Operating guide

# RADIANT · CIRRO, step by step

4 RADIANT · CIRRO procedures from the user manual, with the real screen at every step: read the UPS: cabinet, then one module; look at the waveforms; start the UPS (normal mode); shut the UPS down. Section numbers refer to the manual.

[Every screen explained](https://www.aecups.com/us/support/guides/radiant-manual/#display) Try the display [RADIANT series](https://www.aecups.com/us/products/radiant/) [User manuals](https://www.aecups.com/us/products/radiant/#downloads)

## Daily use

#### Read the UPS: cabinet, then one module Where each reading lives. §4.2.2–4.2.3 (pp. 37–40) · 4 steps

From the home page, open the Cabinet menu.

Press: **Cabinet**

**You should see** Bypass, Main, Output, Load and Battery tabs.

Home page

Open Battery: capacity, remaining time and temperatures.

Press: **Battery**

**You should see** Voltage, current, capacity, remain time, temperatures.

Cabinet — Bypass

Open the Module menu: one power module at a time.

Press: **Module**

**You should see** Input, Output, Load and Information tabs.

Cabinet — Battery

Information: bus and battery voltage, charger, fan and capacitor hours, temperatures.

Press: **Information**

**Why** In the module list, green is the module you are viewing; black is a connected module.

Module — Input

#### Look at the waveforms Output voltage, output current and bypass voltage. §4.2.7 (p. 54) · 4 steps

Open Scope.

Press: **Scope**

**You should see** The output voltage waveform; yellow = A, green = B, red = C.

Home page

Switch to the output current.

Press: **Output Current**

Scope — Output Voltage

And the bypass voltage.

Press: **Bypass Voltage**

Scope — Output Current

Read the bypass voltage waveform of the three phases.

Press: **Waveform**

**Why** The pictures are flat: the display is not connected to a UPS.

Scope — Bypass Voltage

## Start and stop

#### Start the UPS (normal mode) Breakers in order; the rectifiers and the inverters start by themselves; then the battery. §5.1.1 (p. 55) · 7 steps

All breakers open. The commissioning engineer starts the UPS after the installation is complete. Check the phase rotation of the cables (§3.7.4, p. 26).

**Caution** During this procedure the output terminals become live. If loads are connected, check with their users that it is safe; otherwise isolate them from the UPS output.

Home page

RADIANT-IB and CIRRO-IB: close the Output (Q4), Input (Q1) and Bypass input (Q2) breakers one by one; where the cabinet has only the manual bypass breaker, close the external input and external bypass input breakers (§5.1.1 step 2). RADIANT 15–90 kVA: the Bypass and Output breakers in the frame and the external output breaker, then the external main input breaker and the Input breaker; CIRRO 60–1,600 kVA: the upstream feeders, the Bypass Input and Output breakers, then the Main Input breaker.

**You should see** The touchscreen lights and shows the home page; the rectifiers start, and after about 30 s the static bypass closes (§5.1.1 steps 3–5).

Home page

Open Log: every event of the start-up is there (§5.1.1 note). CIRRO 60–1,600 kVA: check that there is no fault; if there is, stop and call AEC service.

Press: **Log**

Home page

Wait: the inverters start by themselves. After about 90 s the UPS transfers from bypass to inverter (§5.1.1 step 6). RADIANT 15–90 kVA: about one minute; CIRRO 60–1,600 kVA: if they do not start, use Control → Function → ON/OFF Control.

Press: **Energy flow**

**You should see** Status indicator steady green (Table 4-1, p. 34); the energy flow runs from the main input through rectifier and inverter to the output.

Home page

Close the external battery breaker: the UPS starts charging the batteries (§5.1.1 step 7). Then open Cabinet.

Press: **Cabinet**

Home page

Battery tab.

Press: **Battery**

Cabinet — Bypass

Check that the battery is connected and charging. Then close the external main output breaker, and the branch breakers one by one (§5.1.1 step 8). CIRRO 60–1,600 kVA: measure 480 V ± 2 V, 60 Hz ± 0.1 Hz first; the largest load first.

Press: **Battery number and status**

**Why** Every event of the start-up is in the Log (§5.1.1 note).

Cabinet — Battery

#### Shut the UPS down Loads off first, then EPO or the breakers. §5.2 (p. 56), §5.5 (p. 59) · 4 steps

Shut down or transfer the loads first.

**Caution** Shutting the UPS down switches off everything it feeds.

Home page

In an emergency, a long press on EPO on the front panel cuts the load power: rectifier, inverter, static bypass and battery stop (Table 4-3 p. 35, §5.5 p. 59). To stop only the inverters and keep the load on the bypass, use Control → Function → ON/OFF Control instead.

Press: **Control**

Home page

ON/OFF Control is the way to stop only the inverters (the display asks for confirmation; this button is not in the manuals).

Press: **ON/OFF Control**

Control — Function

Open the external battery breaker, then the main input breaker and the bypass input breaker (internal or external) one by one. The display goes off completely (§5.2, p. 56).

**Why** If the UPS was on maintenance bypass, open the maintenance bypass breaker too (§5.2 note).

Control — Function

**28 more RADIANT · CIRRO procedures**, settings, commissioning, parallel systems and service, with the full display simulator, are in the [AEC partner portal](https://www.aecups.com/us/partners/#tools).

## Alarms and buzzer

| What you see | Buzzer | Meaning and what to do |
| --- | --- | --- |
| **Status indicator steady green** | Silent | Normal operation (Table 4-1, p. 34). |
| **General alarm (for example an AC fault)** | Two short beeps and one long beep (Table 4-2, p. 34) | A warning: orange text on the home page (p. 36), yellow in the Log (p. 50). Read the Log and look the event up. RADIANT-IB and CIRRO-IB have a green / red status indicator only (Table 4-1); the yellow indicator of RADIANT 15–90 kVA and CIRRO 60–1,600 kVA: AEC product data, not in an available manual. |
| **Status indicator steady red — serious fault (for example a blown fuse or a hardware failure)** | Continuous tone (Table 4-2, p. 34) | Red text on the home page (p. 36) and in the Log (p. 50). Note the event and call AEC service; do not restart repeatedly. |
| **Lost N+X Redundant** | Alarm | No X redundant power module in the system (p. 47): check the modules in Module; replace or reinsert the failed one. |

## Troubleshooting

#### Communication Abnormal (home page)

- The display does not read the UPS. All the simulator's pictures show it: they come from a display not connected to a UPS.
- On a UPS: call AEC service.

#### Utility Abnormal

- Utility voltage or frequency outside the limits: the rectifier shuts down and the UPS runs on battery.
- Check the input voltage.

#### Bypass Volt Abnormal

- Bypass voltage or frequency outside the limits; it resets when the bypass returns to normal.
- First clear related alarms (bypass breaker open, Bypass Sequence Error, Input Neutral Lost).
- Check the bypass breaker and supply; if it recurs, AEC service can widen the bypass window (Set → Sys Set).

#### Bypass Sequence Error

- Bypass phase sequence reversed: check that the input power cables are connected correctly.

#### Byp Freq Over Track

- Bypass frequency outside the tracking limit: the inverter does not synchronize.
- Check the bypass supply. To return to the inverter, use Manual Transfer to Inverter (the output can be interrupted).

#### Battery Not Connected

- Check the battery breaker and cables.
- If the BCB status input (IP1) is not valid, the UPS reports the battery as not connected.

#### Battery Volt Low

- About 3 minutes of full-load runtime remain: shut the loads down in order.

#### Battery EOD / EOD Sys Inhibited

- The inverter stopped at end of discharge; the output stays off until the utility returns.

#### Battery Reverse

- Battery cables connected the wrong way.

#### Battery Test Fail / Battery Maintenance Fail

- Check that the UPS is normal with no alarm and the battery is above 90 % of float voltage; for Battery Maintenance Fail also that the load is above 25 % (p. 47).

#### Module On Less

- The capacity of the running modules is less than the load: reduce the load or add modules.

#### Output Over Load / Inverter Overload Tout

- Module above 100 % of its nominal rating (the CIRRO-IB manual prints 150 %, p. 46): check the load per phase (Cabinet → Load); in a parallel system, check the load balance.
- After a timeout the load moves to bypass, and back to the inverter 2 minutes after the load falls below 95 %.

#### Exceed Tx Times Lmt

- Too many transfers in one hour: the load stays on bypass. It returns within one hour, or clear the fault by hand. Check the load.

#### Output Short Circuit

- Check the loads, the output cables and terminals; then Control → Function → Fault Clear.

#### On UPS Inhibited

- Transfer to inverter blocked: module capacity too small for the load, rectifier not ready, or bypass voltage abnormal.

#### Rectifier Over Temp. / Inverter Over Temp.

- Module too hot: check the room temperature, the ventilation, the fans (and for the rectifier, the input voltage).

#### Inlet Over Temp. / Ambient Over Temp

- Keep the room within 32–104 °F (0–40 °C); air conditioning may be needed.

#### Outlet Temp Error

- Outlet temperature of a module above the limit: check the fans, the air path and the room temperature. Call AEC service.

#### Bypass Over Temp.

- Check the bypass load, the room temperature (below 104 °F / 40 °C) and the bypass fans.

#### Fan Fail / Bypass Fan Fail

- At least one fan of a module or of the bypass module failed.

#### Input Volt Detect Fail

- Input voltage of a module abnormal: check the input cables, fuses and the utility.

#### Battery Volt Detect Fail

- Battery voltage abnormal: check the batteries and battery fuses.

#### Bypass Volt Detect Fail

- Check that the bypass breaker is closed and good, and the bypass cables.

#### Input Curr Unbalance

- Input currents differ by more than 40 % of rating between phases: check the input voltage. Call AEC service.

#### Input Over Curr Tout

- Input over current for too long: the UPS moves to battery. Check whether the input voltage is low and the load high.

#### Input Neutral Lost

- Input neutral lost or not detected. A 3-pole breaker is recommended between the supply and the UPS.

#### Power Share Fail

- Output current of the modules out of balance: AEC service adjusts the module output voltage.

#### REC CAN Fail / INV IO CAN Fail / INV DATA CAN Fail / Sync Pulse Fail

- Communication between modules abnormal: check the communication cables.

#### Bypass CAN Fail

- Bus between the bypass module and the frame abnormal: check the connector and signal cable.

#### Parallel Cable Error

- Parallel cable missing, loose or not in a ring: check the parallel cables.

#### INV IGBT Driver Block

- Inverter IGBTs stopped: check that the power modules are fully inserted. Call AEC service.

#### Module ID Duplicate

- Two modules have the same ID: call AEC service to set the IDs in sequence.

#### Rectifier Fail / Inverter Fail / INV Bridge Fail / Bypass Module Fail / REC Soft Start Fail

- Hardware fault: call AEC service.

#### Firmware Error / System Setting Error

- Reserved to AEC service: call AEC service.

#### Fan / Capacitor / Battery / Bypass Fan Expired

- The service life is reached: replace the part, then reset its timer (Control → Function: Bypass Fan Time Reset, Clear Battery History Data).

#### Dust Filter Expired

- Clean or replace the dust filter, then Control → Function → Reset Dust Filter.

#### UPS Locked

- Manual shutdown of power modules is not allowed.

Practice

## Follow it on the display.

Short guided tours on the real RADIANT · CIRRO display.

Home page

### Shut the UPS down

Step 1 of 4

Shut down or transfer the loads first.

Shutting the UPS down switches off everything it feeds.