Single-phase 120 V UPS

FERRUS online UPS, 1–3 kVA, 120 V

VRLAOnline double conversionTower

FERRUS is AEC's online double-conversion UPS for single-phase 120 V loads from 1 to 3 kVA, in a tower cabinet, with internal VRLA batteries. Its 3-level IGBT inverter runs at power factor 1.0: the 3 kVA model delivers 3,000 W. MOV surge protection is built in.

1–3kVA
93%Efficiency, up to
1.0Power factor
3 yrWarranty
AEC FERRUS: Tower perspective

Efficiency

How efficient is the FERRUS at your load?

The FERRUS in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.

—%

Load
—
Lost as heat
—
Heat to remove
—
Energy lost in a year, 24/7
—
Its cost in a year at per kWh
—

What is what

Inside the FERRUS, part by part.

Each number on the picture is named in the list.

Rear · 1 kVA

AEC FERRUS 1 kVA tower, rear panel: option slot, serial and EPO ports, outlets, fan grille, surge protector and C14 inlet
  1. Intelligent slotFor an optional network or dry-contact card.
  2. External battery connectorFor BAT0424 cabinets of the same height, beside the UPS. Connect them only with the UPS off and unplugged.
  3. RS-232 portTo a computer, for the monitoring software.
  4. EPO terminalTwo pins, normally closed with a jumper fitted; open the loop to stop the output.
  5. NEMA 5-15R outletsThe protected outputs, 120 V, in two groups.
  6. Fan outletThe air enters at the front and leaves here: keep both clear.
  7. Input surge protectorResettable: press it to reset.
  8. Input: C14 inletIEC C14 inlet; the input cable comes with the UPS.

Rear · 3 kVA

AEC FERRUS 3 kVA tower, rear panel: serial and EPO ports, option slot, NEMA 5-20R and L5-30R outlets, output protectors and the input cord
  1. RS-232 portTo a computer, for the monitoring software.
  2. EPO terminalTwo pins, normally closed with a jumper fitted; open the loop to stop the output.
  3. Intelligent slotFor an optional network or dry-contact card.
  4. Fan outletThe air enters at the front and leaves here: keep both clear.
  5. 6 × NEMA 5-20R outletsThe protected outputs, 120 V, in two groups.
  6. Output protectorsResettable, one for each group of outlets.
  7. 1 × NEMA L5-30R outletTwist-lock, 30 A.
  8. Input surge protectorResettable: press it to reset.
  9. Input cord, NEMA L5-30PAttached cord with a locking 30 A plug.

Overview

Key facts

Power range
1–3 kVA
Input / Output
110/120 V, 50–60 Hz, single-phase
Technology
3-level IGBT; MOV surge protection; 8 A settable charger
Display
color LCD
Comms
RS-232, EPO and USB, standard
Battery
internal VRLA batteries
Power factor
1.0 (kVA = kW)
Network card
SNMP-M (SNMP)
Warranty
3 years on UPS · 2 years on VRLA batteries
Quality system
ISO 9001:2015, the group's quality system (SGS)

Models

Which FERRUS fits your load?

3 models for the US market, from the 2026 catalog. Pick the power, open a model for its full datasheet.

External battery cabinets

Each FERRUS model above has its own internal batteries. Up to 4 external battery cabinets can be added per UPS (BAT0424, BAT0848, BAT1272, listed below). Ask us which set-up fits your load.

Options and parts for FERRUS

  • BAT0424Battery Cabinet Tower 24 Vdc5.6" W × 8.6" D × 9.4" H (142 × 218 × 239 mm) · 31.4 lb (14.2 kg)
  • BAT0848Battery Cabinet Tower 48 Vdc5.6" W × 8.6" D × 17.3" H (142 × 218 × 439 mm) · 58.8 lb (26.7 kg)
  • BAT1272Battery Cabinet Tower 72 Vdc5.6" W × 8.6" D × 25.1" H (142 × 218 × 638 mm) · 86.2 lb (39.1 kg)

Datasheet

FERRUS datasheet.

Every model side by side. Filter by power, keep only what differs, print it or take it as CSV.

FERRUS datasheet, 3 models
ModelFER1000-2X9FER2000-4X9FER3000-6X9
Power
Rated power (kVA)123
Active power (kW)123
Output power factor1.01.01.0
Electrical
Input / output120 V single-phase120 V single-phase120 V single-phase
TopologyOnline Double ConversionOnline Double ConversionOnline Double Conversion
Efficiency, up to93%93%93%
Battery DC bus24 V DC48 V DC72 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)VRLA (sealed lead-acid)VRLA (sealed lead-acid)
Battery configurationInternalInternalInternal
Runtime at 50 % load10 min10 min10 min
Runtime at 100 % load4.2 min4.2 min4.2 min
Mechanical
Form factorTowerTowerTower
Dimensions W × D × H5.6 × 8.6 × 13.9 in (142 × 218 × 353 mm)7.5 × 12.6 × 15.8 in (190 × 319 × 400 mm)7.5 × 12.6 × 15.8 in (190 × 319 × 400 mm)
Net weight16.5 lb (7.5 kg)36.3 lb (16.5 kg)45.2 lb (20.5 kg)
Footprint0.3 ft² (0.03 m²)0.7 ft² (0.06 m²)0.7 ft² (0.06 m²)
Shipping
Cartons111
Shipping weight24.3 lb48.5 lb60.6 lb

From the AEC 2026 catalog. Efficiency is the catalog's “up to” figure; runtimes are AEC's runtime tables with new batteries; weights are the unit alone, without batteries outside it. Figures can change: the order confirmation rules.

FERRUS: quick answers

Questions people ask

What sizes does FERRUS come in?

1 to 3 kVA, in 3 models of the 2026 catalog for the US, from the FER1000-2X9 (1 kVA) to the FER3000-6X9 (3 kVA). The datasheet on this page gives every one.

What supply does FERRUS need?

110/120 V, 50–60 Hz, single-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

What batteries does FERRUS use?

Internal VRLA batteries. The battery bus runs from 24 V DC to 72 V DC, by model.

What warranty does FERRUS have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

How is FERRUS monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.