Single-phase 120 V UPS
FERRUS online UPS, 1–3 kVA, 120 V
FERRUS is AEC's online double-conversion UPS for single-phase 120 V loads from 1 to 3 kVA, in a tower cabinet, with internal VRLA batteries. Its 3-level IGBT inverter runs at power factor 1.0: the 3 kVA model delivers 3,000 W. MOV surge protection is built in.

Efficiency
How efficient is the FERRUS at your load?
The FERRUS in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
What is what
Inside the FERRUS, part by part.
Each number on the picture is named in the list.
Rear · 1 kVA

- Intelligent slotFor an optional network or dry-contact card.
- External battery connectorFor BAT0424 cabinets of the same height, beside the UPS. Connect them only with the UPS off and unplugged.
- RS-232 portTo a computer, for the monitoring software.
- EPO terminalTwo pins, normally closed with a jumper fitted; open the loop to stop the output.
- NEMA 5-15R outletsThe protected outputs, 120 V, in two groups.
- Fan outletThe air enters at the front and leaves here: keep both clear.
- Input surge protectorResettable: press it to reset.
- Input: C14 inletIEC C14 inlet; the input cable comes with the UPS.
Rear · 3 kVA

- RS-232 portTo a computer, for the monitoring software.
- EPO terminalTwo pins, normally closed with a jumper fitted; open the loop to stop the output.
- Intelligent slotFor an optional network or dry-contact card.
- Fan outletThe air enters at the front and leaves here: keep both clear.
- 6 × NEMA 5-20R outletsThe protected outputs, 120 V, in two groups.
- Output protectorsResettable, one for each group of outlets.
- 1 × NEMA L5-30R outletTwist-lock, 30 A.
- Input surge protectorResettable: press it to reset.
- Input cord, NEMA L5-30PAttached cord with a locking 30 A plug.
Overview
Key facts
- Power range
- 1–3 kVA
- Input / Output
- 110/120 V, 50–60 Hz, single-phase
- Technology
- 3-level IGBT; MOV surge protection; 8 A settable charger
- Display
- color LCD
- Comms
- RS-232, EPO and USB, standard
- Battery
- internal VRLA batteries
- Power factor
- 1.0 (kVA = kW)
- Network card
- SNMP-M (SNMP)
- Warranty
- 3 years on UPS · 2 years on VRLA batteries
- Quality system
- ISO 9001:2015, the group's quality system (SGS)
Models
Which FERRUS fits your load?
3 models for the US market, from the 2026 catalog. Pick the power, open a model for its full datasheet.



External battery cabinets
Each FERRUS model above has its own internal batteries. Up to 4 external battery cabinets can be added per UPS (BAT0424, BAT0848, BAT1272, listed below). Ask us which set-up fits your load.
Options and parts for FERRUS
- BAT0424Battery Cabinet Tower 24 Vdc5.6" W × 8.6" D × 9.4" H (142 × 218 × 239 mm) · 31.4 lb (14.2 kg)
- BAT0848Battery Cabinet Tower 48 Vdc5.6" W × 8.6" D × 17.3" H (142 × 218 × 439 mm) · 58.8 lb (26.7 kg)
- BAT1272Battery Cabinet Tower 72 Vdc5.6" W × 8.6" D × 25.1" H (142 × 218 × 638 mm) · 86.2 lb (39.1 kg)
Datasheet
FERRUS datasheet.
Every model side by side. Filter by power, keep only what differs, print it or take it as CSV.
| Model | FER1000-2X9 | FER2000-4X9 | FER3000-6X9 |
|---|---|---|---|
| Power | |||
| Rated power (kVA) | 1 | 2 | 3 |
| Active power (kW) | 1 | 2 | 3 |
| Output power factor | 1.0 | 1.0 | 1.0 |
| Electrical | |||
| Input / output | 120 V single-phase | 120 V single-phase | 120 V single-phase |
| Topology | Online Double Conversion | Online Double Conversion | Online Double Conversion |
| Efficiency, up to | 93% | 93% | 93% |
| Battery DC bus | 24 V DC | 48 V DC | 72 V DC |
| Battery and runtime | |||
| Battery type | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) |
| Battery configuration | Internal | Internal | Internal |
| Runtime at 50 % load | 10 min | 10 min | 10 min |
| Runtime at 100 % load | 4.2 min | 4.2 min | 4.2 min |
| Mechanical | |||
| Form factor | Tower | Tower | Tower |
| Dimensions W × D × H | 5.6 × 8.6 × 13.9 in (142 × 218 × 353 mm) | 7.5 × 12.6 × 15.8 in (190 × 319 × 400 mm) | 7.5 × 12.6 × 15.8 in (190 × 319 × 400 mm) |
| Net weight | 16.5 lb (7.5 kg) | 36.3 lb (16.5 kg) | 45.2 lb (20.5 kg) |
| Footprint | 0.3 ft² (0.03 m²) | 0.7 ft² (0.06 m²) | 0.7 ft² (0.06 m²) |
| Shipping | |||
| Cartons | 1 | 1 | 1 |
| Shipping weight | 24.3 lb | 48.5 lb | 60.6 lb |
From the AEC 2026 catalog. Efficiency is the catalog's “up to” figure; runtimes are AEC's runtime tables with new batteries; weights are the unit alone, without batteries outside it. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The FERRUS documents in English, as PDF.
Installation
What does the FERRUS need in the room?
From the AEC US user manual of the FERRUS. Where the manual gives no distance, none is printed here: ask AEC.
- Clearances
- The manual asks for free space in front and behind, not against a wall and not in a closed cabinet, without a distance.
- Wiring
- Plug-in: cords at the rear panel.
- Cable entry
- Plug-in, at the rear
- Breakers and terminals
- Input surge protector and outputs (and the 3K's output protectors) on the rear panel.
Plan it:Size it for your loadBattery runtimeRoom fitFERRUS compared with other makersWarranty terms
Replacing another brand's UPS?Type its model number: the AEC match
FERRUS: quick answers
Questions people ask
What sizes does FERRUS come in?
1 to 3 kVA, in 3 models of the 2026 catalog for the US, from the FER1000-2X9 (1 kVA) to the FER3000-6X9 (3 kVA). The datasheet on this page gives every one.
What supply does FERRUS need?
110/120 V, 50–60 Hz, single-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.
What batteries does FERRUS use?
Internal VRLA batteries. The battery bus runs from 24 V DC to 72 V DC, by model.
What warranty does FERRUS have?
3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.
How is FERRUS monitored over the network?
With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.
What sizes does FERRUS come in?What batteries does FERRUS use?What is the output current of each FERRUS model?All 7 questions
Also in 120V single-phase UPS:LUMINAFERRUS RTCompare the range
The FERRUS for your project
Send the load, the voltage and the minutes. We reply with the FERRUS model that fits, its batteries and the lead time.