Technology · monitoring

# UPS monitoring: display, SNMP, Modbus and cloud

Every AEC UPS can tell people and machines how it is: on its own display, over a network card, to a building management system by Modbus or dry contacts, and to the AEC monitoring cloud.

Reviewed by **[Bruno Grosso](https://www.aecups.com/us/about/#bruno-grosso)** and **[Eng. CP Cheng](https://www.aecups.com/us/about/#cp-cheng)**, with an associate project engineer, AEC Engineering

Series by series

## Ports and network card.

The standard ports and the SNMP card that fits, from the 2026 catalog.

| Series | Standard communication | Network card | Display |
| --- | --- | --- | --- |
| [**LUMINA**](https://www.aecups.com/us/products/lumina/) | RS-232, EPO and USB, standard | SNMP-L | rotating color LCD |
| [**FERRUS**](https://www.aecups.com/us/products/ferrus/) | RS-232, EPO and USB, standard | SNMP-M | color LCD |
| [**FERRUS RT**](https://www.aecups.com/us/products/ferrus-rt/) | RS-232, EPO and USB, standard | SNMP-M | color LCD |
| [**FERRUS SP**](https://www.aecups.com/us/products/ferrus-sp/) | RS-232, EPO and USB, standard | SNMP-M | — |
| [**FERRUS SP RT**](https://www.aecups.com/us/products/ferrus-sp-rt/) | RS232, EPO, USB standard | SNMP-M | — |
| [**ETHERNO**](https://www.aecups.com/us/products/etherno/) | Modbus and dry contacts, standard | SNMP-L | 4.3-inch color touchscreen |
| [**AUREON**](https://www.aecups.com/us/products/aureon/) | Modbus and dry contact standard | SNMP-L | — |
| [**RADIANT**](https://www.aecups.com/us/products/radiant/) | RS-232, EPO and USB, standard | SNMP-M | 7-inch color touchscreen |
| [**RADIANT-IB**](https://www.aecups.com/us/products/radiant-ib/) | RS-232, EPO and USB, standard | SNMP-M | 7-inch color touchscreen |
| [**CIRRO-IB**](https://www.aecups.com/us/products/cirro-ib/) | RS-232, EPO and USB, standard | SNMP-M | 7-inch color touchscreen |
| [**CIRRO**](https://www.aecups.com/us/products/cirro/) | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start | SNMP-M | personalized AEC red color touchscreen |
| [**INFINITE**](https://www.aecups.com/us/products/infinite/) | RS232, RS485/Modbus, EPO and dry contacts standard; SNMP card optional | SNMP-L | 7-inch color touchscreen |
| [**INFINITE 1.5MW**](https://www.aecups.com/us/products/infinite-1-5mw/) | RS232, RS485/Modbus RTU, Modbus TCP/IP, BACnet, BMS, EPO and dry contacts standard; SNMP card optional | SNMP-L | 7-inch color touchscreen + LED display |

## Which interface for which job?

| Who reads the UPS | Interface | What it carries |
| --- | --- | --- |
| IT: the network management system, email, servers | Network card ([SNMP card](https://www.aecups.com/us/products/accessories/snmp-card/)) | Every measurement and alarm, SNMP traps, email, server shutdown |
| Facilities: the building management system | Modbus RTU on RS-485, or Modbus TCP through the card; BACnet as standard on INFINITE 1.5MW | Registers the BMS polls: mode, voltages, load, battery, alarms |
| An alarm panel, a PLC, the generator controls | [Dry contacts](https://www.aecups.com/us/products/accessories/dry-contact-card/) | A few on/off states, no protocol and no network |
| One computer, or the service engineer | USB or RS-232 | One UPS to one PC: a single server's shutdown, or service software such as UPS View |

Most sites use more than one: dry contacts or Modbus to the building system, the network card to IT, and the display for the people in the room.

## What should the monitoring system watch?

The UPS's mode first: normal, on battery or on bypass, since on bypass the load has no protection. Then the load in percent, input and output voltages, battery capacity and estimated runtime, temperatures and alarms. By default the [RADIANT-IB user manual](https://www.aecups.com/us/support/guides/radiant-ib-manual/) sets its alarm relays to battery low (about 3 minutes left at full load), general alarm and utility failure, and the panel raises an alarm when N+X redundancy is lost. An optional battery temperature sensor drives the charger's temperature compensation; an ambient sensor tells you about the room.

[**SNMP-L network card** For LUMINA, ETHERNO, AUREON and INFINITE: web pages over HTTP or HTTPS, SNMP v1, v2c and v3 with the RFC 1628 UPS MIB, and Modbus TCP/IP; email alarms and AEC's shutdown program for Windows servers.](https://www.aecups.com/us/products/accessories/snmp-card/) [**SNMP-M network card** For FERRUS, FERRUS RT, FERRUS SP, FERRUS SP RT, RADIANT, RADIANT-IB, CIRRO-IB and CIRRO: web pages, SNMP v1, v2c and v3 to up to ten managers, Modbus TCP/IP and MQTT; traps and email to up to 20 addresses.](https://www.aecups.com/us/products/accessories/snmp-card/) [**Dry contact relay card** Potential-free relays in the intelligent slot for mains failure, battery low, UPS fault and bypass, read by a building system, a PLC or an alarm panel. It fits every AEC series.](https://www.aecups.com/us/products/accessories/dry-contact-card/) [**UPS Monitoring Cloud** Every UPS with a network card, on one web page, with alarms by email. Open](https://www.aecups.com/us/cloud/)

## How does the UPS shut servers down in time?

Shutdown software on each server listens to the network card (AEC's shutdown program, with SNMP-L) and closes the server in order before the battery runs out. Set the trigger on time, not on a share of the battery: the minutes the servers need to close, plus a margin, against the runtime the UPS reports. Runtime falls faster than the load rises, so a margin that is right at today's load is short after the next rack goes in. With a generator the battery only has to bridge its start; set the shutdown for the day the generator does not start, and try it once with the real load.

## Remote EPO and NEC Article 645

Where an IT room is built under NEC Article 645, its disconnecting means must also disconnect a UPS installed in the room, the UPS's supply and output circuits and its battery (645.10, 645.11). That signal reaches the UPS through its remote EPO input. On RADIANT-IB the input takes a voltage-free normally-open or normally-closed contact; on the normally-closed loop the UPS stops when the loop opens, so a cut wire stops it too: route and label that cable with care. In a parallel system every frame goes on the same EPO switch.

## How do you set up the network card?

- A fixed address, or a DHCP reservation, so the monitoring system always finds the card.
- SNMPv3, with user names, authentication and encryption, on any network that carries other traffic.
- Trap receivers and email alarms set, then the UPS's battery test (20 seconds on battery on RADIANT-IB) to see the alarms arrive.
- The card in the right slot: on RADIANT-IB the SNMP-M card goes in the slot marked SNMP, the intelligent slot takes the dry-contact card.
- One monitor per port: the RADIANT-IB manual says not to run UPS View on RS-232 and the network card at the same time unless AEC confirms that the two work together on that unit.

## Mistakes to avoid with signal wiring

- **Signal cables run with power.** The manual asks for shielded, double-insulated cable, 20 to 16 AWG, no longer than 80 to 160 ft (25–50 m), run apart from the power cables.
- **The wrong relay contact.** At an alarm the NC contact opens and the NO contact closes: wire the panel to the one it expects, or an alarm reads as normal.
- **A battery the UPS cannot see.** With L6 lithium cabinets, connect the BMS link to the UPS, so the cabinet's data and alarms reach the same screens ([lithium and BMS](https://www.aecups.com/us/technology/lithium-lifepo4/)).

The touchscreens

## Try the ETHERNO, INFINITE, LUMINA and L6 screens before the UPS arrives: normal, battery and bypass mode.

[Try the displays](https://www.aecups.com/us/tools/simulators/) [Operating guides](https://www.aecups.com/us/support/guides/)

**Remote monitoring of lithium cabinets**L6 cabinet data through the UPS to the network.

**SNMP-L card**The network card for LUMINA, ETHERNO, AUREON and INFINITE.

[Technology **Online double conversion** How an AEC UPS keeps the load on: rectifier, DC bus, inverter, static and maintenance bypass, and the six operating modes on the real display.](https://www.aecups.com/us/technology/online-double-conversion/) [Technology **Lithium LiFePO4 and BMS** Lithium iron phosphate modules, the battery management system, the L6 cabinet opened up, and state of health against lead-acid.](https://www.aecups.com/us/technology/lithium-lifepo4/) [Technology **Modular UPS and N+X** Power modules in a frame, hot-swap, redundancy and parallel systems, from 15 kVA modules to 1.6 MW.](https://www.aecups.com/us/technology/modular-ups/) [Technology **Efficiency and silicon carbide** Each series' efficiency curve from the catalog, SiC and 3-level IGBT, and what a point of efficiency is worth.](https://www.aecups.com/us/technology/efficiency/) [Technology **Isolation transformers** Galvanic isolation, a new neutral, voltage change: what a transformer does in a UPS and when one is needed.](https://www.aecups.com/us/technology/isolation-transformer-ups/) [Technology **From thyristor to silicon carbide** Seventy years of the UPS power switch: SCR, BJT, MOSFET, IGBT, 3-level IGBT and SiC, era by era, with what AEC uses today.](https://www.aecups.com/us/technology/power-electronics-history/)