title: "Lithium vs VRLA: battery sets over 10 or 15 years | AEC"
url: https://www.aecups.com/us/tools/lithium-vs-vrla/
description: "How many VRLA battery sets a UPS needs in 10 or 15 years at your room temperature, against AEC lithium rated 15 years. Worked table, no prices."
language: en-US
---

Battery sets · 10 or 15 years · no prices

# Lithium or VRLA: how many battery sets in 10 or 15 years?

Over 15 years at 77 °F a VRLA UPS battery needs 3 to 5 sets, 2 to 4 replacements, with the 3–5 years of service AEC's user manuals give; at 95 °F it needs 6 to 10. The 50 Ah lithium module of ETHERNO and L6 is rated for 15 years: one set. Set your own years and room below.

Your count

## Years, room temperature, battery

Type the temperature in °F or °C; a decimal comma is read too. The answer and its working update as you change a value, and the address keeps them for a shared link.

15 years

= 35 °C

VRLA block

VRLA, 3 to 5 years of service (AEC user manuals)

**VRLA at 95 °F (35 °C): 1.5–2.5 years.** The service life at 77 °F is 3–5 years; above 77 °F it halves for about every 18 °F (10 °C), so 50% of it is left.

**Over 15 years: 6–10 sets of VRLA blocks, 5–9 replacements.** Sets = years ÷ life, rounded up: 15 ÷ 2.5 = 6 · 15 ÷ 1.5 = 10.

**50 Ah lithium module (ETHERNO and L6): 1 set over 15 years, 0 replacements.** From: 15 years and 5,000+ cycles, 2026 catalog (the same module in ETHERNO and the L6 cabinet, certified to UL 1973). The catalog gives no change of the lithium life with temperature.

Each VRLA replacement is a site visit, a string out of service while the blocks are changed, and a full set of lead-acid blocks to recycle.

Worked out

## 10 and 15 years at 77 °F and 95 °F

The same rule as the calculator, for the cases asked most. A range of years gives a range of sets: the long life the fewest, the short life the most.

VRLA, 3 to 5 years of service (AEC user manuals)

**Battery sets over 10 and 15 years, VRLA against lithium**

| Years · Battery room | VRLA life | VRLA sets | VRLA replacements | 50 Ah lithium module (ETHERNO and L6) | LUMINA |
| --- | --- | --- | --- | --- | --- |
| 10 years, 77 °F (25 °C) | 3–5 years | **2–4** | 1–3 | 1 | 1 |
| 10 years, 95 °F (35 °C) | 1.5–2.5 years | **4–7** | 3–6 | 1 | 1 |
| 15 years, 77 °F (25 °C) | 3–5 years | **3–5** | 2–4 | 1 | 1–2 |
| 15 years, 95 °F (35 °C) | 1.5–2.5 years | **6–10** | 5–9 | 1 | 1–2 |

Each replacement

## What a VRLA replacement means on site

A visit by a technician. The string out of service while its blocks are changed: until the new blocks are in, that string gives the UPS no backup. A full set of lead-acid blocks to send for recycling. Lithium modules in ETHERNO and L6 are changed one at a time with the UPS running.

Same UPS, same supply

## Weight and floor, two 10 kVA towers

**ETHERNO and AUREON 10 kVA at 208 V, catalog figures**

| Model | Battery inside | Runtime at half / 80% / full load | Weight | Width × depth |
| --- | --- | --- | --- | --- |
| [ETH10-2X50A-LI](https://www.aecups.com/us/products/etherno/eth10/#eth10-2x50a-li) | 2 × 50 Ah lithium modules | 55 / 34 / 27 min | 379.2 lb (172 kg) | 12.6 × 39.1 in |
| [AUR10-80X9A](https://www.aecups.com/us/products/aureon/aur-10/#aur10-80x9a) | 80 × 12 V 9 Ah VRLA blocks | 60 / 28 / 20 min | 699 lb (317.1 kg) | 14.9 × 39.1 in |

At half load the AUR10-80X9A runs longer, 60 min against 55; at 80% load the ETH10-2X50A-LI runs longer, 34 min against 28; at full load the ETH10-2X50A-LI runs longer, 27 min against 20.

For INFINITE at 480 V, [INFINITE with L6 cabinets](https://www.aecups.com/us/products/infinite-l6-lithium/#vs-lead-acid) sets each L6 set beside the lead-acid bank the catalog lists for the same minutes.

Method and sources

## How the count is made, and its limits

VRLA: the 3 to 5 years of typical service AEC's user manuals give at 77 °F (25 °C), the 5-year design life being the upper end, halved for about every 18 °F (10 °C) above 77 °F, the rule the same manuals state. Below 77 °F the page keeps the 77 °F life. Lithium: the life the 2026 catalog gives each product, 15 years for the 50 Ah module, 12 to 15 years and 3,000 cycles for LUMINA; the catalog gives no change with temperature, so none is applied. Sets are the years over the life, rounded up.

It is a rule of thumb, not a guarantee: real life depends on the number and depth of discharges, the charging, the maintenance and the room. A battery bank also loses runtime as it ages; [battery runtime](https://www.aecups.com/us/tools/battery-runtime/) gives the minutes of a VRLA string new and at end of life.

More: [lithium-ion or VRLA for a UPS](https://www.aecups.com/us/blog/ups-power-supply-lithium-batteries/) · [how long UPS batteries last](https://www.aecups.com/us/blog/ups-battery-life/) · [every AEC lithium UPS](https://www.aecups.com/us/products/lithium-ups/) · [VRLA batteries](https://www.aecups.com/us/products/batteries/)

Lithium or VRLA

## Questions people ask

#### How many times is a VRLA battery replaced in 15 years?

At 77 °F, with the 3 to 5 years of service AEC's user manuals give, 2 to 4 times: 3 to 5 sets. At 95 °F the life halves and the count is 6 to 10 sets.

#### Does lithium need replacing in 15 years?

The 2026 catalog rates the 50 Ah module of ETHERNO and L6 for 15 years: one set over 15 years. LUMINA is rated 12 to 15 years, so one or two sets.

#### Why does temperature matter so much for VRLA?

As a rule of thumb its life halves for about every 18 °F (10 °C) above 77 °F (25 °C), which AEC's user manuals state. A room held at 95 °F doubles the number of sets.

#### Is this count a guarantee?

No. It is a rule of thumb on rated lives. Real life also depends on how often the battery discharges, how deep, the charging and the maintenance.

#### Where are the costs?

Not on this page. Give each set its price, add each visit and the cooling of the room, and set the total beside the price of the lithium.

## Compare it on your own project

Send the load, the minutes and the room: we answer with the lithium and the VRLA set-up for it, side by side.

[Send your project](https://www.aecups.com/us/contacts/#form) [+1 786 553 2100](tel:+17865532100)