title: "L6 lithium UPS battery system: LiFePO4, hot-swap, BMS | AEC"
url: https://www.aecups.com/us/products/lithium-batteries/
description: "AEC L6 lithium UPS battery system: 50 Ah LiFePO4 modules on isolated DC/DC converters in parallel, hot-swap, three-level BMS, up to 15 cabinets."
language: en-US
---

L6 lithium battery system · LiFePO4

# L6 lithium battery cabinets for UPS: 50 Ah LiFePO4 modules in parallel.

The AEC L6 is a modular LiFePO4 lithium battery system for UPS: 50 Ah modules of 2.88 kWh in parallel, each on its own DC/DC converter and hot-swappable, so a fault stays in one module and the load stays on. One cabinet of 20 modules gives 15 minutes at 200 kW; up to 15 cabinets run in parallel.

Plan your cabinets Open a cabinet [View in 3D](https://www.aecups.com/assets/models3d/l6/v39/) [Ask an engineer](https://www.aecups.com/us/contacts/?interest=Sizing%20help#form)

**10 kW** per 50 Ah module, 2.88 kWh

**15 min** at 200 kW from one cabinet of 20

**15** cabinets in one system

**5,000+** cycles, 15-year life

One main cabinet with the touchscreen, slave cabinets beside it: the whole system on one screen.

The main feature · Parallel, not series

## Every module works on its own.

Each AEC module has its own DC/DC converter and joins the bus in parallel: hot-swappable, redundant, and new modules can sit beside old ones. In a series string, one module down stops the whole string; in parallel, the other modules carry on. Make one fail and see.

Series string **Modules in series** One string: the current goes through every module

**100 %** battery power

All 8 modules on line · the load is protected

AEC **Modules in parallel** Each module on its own DC/DC converter, joined to the bus

**100 %** battery power

All 8 modules on line · the load is protected

or tap any module

Watch the power flow from the batteries to the UPS. Then make one module fail.

| What happens | In series | AEC, in parallel |
| --- | --- | --- |
| One module fails | The string opens: no battery at all until it is repaired | That module drops out; the other seven keep the load |
| Replacing a module | With the string switched off | Hot-swap: slide it out and in, the load stays on |
| Old and new modules | A string wants matched modules | New beside old: each runs on its own converter |
| Adding runtime | Add a whole string | Add modules: up to 3 in an ETHERNO, 20 in an L6 cabinet |
| Sharing the current | One current through every module | Each converter takes its share; cabinets share within 3 % |
| Safety | The full string voltage runs through every module | Isolated DC/DC: low voltage inside, a fault stays in its module |

Why L6

## What lead-acid costs, and what the L6 does instead.

Lead-acid, and lithium built as one series string, share the same weak point: one bad block or pack affects all of it. The L6 keeps every module on its own.

01 **Heavy blocks**

Floor area and floor load to check for a VRLA battery cabinet beside the UPS.

02 **No warning**

No health analysis and no early warning before a block fails.

03 **Short life**

About three sets of batteries in one UPS life: replaced about twice.

04 **High maintenance**

The whole string is serviced, and checked at least twice a year.

From the comparison with a UPS and a VRLA battery cabinet in the [AEC L6 lithium catalog (2026)](https://www.aecups.com/docs/AEC_L6_LITHIUM_2026.pdf), which gives the lead-acid side as indicative limits, not a test. The same catalog gives the L6 a 15-year life and 5,000+ cycles.

Safe

### A fault stays where it starts.

- **Isolated DC/DC in every module** A fault stays inside its module, and the low voltage inside keeps high-voltage arcs out.
- **Fire protection per module** Temperature is watched module by module: a fault is answered where it starts.
- **On-line insulation monitoring** Checked while the system runs: a leak is located before it becomes a short circuit.
- **A failed module drops out** On its own, while the other modules and the UPS carry on.

Smart

### Every cell in view.

- **Three-level BMS** A BMS in every module, one in every cabinet and one for the system, reporting to the touchscreen and the UPS.
- **Cell-level data** Voltage and temperature of every cell, with the faulty one located.
- **Old and new side by side** Adaptive state of charge: new modules work beside old ones, and cabinets share current within 3 %.
- **On-line battery test** Modules are tested in groups while the system runs.

Simple

### Minutes, not hours.

- **Hot-swap** A module is replaced in about 5 minutes with the load on; a series string is switched off for about 180 minutes.
- **Grows with the load** Add modules, or cabinets: up to 15 cabinets in one system.
- **Matches the UPS** 240 V, 480 V or ±240 V output, to suit the UPS DC bus.
- **Fits the room** Cables and switches reached from the front; a combiner cabinet joins three or more cabinets.

Drag to turn

In 3D

## Look around the L6 cabinet

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/l6/v39/)

Rendered from AEC's 3D model of the L6 lithium battery cabinet. The full 3D view zooms in, opens the unit and names every part.

Hands on

## Open an L6 cabinet.

The catalog's own photos: open the door, pull modules out while the load stays on, and watch the runtime change.

L6 lithium cabinet

Click the door

L6 lithium cabinet · LiFePO4 · for INFINITE

### Twenty modules in parallel. Pull one, the rest keep going.

Modules in **—**

Battery power **—**

Usable energy **—**

Runtime, new modules **—**

Each 50 Ah module joins the DC bus through its own DC/DC converter, so every module works on its own: one out or one failed, the others keep the load on. New and old modules can sit side by side.

- 7-inch touchscreen on the door: voltage, current, charge and temperature of every module
- Three-layer BMS: in every module, in the cabinet, for the whole system
- Up to 15 cabinets in parallel

#### All 3 numbered parts

[INFINITE with lithium](https://www.aecups.com/us/products/infinite/)

Inside the module

## One 50 Ah module, opened.

The same LiFePO4 module runs in the ETHERNO and in the L6 cabinet. Turn it, open it, click a number.

The same module goes in the ETHERNO (up to three) and in the L6 cabinet (up to twenty): 50 Ah, 2.88 kWh, 223 × 665 × 152 mm.

Plan it

## How many cabinets for your UPS?

Pick the UPS and the minutes: cabinets and 50 Ah modules from the L6 backup tables, with new modules. Runtime grows module by module, so nothing is oversized.

**1** cabinet

**6** modules

### Backup at a glance

Every rating of the L6 backup tables, with new 50 Ah modules: each block is a cabinet, filled by its modules.

UPS 15 min 30 min

**60 kVA** 1 cabinet · 6 modules 1 cabinet · 12 modules

**80 kVA** 1 cabinet · 8 modules 1 cabinet · 16 modules

**100 kVA** 1 cabinet · 10 modules 1 cabinet · 20 modules

**200 kVA** 1 cabinet · 20 modules 2 cabinets · 40 modules

**300 kVA** 2 cabinets · 30 modules 3 cabinets · 60 modules

**400 kVA** 2 cabinets · 40 modules 4 cabinets · 80 modules

**500 kVA** 3 cabinets · 50 modules 5 cabinets · 100 modules

**600 kVA** 3 cabinets · 60 modules 6 cabinets · 120 modules

**800 kVA** 4 cabinets · 80 modules 8 cabinets · 160 modules

Range

## The 50 Ah module and its cabinets.

From the 2026 catalog, for the US market: cabinets of 10 or 20 modules, and the combiner cabinet that joins three or more.

**Cells**: 18 × 3.2 V LiFePO4 · 57.6 V

**Energy**: 2.88 kWh

**DC/DC output**: 10 kW

**Cabinet**: 20 modules · 58 kWh

**Backup, one cabinet**: 15 min at 200 kW

**Charge current**: 0.1 to 1 C (0.5 C as set)

**DC/DC output voltage**: ±240 V, 240 V or 480 V

**Current unbalance**: within 3 %

**Noise**: 58 dB

| Model | Description | Size (W × D × H) | Weight |
| --- | --- | --- | --- |
| **L6-CAB-10×50LI** | Lithium cabinet with 10 × 50 Ah modules, BMS and smoke detector | 23.6" W × 33.5" D × 78.7" H (599 × 851 × 1,999 mm) | 1,356 lb (615 kg) |
| **L6-CAB-20×50LI** | Lithium cabinet with 20 × 50 Ah modules, BMS and smoke detector | 23.6" W × 33.5" D × 78.7" H (599 × 851 × 1,999 mm) | 2,172 lb (985 kg) |
| **L6-COMBINER** | Combiner cabinet: joins three or more lithium cabinets to the UPS | 15.7" W × 33.5" D × 78.7" H (399 × 851 × 1,999 mm) | 309 lb (140 kg) |
| **L6-CAB-EMPTY** | Empty lithium cabinet with BMS and smoke detector, for up to 20 × 50 Ah modules | 23.6" W × 33.5" D × 78.7" H (600 × 850 × 2,000 mm) | 540 lb (245 kg) |
| **L6-MOD-50LI** | LiFePO4 module, 50 Ah · 2.88 kWh, with its own DC/DC converter | 8.8" W × 26.2" D × 6" H (223 × 665 × 152 mm) | 82 lb (37 kg) |

The cabinet's own screen

## The L6 BMS display.

The real touchscreen from the user manual: its cabinets, modules, cells, alarms and health pages; pick a page or touch the screen as on the cabinet.

L6 lithium cabinet · the real screen

### Home

The cabinets with their color (blue normal, yellow alarm, red protected, gray not connected), the system work mode, status, current, voltage and SOC. Tap a cabinet for its monitoring pages, or Sys. info for the system extremes.

**The ten main pages**

Lithium UPS

## UPS with lithium inside.

From a 2U rack unit to 1,500 kVA, with LiFePO4 built in or in L6 cabinets.

### LUMINA

Lithium

1–3 kVA · 120 V

Online double-conversion UPS for single-phase 120 V loads from 1 to 3 kVA, in a 19-inch rack, with internal LiFePO4 lithium batteries.

View series

### ETHERNO

Lithium

10–30 kVA · 208 V

Online double-conversion UPS for three-phase 208 V loads from 10 to 30 kVA, in a tower cabinet, with hot-swappable 50 Ah lithium modules.

View series

### INFINITE

3-wire · Delta Lithium or VRLA

100–600 kVA · 480 V 3-wire · Delta

Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 100 to 600 kVA, with external lithium battery cabinets.

View series

### INFINITE 1.5MW

3-wire · Delta Lithium or VRLA

750–1,500 kVA · 480 V 3-wire · Delta

Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 750 to 1,500 kVA, with external lithium battery cabinets.

View series

Questions

## Questions people ask

#### How long does one L6 cabinet run a UPS?

About 15 minutes at 200 kW from one cabinet of 20 modules of 50 Ah: each module is rated 10 kW for 15 minutes, 2.88 kWh nominal. Runtime grows module by module, and up to 15 cabinets run in one system.

#### How long does an L6 lithium battery last?

The AEC L6 lithium catalog (2026) gives a 15-year life and 5,000+ cycles; the cabinets carry a 5-year warranty with their batteries.

#### Can an L6 module be replaced with the load on?

Yes: each module reaches the UPS through its own isolated DC/DC converter, so one is slid out and a new one slid in with the load on, in about 5 minutes. New modules work beside old ones.

#### Which listings and tests does the L6 hold?

The AEC L6 lithium catalog (2026) gives the modules as UL 1973 listed, and UL 9,540A and UN38.3 tested.

#### Which AEC UPS run on L6 cabinets?

INFINITE (100 to 600 kVA) and INFINITE 1.5MW (750 to 1,500 kVA) run on external L6 cabinets, or on a lead-acid bank. ETHERNO takes the same 50 Ah modules inside its tower, up to three.

## Documents

User manual **L6 Lithium battery cabinet**

**L6 Lithium battery cabinet: User manual (US, 2026)** User manual · English · 7.8 MB

User manual **L6 Lithium battery cabinet, touchscreen (MBMU)**

**L6 Lithium battery cabinet, touchscreen (MBMU): User manual (US, 2026)** User manual · English · 4.9 MB

**L6 lithium battery cabinets: Catalog 2026** Catalog · English · 0.8 MB

[Full quality · 2.3 MB](https://www.aecups.com/docs/AEC_L6_LITHIUM_2026.pdf)

User manual **L6 Lithium battery cabinet**

**L6 Lithium battery cabinet: Quick installation guide (US, 2026)** User manual · English · 1.5 MB

## Size a lithium system

Tell us the UPS, the load and the minutes: we size the modules and cabinets.

[Send your project](https://www.aecups.com/us/contacts/#form) [+1 786 553 2100](tel:+17865532100)