# RAD90-4X15 RADIANT 60 kVA, 208V three-phase UPS

VRLA 60 kVA Online double conversion

The AEC RADIANT RAD90-4X15 is a 60 kVA / 60 kW online double-conversion UPS for 208 V three-phase loads, built on four 15 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 48 kW.

Four of the frame's six module slots are fitted and two are free; with one module held as a spare (N+1) it carries 45 kVA. As configured it weighs 329.5 lb (149.5 kg) net.

**60 kVA / 60 kW** Rating

**17.4 × 33.1 × 59.4 in** W × D × H

**329.5 lb** Weight

**VRLA, external** Battery

Technical data [Catalog (PDF)](https://www.aecups.com/docs/AEC_RADIANT_2026.pdf) [Contact us](https://www.aecups.com/us/contacts/?interest=UPS%20three-phase&msg=About%20the%20RAD90-4X15%20(RADIANT)%3A%20%0AQuantity%3A%20#form)

[**Try 3D** X-ray view](https://www.aecups.com/assets/models3d/rad90/v56/#rad90-4)

Series picture.

Drag to turn

In 3D

## Look around the RAD90-4X15

[Open full 3D · X-ray](https://www.aecups.com/assets/models3d/rad90/v56/#rad90-4)

The turntable shows the 90 kVA · 6 modules configuration; the full 3D view opens on this model.

The same on every RADIANT: [The RADIANT display](https://www.aecups.com/us/products/radiant/#display)

Load by load

## The RAD90-4X15 at 25, 50, 75 and 100 % load.

Its 60 kW rating in four steps, worked out from its own catalog figures.

**At 25, 50, 75 and 100 % load**

| Load | Output current per phase, at 208 V | Load on each of its 4 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
| --- | --- | --- | --- | --- | --- |
| 25 % of the RAD90-4X15, 15 kW | 41.6 A per phase | 25 % on each module | 92.8 % efficient | 1.2 kW of heat | 3,970 BTU/h to cool |
| 50 % of the RAD90-4X15, 30 kW | 83.3 A per phase | 50 % on each module | 93.9 % efficient | 1.9 kW of heat | 6,650 BTU/h to cool |
| 75 % of the RAD90-4X15, 45 kW | 125 A per phase | 75 % on each module | 94.0 % efficient | 2.9 kW of heat | 9,800 BTU/h to cool |
| 100 % of the RAD90-4X15, 60 kW | 167 A per phase | 100 % on each module | 93.8 % efficient | 4.0 kW of heat | 13,530 BTU/h to cool |

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

## What is the RAD90-4X15?

The code RAD90-4X15 orders these catalog items:

- 1 × RAD90-FRAME: 90 kVA frame, without power modules, 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm)
- 4 × RAD-PWR-15: 15 kVA hot-swappable power module, 30.5 lb (13.9 kg) each
- Architecture: 4 × 15 kVA hot-swappable power modules in a 90 kVA / 90 kW frame, 6 slots with 4 breakers (scalable to 6 modules / 90 kVA); parallel up to 4 frames.

The lines every RADIANT shares, from technology to warranty, are in the [RADIANT key facts](https://www.aecups.com/us/products/radiant/#overview) and in the datasheet below.

4 × 15 kVA power modules fitted in a 6-slot frame: 2 free slots to grow or add redundancy.

Size and floor

## How big it is

17.4" W × 33.1" D × 59.4" H (442 × 840 × 1,510 mm); 329.5 lb (149.5 kg) net.

**4.0 ft²** footprint (0.37 m²)

**82 lb/ft²** floor load of the cabinet alone

**Modular Rack 19"** form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

Datasheet

## RAD90-4X15 datasheet.

The RAD90-4X15 in the AEC 2026 catalog, figure by figure. [Compare it with every RADIANT model](https://www.aecups.com/us/products/radiant/#datasheet).

**RAD90-4X15 datasheet**

| Parameter | RAD90-4X15 |
| --- | --- |
| Power |  |
| Rated power (kVA) | 60 |
| Active power (kW) | 60 |
| Output power factor | 1.0 |
| Electrical |  |
| Input / output | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 94% |
| Battery DC bus | 240 V DC |
| Battery and runtime |  |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical |  |
| Form factor | Modular Rack 19" |
| Dimensions W × D × H | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) |
| Net weight | 329.5 lb (149.5 kg) |
| Footprint | 4.0 ft² (0.37 m²) |
| Common to every RADIANT |  |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger |
| Battery, RAD90-4X15 | external VRLA (battery bank sized separately) |
| Display | 7-inch color touchscreen |
| Comms | RS-232, EPO and USB, standard |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

## RAD90-4X15: what people ask

#### What is the output current of the RAD90-4X15?

166.5 A per phase at full load: 60 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the RAD90-4X15 from its installation manual and the local electrical code, not from this figure alone.

#### How much heat does the RAD90-4X15 give off?

About 4.0 kW, 13,530 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the RAD90-4X15 is less efficient at part load and while its battery recharges.

#### Will the RAD90-4X15 fit through a standard door?

Yes: 17.4 in (442 mm) across its narrow side and 59.4 in (1,510 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the RAD90-4X15 (size section above).

The method, for any UPS: [runtime explained](https://www.aecups.com/us/blog/ups-runtime-explained/) · [amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/) · [heat output in BTU/h](https://www.aecups.com/us/blog/ups-heat-output-btu/)

RADIANT

## Other RADIANT models

[The RADIANT series, with pictures](https://www.aecups.com/us/products/radiant/#models)

By power, the RAD90-4X15 is number 4 of 6 in the RADIANT series, which runs from 15 to 90 kVA. One size down is the [RAD90-3X15](https://www.aecups.com/us/products/radiant/rad90-3x15/) (15 kVA less and 31 lb lighter). One size up is the [RAD90-5X15](https://www.aecups.com/us/products/radiant/rad90-5x15/) (15 kVA more and 31 lb heavier).

#### Every RADIANT model side by side (6)

**RADIANT models side by side**

| Model | Power | Power against this model | Net weight | Weight against this model |
| --- | --- | --- | --- | --- |
| [RAD90-1X15](https://www.aecups.com/us/products/radiant/rad90-1x15/) | 15 kVA | 45 kVA less | 238 lb | 92 lb lighter |
| [RAD90-2X15](https://www.aecups.com/us/products/radiant/rad90-2x15/) | 30 kVA | 30 kVA less | 269 lb | 61 lb lighter |
| [RAD90-3X15](https://www.aecups.com/us/products/radiant/rad90-3x15/) | 45 kVA | 15 kVA less | 299 lb | 31 lb lighter |
| **RAD90-4X15** | 60 kVA | this page | 330 lb | this page |
| [RAD90-5X15](https://www.aecups.com/us/products/radiant/rad90-5x15/) | 75 kVA | 15 kVA more | 360 lb | 31 lb heavier |
| [RAD90-6X15](https://www.aecups.com/us/products/radiant/rad90-6x15/) | 90 kVA | 30 kVA more | 391 lb | 61 lb heavier |