Battery runtime

# UPS battery runtime calculator

How long a VRLA battery bank holds your load: the block's own discharge table, the bank, the room temperature, new and at end of life. 502 datasheet tables of 13 makers' 12 V blocks, read the way the battery makers' own tools read them.

Battery block

Loading the battery data…

Constant power from the battery: the UPS load divided by the inverter efficiency, shared by every cell of the bank, read on the block's constant-power table (watts per cell to the end voltage, 77 °F) interpolated on log scales between the maker's published points. Below 77 °F, the temperature factor of [IEEE 485](https://standards.ieee.org/standard/485-2020.html) Table 1. End of life: 80 % of the capacity (aging factor 1.25, IEEE 485 and 1188). A block known only by its 15-minute rating borrows the average shape of the published high-rate curves and is marked as an estimate. A figure is for sizing, not a guarantee: the block maker's warranty and its own tool rule.

For an AEC UPS, the [sizing tool](https://www.aecups.com/us/tools/ups-sizing/) gives the runtime of every model and battery set-up.