# L6 lithium cabinet, step by step

3 L6 lithium cabinet procedures from the user manual, with the real screen at every step: daily check of a cabinet; look at another cabinet; an alarm is showing. Section numbers refer to the manual.

Try the display [L6 cabinets](https://www.aecups.com/us/products/lithium-batteries/) [User manuals](https://www.aecups.com/us/downloads/)

## Daily use

#### Daily check of a cabinet Home, system info, cabinet status and data, cells. §2.3 – 2.4 (pp. 3–13) · 10 steps

Home: the cabinet color (blue normal, yellow alarm, red protected, gray not connected), work mode, status, current, voltage, SOC.

Press: **Sys. info**

System home

Sys. info: where the highest and lowest cell voltage and temperature are. Tap outside the window to close it.

Press: **Close**

System info

Tap the cabinet.

Press: **Battery cabinet**

**You should see** Communication, fire control, insulation, DC breakers and every module's state.

System home

BAT cabinet data: voltage, current, SOC and the module statistics.

Press: **BAT cabinet data**

BAT cabinet status

Scroll down for the cell statistics.

Press: **Scroll down**

BAT cabinet data 1

Scroll back up.

Press: **Scroll up**

BAT cabinet data 2

Open Mod. status & data.

Press: **Mod. status & data**

BAT cabinet data 1

Cell data: every cell of a module, voltage first.

Press: **Cell data**

Module status & data 1

Temp. shows the cell temperatures.

Press: **Temp.**

Cell data — voltage

Health mgt.: the health of every module and cell.

Press: **Health mgt.**

Cell data — temperature

#### Look at another cabinet Switch device on a multi-cabinet system. §2.4 (pp. 8–9) · 3 steps

On any monitoring page, tap Switch device on the right edge.

Press: **Switch device**

BAT cabinet status

Pick the cabinet, e.g. LITHIUM\_2 (slave 1).

Press: **LITHIUM\_2**

Switch device

Determine.

Press: **Determine**

**You should see** The monitoring pages now show that cabinet.

Switch device

## Alarms & history

#### An alarm is showing Read, confirm, find it in the records. §2.3.2, §2.5.1 (pp. 6–7, 14–15) · 7 steps

The bell at the top shows the number of alarms. Tap Alarm.

Press: **Alarm**

System home

Sort by level: prompting information, general, serious, critical alarm.

Press: **Grade rank**

Alarm info

Confirm marks one as seen; you can type a description.

Press: **Confirm**

**Caution** Confirming an alarm is only for record keeping. It does not clear the alarm: the cause must still be found and fixed (§2.3.2, p. 7).

Alarm info

Report mgt.

Press: **Report mgt.**

**You should see** Event record: every alarm with time, level and confirmation.

Alarm info

Screening filters by device, level, recovered or not, confirmed or not.

Press: **Screening**

Event record

Fault record.

Press: **Fault record**

Event record — screening

View shows the data recorded around the fault.

Press: **View**

Fault record

**19 more L6 lithium cabinet procedures**, settings, commissioning, parallel systems and service, with the full display simulator, are in the [AEC partner portal](https://www.aecups.com/us/partners/#tools).

## Alarms and buzzer

| Shown | Where | Meaning |
| --- | --- | --- |
| **Blue cabinet** | Home | Normal. |
| **Yellow cabinet** | Home | Alarm. |
| **Red cabinet** | Home | Protected. |
| **Gray cabinet** | Home | Not connected (in a multi-cabinet system, also a slave whose address is not set yet). |
| **Alarm levels** | Alarm › Grade rank | Prompting information, general alarm, serious alarm, critical alarm — from the least to the most severe. |
| **Event record levels** | Report mgt. › Screening | Prompt message, general, important, major, emergency alarm — the levels used by the event record filter. |
| **Module normal / alarm / protection / unknown** | Monitoring | Green / orange / red / gray dot of each module. |
| **Healthy / commonly / unknown** | Health mgt. | Green / orange / white mark of each cell. |
| **Charge / discharge / sleep** | Home and Monitoring | Work mode: charging, feeding the UPS, or at rest (sleep is needed for a group test). |

Practice

## Follow it on the display.

Short guided tours on the real L6 lithium cabinet display.

System home

### Daily check of a cabinet

Step 1 of 10

Home: the cabinet color (blue normal, yellow alarm, red protected, gray not connected), work mode, status, current, voltage, SOC.

## Need a technician?

AEC service supports commissioning, maintenance and 24/7 after-sales: tell us the UPS and what it shows.