Operating guide

# FERRUS SP, step by step

2 FERRUS SP procedures from the user manual, with the real screen at every step: start the UPS on utility power; read the UPS. Section numbers refer to the manual.

Try the display [FERRUS SP series](https://www.aecups.com/us/products/ferrus-sp/) [User manuals](https://www.aecups.com/us/products/ferrus-sp/#downloads)

## Start and stop

#### Start the UPS on utility power Battery breaker, input breaker, about a minute to line mode, then the loads. §6.1.1 (p. 25), §4.2 (p. 17) · 7 steps

Before the first start: the wiring is checked, the loads are switched off, and the battery number set matches the blocks installed (§5.3).

Long-backup models: close the external battery breaker.

Close the input breaker. The cooling fans start and the rectifier begins to start up.

Home page

About one minute later the UPS transfers to Line mode. If the utility is abnormal it runs in Battery mode without interrupting the output.

**You should see** REC and INV green on the panel (§5.1).

Home page

Check the home page: power flow from the utility through the rectifier and inverter to the load, no alarm. Check the output voltage of the two legs.

Press: **Output voltage L1/L2**

**You should see** 120/120 V.

Home page

Switch on the loads one at a time (§4.2.3). Then check the load: open Data.

Press: **Data**

Home page

Open Load.

Press: **Load**

**You should see** KVA, kW and % of each leg.

Data, page 1

## Daily use

#### Read the UPS Input, output, load and battery pages. Touchscreen (not in the v1.0 manual, readings as §5.2, p. 22) · 13 steps

From the home page, open Data.

Press: **Data**

**You should see** Bypass, Input, Output, Load, Battery, Information.

Home page

Open Input: voltage L1–L2, current, frequency, power factor.

Press: **Input**

Data, page 1

Back to the Data menu.

Press: **Back**

Data — Input

Open Bypass: the bypass voltage and frequency.

Press: **Bypass**

Data, page 1

Back.

Press: **Back**

Data — Bypass

Open Output: voltage and current of L1/L2.

Press: **Output**

**You should see** 120.0/120.0 V, 60.00 Hz.

Data, page 1

Back.

Press: **Back**

Data — Output

Open Load: kVA, kW and % per leg.

Press: **Load**

Data, page 1

Back.

Press: **Back**

Data — Load

Open Battery: voltage, capacity, remaining time.

Press: **Battery**

Data, page 1

Back.

Press: **Back**

Data — Battery

Open Information: DC bus, charger and temperatures.

Press: **Information**

Data, page 1

Transformer temp.: the output isolation transformer; the rectifier and inverter IGBT temperatures below it.

Press: **Transformer temp. (°C)**

Data — Information

**16 more FERRUS SP procedures**, settings, commissioning, parallel systems and service, with the full display simulator, are in the [AEC partner portal](https://www.aecups.com/us/partners/#tools).

## Alarms and buzzer

| No. | Alarm | Cause and action |
| --- | --- | --- |
| **1** | Battery not connected | Check that the battery cables are connected correctly, the battery breaker / fuse is closed, and the batteries are not damaged. |
| **2** | Emergency power off (EPO) | Check that the EPO contact is closed correctly, or whether the EPO was operated. |
| **3** | Inverter under-rated | The hardware is not configured for the selected rated power. |
| **4** | Input fault | Check that the utility input voltage and frequency are in range and the input and external breakers are closed. Restore the utility supply, or the output stops when the battery reaches end of discharge. |
| **5** | Bypass phase sequence reversed | Check whether the bypass input is phase-reversed. |
| **6** | Bypass abnormal | Bypass voltage or frequency out of the set range: check the bypass input supply and the bypass input breaker. |
| **7** | Bypass fault | Bypass SCR open or shorted: contact AEC service. |
| **8** | Bypass overload | Reduce the load below 95 % of the rating. |
| **9** | Bypass overload timeout | The bypass overload lasted too long: the output has been switched off. |
| **10** | Hourly transfer limit reached | 5 transfers in 1 hour: check the utility supply and the load. |
| **11** | Output short circuit | Faulty load or output breaker. Find and switch off the faulty load, check the breaker, then clear the fault to restart. |
| **12** | Battery end of discharge | The battery is discharged after a utility failure. |
| **13** | Battery self-test failed | Check for active alarms; check that the battery can supply more than 20 s. |
| **14** | Rectifier fault | DC bus over/undervoltage, short circuit or IGBT open. Clear the fault; if it persists, contact AEC service. |
| **15** | Inverter fault | Inverter voltage abnormal or IGBT open. Clear the fault; if it persists, contact AEC service. |
| **16** | Rectifier over-temperature | Heatsink too hot or sensor disconnected: check fans, ventilation, sensor wiring and room temperature. |
| **17** | Fan failure | One or more fans faulty or blocked: check each fan. |
| **18** | Overload | Inverter overloaded: remove non-critical loads, or the UPS transfers to bypass. |
| **19** | Inverter overload timeout | The UPS has transferred to bypass; if the bypass is also overloaded the output stops. Reduce the load: the UPS returns to the inverter. |
| **20** | Inverter over-temperature | Heatsink too hot or sensor disconnected: check fans, ventilation, sensor wiring and room temperature. |
| **21** | Low battery voltage | Battery capacity low while on battery. |
| **22** | Input neutral disconnected | 3 / 1 model only: the input neutral is missing or not connected. |
| **23** | Bypass fan failure | One or more fans faulty or blocked: check each fan. |
| **24** | Manual shutdown | Inverter switched off or transferred to bypass by hand. |
| **25** | Battery or charger fault | No charger output: contact AEC service. |
| **26** | EOD restart inhibit | Automatic restart after end of discharge is inhibited. |
| **27** | Input overcurrent timeout | Input current above the limit for too long: the UPS goes to battery or bypass. Check the input voltage, the load and whether the source (transformer, generator) is too small; contact AEC service if needed. |
| **31** | System power supply disabled | No output available. |
| **32** | Relay open circuit | Inverter relay open. |
| **33** | Relay short circuit | Inverter relay shorted. |
| **34** | Inverter protection | Inverter output voltage out of range or DC bus overvoltage. |
| **35** | Parallel cable fault | One or more parallel cables disconnected. |
| **36** | Synchronization signal lost | Contact AEC service. |
| **37** | Current-sharing failure | Contact AEC service. |
| **38** | Input current imbalance | Contact AEC service. |
| **39** | Maintenance breaker closed | The maintenance bypass switch is on BYPASS: the UPS has transferred to bypass and the inverter cannot start. |
| **40** | Bypass over synchronization | Bypass outside the synchronization range. |
| **41** | Battery self-test in progress | The battery is being tested. |
| **42** | Battery maintenance in progress | The battery is being maintained. |
| **43** | Battery maintenance failed | Check for other alarms and that the battery capacity supports more than 20 s of discharge. |
| **44** | Manual bypass | The UPS was transferred to bypass by hand. |
| **45** | Battery reverse connection | Battery polarity reversed: check the battery pack polarity on BAT+ · BAT− with a voltmeter (§4.2.3). |
| **46** | Scheduled shutdown | Automatic shutdown at the set time. |
| **47** | BMS communication failure | Check the BMS communication wiring and that the BMS protocol matches the UPS. |
| **48** | Output transformer over-temperature | Check the ambient temperature and the load level; contact AEC service. |
| **—** | Communication Abnormal (status bar) | Touchscreen message, not in the v1.0 alarm list: the screen is not receiving data from the UPS controller. Restart the UPS; if it stays, contact AEC service. |

## Troubleshooting

#### The screen stays dark, no LEDs

- No input and no battery, or the UPS is off: check the input breakers and the utility supply.
- On battery, press COLD START on the rear panel.

#### The UPS runs on battery with utility present

- Check the input voltage (176–275 V) and the input breaker; see alarm 4.

#### The load is on bypass

- Read the alarm: overload (reduce the load), over-temperature (check vents and fans) or a manual bypass.
- Return with Control › Function › Manual Transfer to Inverter once the cause is removed.

#### Short runtime

- Let the battery recharge on utility power, run a battery test (alarm 13 if it fails); replace old batteries (§7.2).

#### No network access

- Check Set › NetWork and the SNMP card (setting category 345, §5.3).

#### Wrong output voltage (120 V instead of 240 V or the reverse)

- Check the output jumpers and the rated values (Set, page 2).

#### One leg overloaded, the other lightly loaded

- Move 120 V loads to the lighter leg.

#### Parallel units do not share the load

- Check the parallel cables (alarm 35) and that each unit has its own ID and the same settings.

#### "Communication Abnormal" in the status bar

- The screen is not receiving data from the UPS controller: restart the UPS; if it stays, contact AEC service.

Practice

## Follow it on the display.

Short guided tours on the real FERRUS SP display.

Home page

### Start the UPS on utility power

Step 1 of 7

Before the first start

The wiring is checked, the loads are switched off, and the battery number set matches the blocks installed.