480 V · up to 1.2 MW · LiFePO4

Containerized UPS: INFINITE and L6 lithium in a 40 ft container

A containerized UPS puts the UPS, LiFePO4 lithium batteries and switchgear in one container, installed and wired before it ships, for 480 V, 60 Hz sites from 200 kW to 1.2 MW. AEC's container comes with an HMI panel, fingerprint access and CCTV, and is sized to the load and the minutes on battery the site needs.

AEC containerized UPS

Build your container

From 200 kW to 1.2 MW, 200 kW at a time.

Open it, then drag systems in or use + and −. Up to 600 kW, one to three INFINITE 200 kVA N+1, each with its own L6 lithium cabinet; from 800 kW, one INFINITE 1.5MW frame N+1 with one L6 cabinet per 200 kW on the L6 combiner. Always 15 minutes at full load. The drawing lays out the UPS, the lithium, the cooling and the switchgear for you.

Containerized UPS · 480 V · LiFePO4

1 MW for 15 minutes, in one 40-foot container.

Power, N+1 in every frame1,000 kW
Runtime at full load15 min
UPS heat at full load26 kW
Cabinets—
AEC containerized UPS, a 40-foot IP55 containerClick the container to open it

A sealed IP55 40-foot container with the UPS, the lithium cabinets, cooling, switchgear, fire protection and security inside. Open it, then add or remove systems from 200 kW to 1.2 MW.

Built in

A power plant that arrives on a truck.

The container

The container

UPS, lithium batteries and switchgear built into one transportable unit.

Cabinets in a row

Cabinets in a row

UPS and battery cabinets installed and wired before the container ships.

HMI touch panel

HMI touch panel

Every cabinet and battery string on one screen.

Fingerprint access

Fingerprint access

Entry for authorized staff only.

CCTV

CCTV

Camera surveillance of the inside.

Power cabling

Power cabling

Cable entries ready for the site connection.

Container layout drawing
Layout of the container

From the 2026 container catalog

The container in figures.

The 1 MW and 1.2 MW systems as the AEC containerized UPS catalog (2026) draws them; a project drawing sets each position.

Supply
480 V, 60 Hz, three-phase, 3 wires and ground, in and out, through a sealed, isolated cable entry
Container
40 ft (12,192 mm) long, sealed steel, IP55, on its own concrete pad
Inside at 1 MW
one row, 24 ft 11 in (7,600 mm) as drawn: four in-row A/C units, the INFINITE 1.5MW frame (N+1), the L6 combiner and five L6 lithium cabinets; at 1.2 MW a sixth L6
Runtime
15 minutes at full load; 348 kWh of lithium at 1.2 MW, 6 L6 cabinets of 58 kWh
UPS and battery weight
16,980 lb (7,702 kg) at 1 MW; 19,390 lb (8,795 kg) at 1.2 MW
Cooling
4 in-row A/C units with a cold aisle in front of the row and a hot aisle behind it; 4 outdoor units with two fans each, 7 ft 4 in × 40.8 in (2,243 × 1,037 mm) as drawn, 23.6 in (600 mm) apart
Fire and environment
fire protection, water, humidity and temperature watched in the container; a smoke detector and fire protection in every L6 cabinet, module by module; on-line insulation monitoring
Access and security
end double door and side door; fingerprint reader on a magnetic lock; CCTV inside and out, 30 days of recording on a 4 TB video server
Monitoring
7-inch touchscreen on the INFINITE 1.5MW frame, 10-inch on the L6 master; Modbus RTU, RS-232, RS-485, EPO and dry contacts (4 in, 3 out) standard; SNMP card as an option

Questions

Questions people ask

What supply does the AEC containerized UPS need?

480 V, 60 Hz three-phase, 3 wires and ground, in and out, by the AEC containerized UPS catalog (2026). The INFINITE UPS inside is 3-wire, without a neutral: loads that need 277 V line to neutral go behind a transformer.

How long does the containerized UPS run on battery?

15 minutes at full load: one L6 lithium cabinet of 58 kWh per 200 kW, 348 kWh at 1.2 MW with six cabinets.

How much does the containerized UPS weigh?

The catalog gives 16,980 lb (7,702 kg) of UPS and battery at 1 MW and 19,390 lb (8,795 kg) at 1.2 MW, in a 40 ft container. Ask AEC for the container's own weight and the pad drawing of your project.

How is the container cooled and protected?

Four in-row A/C units with four outdoor units, a cold aisle in front of the cabinets and a hot aisle behind them. Fire, water, humidity and temperature are watched, every L6 cabinet has a smoke detector and fire protection, and entry is by fingerprint, with CCTV inside and out.

Plan a containerized system

Tell us the power, the runtime and the site. We design the container around it.