Operating guide

# ETHERNO, step by step

6 ETHERNO procedures from the user manual, with the real screen at every step: start the UPS; shut the UPS down; daily check of the readings; a fault is showing; a mains failure; transfer to maintenance bypass. Section numbers refer to the manual.

Try the display [ETHERNO series](https://www.aecups.com/us/products/etherno/) [User manuals](https://www.aecups.com/us/products/etherno/#downloads)

## Daily use

#### Start the UPS Breakers, battery modules, ON/OFF, output breaker, loads — in the manual's order. §5.1 – 5.2 (p. 79), §2.1.3 (pp. 9–10), §2.1.5 · 8 steps

Before starting, with every breaker open (no power: the display is dark): wiring firm and color-coded, UPS grounded, N–PE voltage below 5 Vac, no short circuit on the output, load not above rating. Also: RS485 wiring if remote monitoring is used, wiring neat and tied, maintenance-bypass cover fitted and its breaker OFF, EPO input shorted (or wired to a closed remote EPO switch).

**Caution** Check the N–PE voltage with a meter: above 5 Vac the grounding is not good enough (§5.1).

Close the input and bypass breakers. The touch screen lights and initializes.

**You should see** Screen initializes, then the main page shows Bypass output (bypass → output, mains → REC. charging the battery).

**Caution** The load is already powered through the bypass.

Bypass output

Turn the knob of every battery module to the closed padlock: all green run indicators light.

**Caution** With the knob on the closed padlock the module switches on and its output connector carries DC voltage.

Bypass output

Tap the ON/OFF icon, bottom of the left column (or press both ON buttons under the screen for 1 s).

Press: **ON / OFF**

**You should see** “Confirm to power on?”

Bypass output

Confirm with OK.

Press: **OK**

**You should see** Inverter starting; about 10 s later the main page shows yellow energy flow: mains → rectifier → inverter → output.

Confirm power on

Close the OUTPUT breaker on the rear panel.

**You should see** Normal operation: INPUT, BYPASS and OUTPUT ON, maintenance bypass OFF.

Mains inverting (normal mode)

When the UPS runs steadily, switch on the loads, largest first and smallest last.

**Caution** Starting a large load last could trigger the overload protection.

Mains inverting (normal mode)

Check the output: tap Output on the flow diagram.

Press: **Output information**

**You should see** Output voltage, current, load % and frequency per phase.

Mains inverting (normal mode)

#### Shut the UPS down Cool-down, ON/OFF, battery modules off, breakers open. §5.3 (p. 80) · 6 steps

Switch off the loads and let the UPS run without load for about 10 minutes.

**Why** The fans carry the heat out before the UPS stops (§5.3).

Mains inverting (normal mode)

Tap the ON/OFF icon (or press both OFF keys under the screen together for 1 s).

Press: **ON / OFF**

**You should see** “Confirm to power off?”

Mains inverting (normal mode)

Confirm with OK.

Press: **OK**

**You should see** Bypass output: inverter off, the load is still fed by the bypass.

**Caution** The load stays powered through the bypass until the input and bypass breakers are opened.

Confirm power off

Turn the knob of every battery module to the open padlock: all module indicators go off.

**You should see** Module run, alarm and fault indicators all off (“Switched off (knob)” in the Battery modules list).

Bypass output

Open the INPUT and BYPASS breakers.

**You should see** The output stops; the screen goes dark once the UPS has no power left.

**Caution** Dangerous voltage can remain inside even when the UPS is off.

Main page — no output (initializing or bypass unavailable)

To isolate the UPS completely, also open the OUTPUT breaker and the upstream breakers.

**You should see** All breakers OFF, maintenance-bypass cover fitted.

#### Daily check of the readings Bypass, mains, battery and output pages from the flow diagram. §4.2 · 11 steps

From the main page, tap Bypass.

Press: **Bypass information**

**Why** Phase voltages are shown (the nameplate gives line voltage).

Mains inverting (normal mode)

Back to the main page: tap Back.

Press: **Back**

Bypass information

Tap Mains.

Press: **Mains information**

Mains inverting (normal mode)

Back.

Press: **Back**

Mains information

Tap Batt.: battery voltage, currents, SOC, SOH.

Press: **Battery information**

Mains inverting (normal mode)

Next page: remaining backup time.

Press: **Next**

Battery cabinet info 1

Mod. info: each battery module in detail.

Press: **Mod. info.**

Battery cabinet info 2

Pick another module with the box bottom left.

Press: **Select module**

Module info 1

Choose Mod.2.

Press: **Mod.2**

Module selection

Home, then Output.

Press: **Home**

Module info 1

Tap Output: voltage, current, power, load % and frequency.

Press: **Output information**

Mains inverting (normal mode)

## Alarms & faults

#### A fault is showing Read it, mute it, find it in the history. §4.6, §4.7, §5.9 · 5 steps

The alarm icon on the left is lit; the buzzer sounds when the UPS is on (Table 5-2 — this picture is in the off state, so it is silent).

**You should hear** Depends on the fault — see the Alarms & buzzer tab.

Fault alarm status

Tap the alarm icon.

Press: **Current fault**

**You should see** The current faults with date and time.

Fault alarm status

Back to the main page.

Press: **Back**

Current fault

Tap the buzzer icon to mute.

Press: **Buzzer**

**Caution** A long beep cannot be muted (§4.7).

Fault alarm status

Look the fault up in the Alarms & buzzer and Troubleshooting tabs; History record keeps it after it clears.

History record

#### A mains failure What the screen shows on battery and how long is left. §2.2.2 · 4 steps

The mains fails: the battery feeds the inverter with no break. The Mains icon is red.

**You should hear** Mains abnormal: 3 alarms every 10 s.

Battery inverting

Tap Batt. to see how long is left.

Press: **Battery information**

Battery inverting

Next page: remaining time at this load.

Press: **Next**

**Why** Decide whether to shut the loads down before the battery reaches its low-voltage point.

Battery cabinet info 1

If the mains does not come back, the UPS stops at the battery low-voltage point (long beep) and shuts itself down about 1 min after a complete outage. It restarts by itself when the mains returns.

Battery cabinet info 2

#### Transfer to maintenance bypass Keep the load powered while the UPS is worked on. §2.1.3 (pp. 9–10), §2.2.2 (p. 22) · 6 steps

The UPS runs normally. On the maintenance bypass the load runs on unprotected utility power.

Mains inverting (normal mode)

Remove the cover of the maintenance-bypass breaker (rear panel). The door switch opens: the UPS turns its inverter off and transfers the load to bypass. Check that the main page shows Bypass output.

Bypass output

Close the MAINTENANCE breaker.

**You should see** Maintenance-bypass output: the alarm icon lit (maintenance bypass detection).

Maintenance bypass

Open the INPUT, BYPASS and OUTPUT breakers. The load is fed through the maintenance bypass; the UPS input and output are disconnected.

To service the UPS, also turn the knob of every battery module to the open padlock, and wait 10 minutes.

**Caution** Hazardous voltage can be present inside even when the UPS is not operating: check with a meter before touching anything.

Return: turn every module knob to the closed padlock; close the INPUT, BYPASS and OUTPUT breakers, in that order; when the touchscreen shows the bypass output voltage, open the MAINTENANCE breaker; refit its cover; press both ON keys for 1 s.

Press: **ON keys** (hold 1 s)

**You should see** About 10 s later the main page shows normal mode.

Bypass output

**27 more ETHERNO procedures**, settings, commissioning, parallel systems and service, with the full display simulator, are in the [AEC partner portal](https://www.aecups.com/us/partners/#tools).

## Alarms and buzzer

| Fault shown | Buzzer | Meaning |
| --- | --- | --- |
| **EPO** | Long beep | Emergency power off: bypass and inverter outputs all closed. For the EPO input terminal: released after full shutdown and the port short-circuited again (§2.1.5). |
| **Mode fault** | Long beep | System mode setting does not match the wiring: check mains and bypass wiring against the set mode. |
| **Maintenance bypass fault** | Long beep | Maintenance-bypass protection, inverter output off: check the maintenance-bypass cover and door switch, and the maintenance-bypass detection port on the backplane. |
| **Output fault** | Long beep | Output short circuit or overload. |
| **Mode mismatch** | Long beep | Parallel: input/output mode differs between UPS. |
| **Voltage mismatch** | Long beep | Parallel: output voltage setting differs. |
| **Frequency mismatch** | Long beep | Parallel: frequency setting differs. |
| **Bypass mismatch** | Long beep | Parallel: bypass voltage or frequency setting differs. |
| **Pattern mismatch** | Long beep | Parallel: parallel mode setting differs. |
| **Power mismatch** | Long beep | Parallel: output power setting differs. |
| **Battery number mismatch** | Long beep | Parallel: the battery module quantity of this UPS differs from the system. |
| **Parallel mismatch** | Long beep | Parallel: parameter settings differ. |
| **Short mismatch** | Long beep | Parallel: “short circuit to bypass” setting differs. |
| **Two-ended fault** | Long beep | Parallel cable off at both ends. |
| **Single-ended fault** | Slow beep | Parallel cable off at one end. |
| **Auxiliary power supply failure** | Long beep | Internal power supply failed; if it does not recover, call service. |
| **Fan failure** | Rapid beep (about every 0.2 s) | Check fans for damage or blockage. |
| **CAN fault** | Slow beep (about every 2 s) | Parallel CAN communication abnormal: parallel cable damaged, or only one UPS running. |
| **SCI fault** | Long beep | Internal communication abnormal; if it persists, call service. |
| **No redundancy in the parallel UPS** | Slow beep (about every 2 s) | Total load of the parallel system is above the full load of one UPS: the load is above the redundancy limit. |
| **Mains abnormal — phase sequence** | Long beep | Mains input phase sequence wrong: check input wiring. |
| **Mains abnormal** | 3 alarms every 10 s | Missing neutral, outage, over/under-voltage, over/under-frequency: check the mains input. |
| **Bypass abnormal** | Slow beep (about every 2 s) | In normal mode the bypass voltage, frequency or phase sequence is abnormal, or the mode setting does not match the wiring: check the bypass breaker is closed, the bypass phase sequence, and that the bypass wiring matches the system mode. |
| **Battery abnormal — over-voltage** | Slow beep (about every 2 s) | Battery overvoltage protection, charging fuse failure or overvoltage alarm: check the battery. |
| **Battery abnormal — wiring / under-voltage** | Rapid beep (about every 0.2 s) | Battery wiring fault, charger short circuit, undervoltage protection or undervoltage warning: check the module plug-ins and the battery status. |
| **Battery abnormal — charging temperature high** | No beep | Battery charging temperature too high. |
| **Rectifier abnormal** | Rapid beep (about every 0.2 s) | Rectifier fault. Contact AEC service. |
| **Inverter abnormal** | Long beep | Inverter fault. Contact AEC service. |

## Troubleshooting

#### Mains is normal, the UPS outputs but runs on battery and beeps intermittently

- Contactors or input terminals loose or damaged.
- Mains voltage or frequency on the screen out of the allowed range.
- Mains input breaker open: close it.

#### Connecting the UPS blows the fuse or trips the breaker

- Input or output wiring short-circuited.

#### Screen and output normal, but output stops as soon as the load is connected

- Severe overload or output short circuit: reduce the load or find the short (often a faulty power strip or a damaged load).
- Loads not started biggest-first: restart, then start the large loads first.

#### Long beep, fault indicator on, UPS on bypass, inverter failure

- Output overload above rating: reduce load or use a larger UPS. A short transfer on a load inrush that recovers by itself is normal.
- Over-temperature: air inlet/outlet blocked or room too hot.

#### On a power failure it does not go to battery, or reaches battery under-voltage quickly

- Modules with lost capacity: check their SOH and replace them.
- Charger fault: the battery is not being charged.
- Module plug-in loose or bad contact.

#### On a power failure the UPS keeps running but the computers halt

- Poor grounding: N–PE floating voltage too high.

#### Module quantity on screen differs from the modules installed

- Li-batt. module quantity in Batt. manage not set to the real number.

#### Mains normal, SOC below 80 %, the lithium modules do not charge

- UPS charging voltage out of the allowed range.
- Module plug-in loose.
- Lithium battery switched off (Batt. manage → Li-batt. ON).

#### The lithium system protects as soon as it starts discharging

- Load above the battery system's rated output: reduce the load or add modules.
- Not charged for a long time: low SOC or damaged cells.

#### On battery the system shuts down after a while

- Normal end-of-discharge low-voltage protection; it restarts and recharges when mains returns.

#### Red indicator on a lithium module

- Low-SOC protection.
- Operating temperature out of range or module fan not running.
- Module fault: replace the module (switch it off, remove it, call AEC service).

Practice

## Follow it on the display.

Short guided tours on the real ETHERNO display.

Mains inverting (normal mode)

### Shut the UPS down

Step 1 of 6

Switch off the loads and let the UPS run without load for about 10 minutes.