---
title: "UPS efficiency curves and silicon carbide (SiC) | AEC"
url: https://www.aecups.com/us/technology/efficiency/
description: "UPS efficiency explained: the 2026 catalog's efficiency curve for each AEC series, SiC and 3-level IGBT, and the energy a better UPS saves at your load."
language: en-US
---

Technology · efficiency

# Efficiency and silicon carbide

Efficiency is the share of the input power that reaches the load; the rest is heat. AEC series reach 92.6 % to 97.5 % at their best point, by the 2026 catalog; the chart below shows how each behaves from light load to full load.

Reviewed by **[Bruno Grosso](https://www.aecups.com/us/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/us/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

Efficiency curves

## Every series, at your load.

Pick a series and a size, then drag along the curve: the 2026 catalog's curves, with the heat they make and what it costs in a year.

**—** %

**Load**: —

**Lost as heat**: —

**Heat to remove**: —

**Energy lost in a year, 24/7**: —

**Its cost in a year at per kWh**: —

#### The catalog's figures as a table: efficiency at 25, 50, 75 and 100 % load

**Normal (double-conversion) mode, read off each series' efficiency curve in the AEC 2026 catalog. INFINITE 1.5MW has no published curve: its catalog gives up to 97.5% AC/AC.**

| Curve | 25 % load | 50 % load | 75 % load | 100 % load | Peak |
| --- | --- | --- | --- | --- | --- |
| [LUMINA 1.5 to 3 kVA](https://www.aecups.com/us/products/lumina/) | 89.1 % | 92.1 % | 92.6 % | 92.4 % | 92.6 % at 75 % |
| [FERRUS](https://www.aecups.com/us/products/ferrus/) | 89.3 % | 92.5 % | 93.0 % | 92.8 % | 93.0 % at 75 % |
| [FERRUS RT](https://www.aecups.com/us/products/ferrus-rt/) | 89.2 % | 92.5 % | 93.0 % | 92.8 % | 93.0 % at 75 % |
| [FERRUS SP](https://www.aecups.com/us/products/ferrus-sp/) | 90.8 % | 92.8 % | 93.0 % | 92.8 % | 93.0 % at 72 % |
| [ETHERNO](https://www.aecups.com/us/products/etherno/) | 92.5 % | 93.9 % | 94.0 % | 93.8 % | 94.0 % at 68 % |
| [AUREON](https://www.aecups.com/us/products/aureon/) | 92.5 % | 93.9 % | 94.0 % | 93.8 % | 94.0 % at 68 % |
| [RADIANT](https://www.aecups.com/us/products/radiant/) | 92.8 % | 93.9 % | 94.0 % | 93.8 % | 94.0 % at 65 % |
| [RADIANT-IB](https://www.aecups.com/us/products/radiant-ib/) | 92.7 % | 93.9 % | 94.0 % | 93.8 % | 94.0 % at 65 % |
| [CIRRO-IB](https://www.aecups.com/us/products/cirro-ib/) | 95.0 % | 95.9 % | 96.0 % | 95.8 % | 96.0 % at 65 % |
| [CIRRO 360](https://www.aecups.com/us/products/cirro/) | 95.1 % | 95.9 % | 96.0 % | 95.8 % | 96.0 % at 65 % |
| [CIRRO 600-1600](https://www.aecups.com/us/products/cirro/) | 96.2 % | 96.9 % | 97.0 % | 96.8 % | 97.0 % at 65 % |
| [INFINITE](https://www.aecups.com/us/products/infinite/) | 96.9 % | 97.3 % | 97.3 % | 97.3 % | 97.3 % at 60 % |

## Where do the losses come from?

A UPS loses power in three ways. Some losses are fixed: control boards, fans and the magnetic cores of the chokes, there as soon as the UPS is on. Some grow with the current, as the semiconductors switch. Some grow with the square of the current, in every conductor and winding. At light load the fixed part dominates and the efficiency falls; near full load the square term bends the curve down again. That is the shape of every curve in the chart, which the catalog draws with this three-term model.

## Why do the 25 and 50 % points matter more than the peak?

Redundant systems rarely run near full load. In a 2N design each UPS carries at most half the load; in an N+1 frame the spare module shares the load too, so every module runs below its rating. Compare UPS where yours will run: on the catalog curves INFINITE goes from 96.9 % at 25 % load to 97.3 % at 50 %, ETHERNO from 92.5 % to 93.9 %. Modular frames can also put modules to sleep at part load, so the others run nearer their best point ([modular UPS](https://www.aecups.com/us/technology/modular-ups/)).

Your load

## What a point of efficiency is worth.

Peak efficiency by series and the energy saved in a year of continuous running at your load.

## What do the losses cost in cooling?

Every kilowatt the UPS loses is heat the room's cooling must remove: 1 kW is 3,412 BTU/h. At a steady 100 kW, going from 96 % to 97 % cuts the loss by about 1.07 kW: about 3,660 BTU/h less heat, and about 9,400 kWh a year less at the meter before the cooling's own consumption is counted. [UPS heat output](https://www.aecups.com/us/blog/ups-heat-output-btu/) turns efficiency into BTU/h for every AEC model.

## What does "up to" mean on a datasheet?

A series' efficiency figure is the peak of its curve: in double-conversion mode, at one load point, at nominal voltage, with the battery charged. ECO-mode figures are higher because the inverter is out of the power path, so they compare only with other ECO figures. A transformer in the UPS or after it adds its own losses ([isolation transformers](https://www.aecups.com/us/technology/isolation-transformer-ups/)), and the system's efficiency is the product of the two.

## What happens on the input side?

Efficiency is the output half of the story; the input decides what the building must supply. The active rectifiers of current AEC designs draw a near-sinusoidal current: input power factor above 0.99 and current THD of 3 % or less ([INFINITE 1.5MW](https://www.aecups.com/us/products/infinite-1-5mw/) catalog page; [RADIANT-IB user manual](https://www.aecups.com/us/support/guides/radiant-ib-manual/)). Less reactive and harmonic current means smaller feeders and breakers, a generator that needs no oversizing for distortion, and an easier time with IEEE 519, whose limits apply to the whole facility at the point where it connects to the utility, not to one device.

## What should a specification ask for?

- Efficiency at 25, 50, 75 and 100 % load, in double-conversion mode, at your voltage, for the size you buy, as the table above gives it.
- Input power factor and current THD at the same load points.
- The heat in BTU/h at your load, for the cooling design.
- No oversizing for comfort: a UPS at 20 % load runs on the steep end of its curve.

Semiconductors

## SiC and 3-level IGBT

**Silicon carbide (SiC)** switches faster and with lower losses than silicon: INFINITE uses it in its 100 kVA modules and reaches 97.3%.

**3-level IGBT** inverters split each switching step in two, lowering losses and harmonic content: FERRUS, ETHERNO, AUREON, RADIANT and CIRRO use them, by their catalog lines.

**Unity power factor** (kVA = kW) on most series means the full rating is usable by modern IT loads.

**LUMINA performance**LUMINA's performance radar from its catalog.

**LUMINA safety**LUMINA's safety radar from its catalog.

**Three-stage charge**How ETHERNO charges its lithium modules.

[Technology **Online double conversion** How an AEC UPS keeps the load on: rectifier, DC bus, inverter, static and maintenance bypass, and the six operating modes on the real display.](https://www.aecups.com/us/technology/online-double-conversion/) [Technology **Lithium LiFePO4 and BMS** Lithium iron phosphate modules, the battery management system, the L6 cabinet opened up, and state of health against lead-acid.](https://www.aecups.com/us/technology/lithium-lifepo4/) [Technology **Modular UPS and N+X** Power modules in a frame, hot-swap, redundancy and parallel systems, from 15 kVA modules to 1.6 MW.](https://www.aecups.com/us/technology/modular-ups/) [Technology **Monitoring and communication** Network cards, Modbus, dry contacts, the monitoring cloud and the touchscreens, series by series.](https://www.aecups.com/us/technology/monitoring/) [Technology **Isolation transformers** Galvanic isolation, a new neutral, voltage change: what a transformer does in a UPS and when one is needed.](https://www.aecups.com/us/technology/isolation-transformer-ups/) [Technology **From thyristor to silicon carbide** Seventy years of the UPS power switch: SCR, BJT, MOSFET, IGBT, 3-level IGBT and SiC, era by era, with what AEC uses today.](https://www.aecups.com/us/technology/power-electronics-history/)

## Talk to an engineer

Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.

[Send your project](https://www.aecups.com/us/contacts/#form) [+1 786 553 2100](tel:+17865532100)
