Operating guide

# INFINITE, step by step

5 INFINITE procedures from the user manual, with the real screen at every step: shut the UPS down; daily check of the readings; read a fault: current list, history, waveforms; silence the buzzer; to maintenance bypass and back. Section numbers refer to the manual.

Try the display [INFINITE series](https://www.aecups.com/us/products/infinite/) [User manuals](https://www.aecups.com/us/products/infinite/#downloads)

## Daily use

#### Shut the UPS down Loads off, inverter OFF, switches open, wait for the screen to go dark. §5.1.4 (p. 85) · 5 steps

Turn off the user loads.

**Caution** With an abnormal bypass, an inverter shutdown cuts the output: the load must be able to lose power.

Mains inverter output (normal)

Tap the Inverter ON/OFF icon.

Press: **Inverter ON / OFF**

**You should see** “Confirm to power off?”

**Why** Or hold the two OFF buttons on the operation panel for 3 s.

Mains inverter output (normal)

Tap Single OFF (Parallel OFF on a parallel system, Figure 5-5).

Press: **Single OFF**

**You should see** Inverter indicator off, bypass indicator green: Bypass output.

Inverter OFF

If only the inverter had to stop, you are done: the load is on bypass. For a full shutdown go on.

Bypass output — inverter off

Open the external battery switch, the mains switch, the bypass switch and the output switch, in that order. Wait until the touch screen and every LED are off.

**You should see** The output stops; the touch screen and every LED go dark.

**Caution** Dangerous voltage remains inside: wait 10–15 minutes and check with a meter before you open covers (§5.1.4, §1.5).

#### Daily check of the readings Mains, bypass, battery, rectifier, inverter and output from the diagram. §6.3 (Table 6-1, p. 95) · 12 steps

From the main page, tap Mains.

Press: **Mains information**

**You should see** Phase and line voltage, current, frequency.

Mains inverter output (normal)

Back.

Press: **Back**

Mains info

Tap Bypass.

Press: **Bypass information**

Mains inverter output (normal)

Back.

Press: **Back**

Bypass info

Tap Battery: voltage, currents, remaining capacity and time, status.

Press: **Battery information**

**Why** On mains the status reads Floating charge (or Equalized charge after a discharge).

Mains inverter output (normal)

Back.

Press: **Back**

Battery info

Tap Rectifier: each power module's input side.

Press: **Rectifier information**

Mains inverter output (normal)

Module-1 picks another module.

Press: **Module-1**

Rectifier info

Back.

Press: **Back**

Rectifier info

Tap Inverter: each module's output, load rate and power.

Press: **Inverter information**

**Why** The modules should share the load evenly; one far off points to a module problem.

Mains inverter output (normal)

Back.

Press: **Back**

Inverter info

Tap Output: the total output, load rate and power factor.

Press: **Output information**

Mains inverter output (normal)

#### Read a fault: current list, history, waveforms From the alarm icon to the history record and wave capture. §6.2, §6.4 (Table 6-2), §2.11 · 10 steps

The alarm icon is red: tap it.

Press: **Current fault**

**You should see** Current abnormal: each fault with date and time.

Fault protection — no output

Open Info manage (magnifier).

Press: **Info manage**

Current abnormal

History record: what happened before and after.

Press: **History record**

Info manage

Scroll to older records.

Press: **Scroll down**

**Why** “recover” lines show when each event ended.

History record

Back to Info manage.

Press: **Back**

History record

Smart wave capture: the waveforms saved at the fault.

Press: **Smart wave capture**

Info manage

Pick the capture with the fault's time — here 01, a mains power down.

Press: **Capture 01**

**You should see** The waveforms around the event: the mains voltages fall to zero at the cursor, the bus voltage holds.

Smart wave capture

Untick a signal to read the others more easily; Back returns to the list.

Press: **Back**

Wave capture 01 — mains power down

Before calling service, export the records (Record manage) and note the S/N (Device info).

Press: **Back**

Smart wave capture

Device info: model and S/N.

Press: **Device info**

Info manage

#### Silence the buzzer What can be silenced and what cannot. §6.2.2 (p. 95) · 4 steps

A fault sounds the buzzer. Read it first: tap the alarm icon.

Press: **Current fault**

Fault protection — no output

Back to the main page.

Press: **Home**

Current abnormal

Tap the buzzer icon to turn the buzzer off.

Press: **Buzzer**

**You should hear** Silent — until a new fault occurs, which turns it back on.

**Caution** A continuous beep cannot be silenced from the icon: it stops only when its cause is removed (EPO, output faults, overload protection, system and cabinet faults — Alarms tab).

Fault protection — no output

Tap it again to turn the buzzer back on.

Press: **Buzzer**

Fault protection — no output

## Commissioning & service

#### To maintenance bypass and back Without dropping the load. §7.1.1 – 7.1.2 (pp. 116–118) · 9 steps

Inverter off first: tap Inverter ON/OFF.

Press: **Inverter ON / OFF**

**Caution** With an abnormal bypass this cuts the output: the load must be able to lose power.

Mains inverter output (normal)

Single OFF (Parallel OFF on a parallel system).

Press: **Single OFF**

**You should see** Inverter indicator off, bypass indicator green: Bypass output.

Inverter OFF

Check the inverter is off, then close the external maintenance bypass switch.

Bypass output — inverter off

The screen shows “Maintenance bypass open”: the load is on the maintenance bypass.

Maintenance bypass output

Open the external battery switch, utility switch, bypass switch and output switch, one by one. Wait until screen and LEDs are off; after 10–15 minutes (§1.5, p. 13; §5.1.4), check with a meter, then maintenance can start.

**Caution** Never close the output switch in this state. The maintenance bypass is a separate source: the output side can carry lethal voltage.

Maintenance bypass output

Return: the bypass input must be normal. Close the bypass switch and the mains switch: the touch screen lights up, still showing the maintenance bypass. Bypass module ready switch locked; close the external battery switch (no “Not allow to connect battery” alarm first).

Maintenance bypass output

Close the output switch: the Output icon on the main page lights. When the bypass indicator is green, open the maintenance bypass switch: the message disappears and the beeping stops.

Bypass output — inverter off

Lock the ready switches of all power modules. When their run indicators flash green slowly, start the inverter: Inverter ON/OFF.

Press: **Inverter ON / OFF**

Bypass output — inverter off

Single ON (Parallel ON on a parallel system).

Press: **Single ON**

**You should see** The DC/AC indicator turns green; about 10 s later the bypass indicator goes off: inverter output.

Inverter ON — single system

**38 more INFINITE procedures**, settings, commissioning, parallel systems and service, with the full display simulator, are in the [AEC partner portal](https://www.aecups.com/us/partners/#tools).

## Alarms and buzzer

| Fault information | Buzzer & lamps | What it blocks / means |
| --- | --- | --- |
| **Mains overvoltage / under-voltage / unbalance / over- or underfrequency / power down / phase loss / phase sequence abnormal / large mains harmonic component / mains flash drop / mains PFC overload protection / large mains DC component** | Slow beep · rectifier LED red · Mains icon red · yellow lamp | Mains supply not allowed: the UPS runs on battery. Check the input voltage and wiring. |
| **Battery reverse connection / overvoltage / charger overcurrent / battery circuit abnormal / under-voltage protection / overload** | Rapid beep · battery LED red · Battery icon red · yellow lamp | Battery power not allowed. Check polarity, battery switch and cells. |
| **Bypass overvoltage / under-voltage / unbalance / over- or underfrequency / power down / phase loss / phase sequence abnormal / large bypass harmonic components** | Slow beep · bypass LED red · Bypass icon red · yellow lamp | Bypass output not allowed: the inverter cannot transfer to bypass. Check the bypass window (Output setting → Bypass range). |
| **ECO power down fast detection / overvoltage / under-voltage / over- or underfrequency; WECO under-voltage** | Slow beep · yellow lamp | ECO (W-ECO) output not allowed: the load goes to inverter. |
| **Inverter output fault / output short circuit / inverter over- or under-voltage / low output PF / large output DC component** | Continuous beep · inverter LED red · Output icon red · red lamp | Inverter output not allowed. Check the output for short circuits and the load. |
| **Output circuit abnormal** | Slow beep · inverter LED red · Output icon red · red lamp | Output circuit problem; no protection action. |
| **System fault / System bypass fault / System inverter fault / System EPO on / EPO on** | Continuous beep · red lamp | System fault. With System EPO on or EPO on, bypass and inverter output are not allowed: clear EPO1/EPO2 and restart (see “Emergency power off and clearing it”). |
| **Bypass SCR abnormal** | Continuous beep · bypass LED red · Bypass icon red · red lamp | Bypass output not allowed; if OUT.2 (SCR short-circuit) drives a shunt trip, the bypass breaker opens. |
| **Bypass overload protection / inverter overload protection** | Continuous beep · load LED red · Output icon red · red lamp | Bypass overload protection: no bypass and no inverter output; inverter overload protection: no inverter output. Reduce the load. |
| **Parallel cable abnormal / parallel system master permissions fault** | Continuous beep · red lamp | Parallel cable abnormal: inverter output not allowed — check the parallel cables. Master permissions fault: no protection action. |
| **External maintenance bypass enabled (system fault)** | Continuous beep · red lamp | Inverter output not allowed while the maintenance bypass is closed. The same event as an input dry contact gives a slow beep and yellow lamp (below). |
| **System battery charge disabled / system battery discharge disabled** | Rapid beep · battery LED red · Battery icon red · red lamp | Charging or discharging blocked by an input dry contact. |
| **Bypass overtemperature** | Continuous beep · bypass LED red · Bypass icon red · red lamp | Bypass output depends on “Bypass output allowed when over-temperature”. |
| **Cabinet fault / inverter output overcurrent / rectifier or inverter fault self-locking / battery overload protection / battery discharge protection / UPS fault** | Continuous beep · red lamp | Cabinet fault: call AEC service. |
| **Cabinet overtemperature / battery high or low temperature / battery under-voltage alarm / backup time insufficient** | Rapid beep · yellow lamp | Cabinet pre-alarm: the UPS still runs. Check ventilation, battery temperature, remaining time. |
| **Output overload alarm** | Rapid beep · load LED red · Output icon red · yellow lamp | Overload pre-alarm: reduce the load before overload protection. |
| **Output frequency out of range / bypass auxiliary power abnormal / bypass overtemperature alarm / partial power module PFC abnormal / battery power-on auto start disabled** | Rapid beep · yellow lamp | Cabinet pre-alarm. |
| **Battery not connected / auxiliary power abnormal** | Slow beep · yellow lamp | Cabinet alarm: check the battery switch. |
| **Bypass installation not ready** | Slow beep · bypass LED red · Bypass icon red · yellow lamp | Bypass output not allowed: check the bypass module and its ready switch. |
| **Bypass module offline** | Slow beep · bypass LED red · Bypass icon red | Bypass output not allowed: the bypass module does not communicate. |
| **Setting / battery parameter mismatch, module or cabinet count mismatch, system card not ready / flash abnormal / slot address repeat, system card on/off status not synchronized with master card, master/backup card parameters out of sync, output state out of sync** | Slow beep · yellow lamp | Cabinet alarm: settings or cards do not agree. |
| **Current mode is bypass output / fan dedusting** | Slow beep · yellow lamp | Cabinet alarm: information on the running state (the inverter is off and the bypass feeds the load, or the fans are dedusting). |
| **Power-on failure: load too large to invert output, load unknown waiting for common inversion, PFC / INV / CCM software inconsistent, module hardware or version inconsistent, key parameter mismatch, parallel cabinet address conflict, module version inconsistent** | Slow beep · yellow lamp | Static startup not allowed. Compare module versions (Device info p. 3) and parallel addresses. |
| **Component failure: bypass / cabinet / system card NTC, bypass or cabinet fan abnormal, parallel cable 1/2 alarm, bypass 1/2 or monitoring card installation not ready, dry contact expansion card offline** | Slow beep · yellow lamp | A component failed: call service. |
| **Communication abnormal: inner sync / equalized-current / display CAN, inter-cabinet CAN, BMS communication fault, internal SCI** | Rapid beep · yellow lamp | Internal or parallel communication lost; BMS fault = check the BMS card and RJ45 to the lithium cabinet. |
| **Smart mode: generator mode enable / charge prohibited, only one BSC system detected, load above safety load, no (insufficient) module / cabinet / system card redundancy, self-load faults, inverter and bypass out of sync** | Slow beep · yellow lamp | Smart mode alarm: information on the running mode and redundancy. |
| **Input dry contact: battery abnormal / grounding abnormal / battery switch off** | Rapid beep · battery LED red · Battery icon red · yellow lamp | Reported by an input dry contact. |
| **Input dry contact: bypass switch disconnected** | Slow beep · bypass LED red · Bypass icon red · yellow lamp | The bypass switch is open. |
| **Input dry contact: output switch disconnected** | Slow beep · yellow lamp | The output switch is open. |
| **Input dry contact: battery charge disabled / battery discharge disabled** | Rapid beep · battery LED red · Battery icon red · yellow lamp | Charging or discharging turned off by an input dry contact. |
| **Input dry contact: generator mode / SPD abnormal / external maintenance bypass enabled / environmental smog abnormal / mains abnormal** | Slow beep · yellow lamp | Reported by an input dry contact. |
| **Power module 1/2/3 offline, system card 1/2 offline** | Slow beep · yellow lamp | Offline alarm state: the module or card is not seen by the system. |

## Troubleshooting

#### Mains is normal but the UPS runs on battery, the buzzer beeps intermittently

- Poor contact in the mains connections or sockets feeding the UPS.

#### Closing the mains or power switch blows the fuse or trips the breaker

- Input or output wiring wrong, e.g. a live wire swapped with ground (chassis).

#### The UPS outputs 480 V but stays on bypass

- Load above the UPS rating: reduce it or use a larger UPS.
- A temporary bypass caused by a load inrush that recovers on its own is normal.

#### Output normal after start-up, but stops as soon as the load is started

- Severe overload or a short circuit in the output (adapter sockets, damaged equipment).
- Loads not started largest first: restart the UPS, then start loads from the largest to the smallest.

#### The UPS shuts down by itself after a while

- Battery under-voltage protection at the end of a discharge: normal. When mains returns the UPS restarts and charges.
- If mains stays off a long time, open the battery switch to protect the battery, then restart the UPS and recharge fully when mains returns.

#### After long running the buzzer beeps continuously and the screen shows battery under-voltage

- A low utility voltage kept the UPS on battery until the under-voltage protection: check the utility. Recharge the battery fully as soon as possible: a battery left at under-voltage loses life.

#### Output fine on mains, nothing on battery

- Battery faulty or seriously damaged.
- Charger fault: the battery never charged.
- Battery wiring loose or poor terminal contact.
- Battery switch open.
- After a severe overload the UPS was not restarted and stayed on bypass.

#### Continuous beep, the UPS goes to bypass

- Read the fault on the touch screen (Current fault).

#### Mains present but the buzzer beeps intermittently

- Mains voltage or frequency outside the UPS's input range.

#### UPS fine after a mains failure but the user equipment stops

- Poor grounding of the installation.

#### System fault (emergency measure, §7.8.1)

- Switch the inverter off; if needed turn off the user load and open the UPS input/output switches to prevent further damage; call service.

#### The fault indicator of a power module is on

- The power module is faulty and isolates itself; the system normally keeps running with less redundancy. Set its ready switch to unlocked, remove it and call AEC service. Wait 10–15 min and measure before opening it.
- Never reinsert a removed faulty module, and never clear alarms by pulling modules.

Practice

## Follow it on the display.

Short guided tours on the real INFINITE display.

Mains inverter output (normal)

### Shut the UPS down

Step 1 of 5

Turn off the user loads.

With an abnormal bypass, an inverter shutdown cuts the output: the load must be able to lose power.

## Need a technician?