# Three-phase UPS systems for 208 V and 480 V

A three-phase (3-phase) UPS keeps three-phase loads running when the utility fails. AEC offers eight online double-conversion series for US supplies: towers and modular frames from 10 to 100 kVA at 208 V, and modular systems from 30 to 1,600 kVA at 480 V, 4-wire or 3-wire, with lithium or VRLA batteries. Choose the supply first, then the power.

[Size a UPS](https://www.aecups.com/us/tools/ups-sizing/) [208V UPS](https://www.aecups.com/us/products/three-phase-ups-208v/) [480V UPS](https://www.aecups.com/us/products/three-phase-ups-480v/)

Side by side

## Every AEC three-phase UPS.

From the 2026 catalog. Click a series for its models, runtimes and drawings.

| Series | Supply | Power | Type | Battery | Efficiency |
| --- | --- | --- | --- | --- | --- |
| [**ETHERNO**](https://www.aecups.com/us/products/etherno/) | 208 V | 10–30 kVA | Tower | Lithium LiFePO4 | up to 94% |
| [**AUREON**](https://www.aecups.com/us/products/aureon/) | 208 V | 10–30 kVA | Tower | VRLA | up to 94% |
| [**RADIANT**](https://www.aecups.com/us/products/radiant/) | 208 V | 15–90 kVA | Modular, N+X | VRLA | up to 94% |
| [**RADIANT-IB**](https://www.aecups.com/us/products/radiant-ib/) | 208 V | 20–100 kVA | Modular, N+X | VRLA | up to 94% |
| [**CIRRO-IB**](https://www.aecups.com/us/products/cirro-ib/) | 480 V, 4-wire | 30–150 kVA | Modular, N+X | VRLA | up to 96% |
| [**CIRRO**](https://www.aecups.com/us/products/cirro/) | 480 V, 4-wire | 60–1,600 kVA | Modular, N+X | VRLA | up to 97% |
| [**INFINITE**](https://www.aecups.com/us/products/infinite/) | 480 V, 3-wire | 100–600 kVA | Modular, N+1 | Lithium LiFePO4 or VRLA | up to 97.3% |
| [**INFINITE 1.5MW**](https://www.aecups.com/us/products/infinite-1-5mw/) | 480 V, 3-wire | 750–1,500 kVA | Modular, N+1 | Lithium LiFePO4 or VRLA | up to 97.5% |

The supply decides

## 208 V, 480 V 4-wire or 480 V 3-wire.

**208Y/120 V** is the three-phase supply of most US commercial buildings and server rooms: ETHERNO, AUREON, RADIANT and RADIANT-IB, 10 to 100 kVA.

**480Y/277 V, 4-wire** carries the neutral: CIRRO-IB and CIRRO, 30 to 1,600 kVA.

**480 V, 3-wire** (delta, no neutral) is common in industry: INFINITE, 100 to 600 kVA, and INFINITE 1.5MW, 750 to 1,500 kVA, with silicon carbide modules.

More: [208 V or 480 V UPS](https://www.aecups.com/us/blog/208v-vs-480v-ups/) · [when a transformer is needed](https://www.aecups.com/us/technology/isolation-transformer-ups/) · [modular UPS and N+X](https://www.aecups.com/us/technology/modular-ups/)

Current per phase

## How many amps at each size?

| UPS | at 208 V | at 480 V |
| --- | --- | --- |
| 10 kVA | 28 A | 12 A |
| 30 kVA | 83 A | 36 A |
| 60 kVA | 167 A | 72 A |
| 100 kVA | 278 A | 120 A |
| 300 kVA | 833 A | 361 A |
| 600 kVA | 1,665 A | 722 A |

kVA × 1,000 ÷ (√3 × V), at full load. The breakers and cables follow the UPS's own input current: see [UPS amps from kVA](https://www.aecups.com/us/blog/ups-amps-from-kva/).

Questions

## Questions people ask

#### What is a three-phase UPS?

A UPS that takes and delivers three-phase power: three lines 120 degrees apart, at 208 V or 480 V in the United States. It carries larger loads than a single-phase UPS with less current per conductor, which is why server rooms, data centers, hospitals and factories use it.

#### Single-phase or three-phase UPS?

Single-phase for loads up to about 20 kVA on 120 V or 120/240 V circuits; three-phase when the panel is three-phase or the load is larger. AEC three-phase UPS start at 10 kVA.

#### 208 V or 480 V?

208 V (208Y/120 V) suits server rooms and buildings that distribute at 208 V; 480 V suits large loads and data centers, with less than half the current for the same power. The UPS follows the panel it is connected to.

#### What is the difference between 480 V 3-wire and 4-wire?

A 4-wire supply carries the neutral, a 3-wire (delta) supply does not. CIRRO is built for 480 V 4-wire, INFINITE for 480 V 3-wire: pick the UPS by the supply on site.

#### How many amps does a three-phase UPS draw?

Current per phase = kVA × 1,000 ÷ (√3 × voltage): a 30 kVA UPS carries about 83 A per phase at 208 V and 36 A at 480 V, at full load and unity power factor.

#### Modular or tower?

A tower UPS is one unit of fixed size; a modular UPS holds power modules in a frame, so it grows by adding modules and stays on line when one is swapped (N+1). AEC offers both.

## Which three-phase UPS?

Send the supply, the load in kW and the minutes you need: we answer with the series, the model and the batteries.