 catalog, figure by figure. [Compare it with every INFINITE model](https://www.aecups.com/us/products/infinite/#datasheet).

**INF-100 datasheet**

| Parameter | INF-100 |
| --- | --- |
| Power |  |
| Rated power (kVA) | 100 |
| Active power (kW) | 100 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 480 V three-phase, 3-wire (delta) |
| Topology | Online double conversion, modular |
| Efficiency, up to | 97.3% |
| Battery DC bus | 480 V DC |
| Battery and runtime |  |
| Battery type | VRLA or lithium LiFePO4 |
| Battery configuration | External VRLA bank or L6 lithium cabinets |
| Mechanical |  |
| Form factor | Modular |
| Dimensions W × D × H | 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm) |
| Net weight | 452.2 lb (205.1 kg) |
| Footprint | 6.5 ft² (0.60 m²) |
| Common to every INFINITE |  |
| Technology | Silicon-Carbide (SiC) semiconductors; unity power factor; 120 A settable charger; up to 3 frames in parallel (600 kVA) |
| Display | 7-inch color touchscreen |
| Comms | RS232, RS485/Modbus, EPO and dry contacts standard; SNMP card optional |
| Battery, INF-100 | external, lead-acid (30–50 blocks) or AEC L6 lithium cabinets |
| Use | 100 to 600 kVA: one 100 or 200 kVA frame, or up to three 200 kVA frames in parallel; above 600 kVA, INFINITE 1.5MW |
| Network card | SNMP-L (SNMP) |
| Warranty | 3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## INF-100: what people ask

#### What is the output current of the INF-100?

120.3 A per phase at full load: 100 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the INF-100 from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the INF-100 give off?

About 2.8 kW, 9,470 BTU/h, at full load, where it is 97.3% efficient. Plan the room's cooling for a little more than that: the INF-100 is less efficient at part load and while its battery recharges.

#### Will the INF-100 fit through a standard door?

Not upright through a standard 36 × 80-inch door, which clears about 79 in in height: at 81.4 in (2,068 mm) high it needs an opening taller than 81.4 in. Check elevators and the floor load on the way in too.

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

INFINITE

## Other INFINITE models

[The INFINITE series, with pictures](https://www.aecups.com/us/products/infinite/#models)

By power, the INF-100 is the smallest in the INFINITE series, which runs from 100 to 600 kVA. One size up are the [INF-200](https://www.aecups.com/us/products/infinite/inf-200/), [INF-200+1](https://www.aecups.com/us/products/infinite/inf-200-1/), [INF-200+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-1-l6-cab-20x50li/) and [INF-200+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-l6-cab-20x50li/), all 100 kVA more. The same 100 kVA also comes as the [INF-100+1](https://www.aecups.com/us/products/infinite/inf-100-1/), [INF-100+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-1-l6-cab-20x50li/), [INF-100+L6-CAB-10x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) and [INF-100+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/): the table below gives each one's weight and battery.

#### Every INFINITE model side by side (13)

**INFINITE models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model | Battery configuration |
| --- | --- | --- | --- | --- | --- |
| **INF-100** | 100 kVA | this page | 452 lb | this page | External VRLA bank or L6 lithium cabinets |
| [INF-100+1](https://www.aecups.com/us/products/infinite/inf-100-1/) | 100 kVA | the same power | 571 lb | 119 lb heavier | External VRLA bank or L6 lithium cabinets |
| [INF-100+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-1-l6-cab-20x50li/) | 100 kVA | the same power | 2,743 lb | 2,291 lb heavier | External L6 lithium cabinets |
| [INF-100+L6-CAB-10x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-10x50li/) | 100 kVA | the same power | 1,808 lb | 1,356 lb heavier | External L6 lithium cabinets |
| [INF-100+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-100-l6-cab-20x50li/) | 100 kVA | the same power | 2,624 lb | 2,172 lb heavier | External L6 lithium cabinets |
| [INF-200](https://www.aecups.com/us/products/infinite/inf-200/) | 200 kVA | 100 kVA more | 591 lb | 139 lb heavier | External VRLA bank or L6 lithium cabinets |
| [INF-200+1](https://www.aecups.com/us/products/infinite/inf-200-1/) | 200 kVA | 100 kVA more | 710 lb | 258 lb heavier | External VRLA bank or L6 lithium cabinets |
| [INF-200+1+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-1-l6-cab-20x50li/) | 200 kVA | 100 kVA more | 2,882 lb | 2,430 lb heavier | External L6 lithium cabinets |
| [INF-200+L6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-200-l6-cab-20x50li/) | 200 kVA | 100 kVA more | 2,763 lb | 2,311 lb heavier | External L6 lithium cabinets |
| [INF-400](https://www.aecups.com/us/products/infinite/inf-400/) | 400 kVA | 300 kVA more | 1,183 lb | 730 lb heavier | External VRLA bank or L6 lithium cabinets |
| [INF-400+2xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-400-2xl6-cab-20x50li/) | 400 kVA | 300 kVA more | 5,526 lb | 5,074 lb heavier | External L6 lithium cabinets |
| [INF-600](https://www.aecups.com/us/products/infinite/inf-600/) | 600 kVA | 500 kVA more | 1,774 lb | 1,322 lb heavier | External VRLA bank or L6 lithium cabinets |
| [INF-600+3xL6-CAB-20x50LI](https://www.aecups.com/us/products/infinite/inf-600-3xl6-cab-20x50li/) | 600 kVA | 500 kVA more | 8,597 lb | 8,145 lb heavier | External L6 lithium cabinets |

Install and run it: [INFINITE operating guide](https://www.aecups.com/us/support/guides/infinite/) [L6 lithium cabinet guide](https://www.aecups.com/us/support/guides/lithium-cabinet/) [Guide specification, CSI 26 33 53](https://www.aecups.com/us/products/infinite-guide-specification/)

## The INF-100 for your project

Send the load, the voltage and the minutes you need from the INF-100. We reply with the configuration, the batteries and the lead time.

[Send your project](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20INF-100%20(INFINITE)%3A%20%0AQuantity%3A%20#form) [+1 786 553 2100](tel:+17865532100)