Three-phase 480 V UPS

CIRRO-IB modular UPS, 30–150 kVA, 480 V

4-wire · 3P+NVRLAModular N+XModular

CIRRO-IB is AEC's modular online UPS with N+X redundancy for three-phase 480 V, 4-wire loads from 30 to 150 kVA, with internal hot-swappable VRLA battery trays. For 30 kVA modular at 480 V, the CIRIB150-1X30 is one 30 kVA power module in the frame; at 208 V it is the RADIANT RAD90-2X15, two 15 kVA modules.

30–150kVA
96%Efficiency, up to
1.0Power factor
3 yrWarranty
AEC CIRRO-IB, rendered from its 3D modelDrag to turn

In 3D

Look around the CIRRO-IB

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

Rendered from AEC's 3D model of the CIRRO-IB 30–150 kVA. The full 3D view zooms in, opens the unit and names every part.

Hands on

Open the CIRRO-IB yourself.

Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.

AEC CIRRO-IB, closed

Every part in 3D

Efficiency

How efficient is the CIRRO-IB at your load?

The CIRRO-IB in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.

—%

Load
—
Lost as heat
—
Heat to remove
—
Energy lost in a year, 24/7
—
Its cost in a year at per kWh
—

The display

The CIRRO-IB display.

The real touchscreen, from the user manual: pick a main page, or touch the screen as on the UPS.

Home

RADIANT · CIRRO · the real screen

Home

The home page after the welcome window: status bar, output voltage gauges, battery bars, energy flow and warning information, with the main menu on the left.

The ten main pages

What is what

Inside the CIRRO-IB, part by part.

Each number is named in the list under its picture: the front with its door open and the rear, side by side.

Front, door open

AEC CIRRO-IB 150 kVA, front with the door open: power modules, bypass and monitoring module, battery trays
  1. 5 power-module slots30 kVA modules, hot-swappable; No. 1 at the bottom, No. 5 at the top.
  2. Bypass & monitoring moduleCommunication panel and fans.
  3. Battery trays, 4 per row × 6 rows = 24Ten 12 V blocks in each tray.
  4. TouchscreenOn the door, seen here from inside.
  5. Base and anchor boltsFour anchor bolts and no casters: the cabinet is moved with a pallet truck or a forklift.

Rear, doors open

AEC CIRRO-IB from the rear with both rear doors open, beside the cabinet closed from the front
  1. Module backplaneThe power modules seen from the rear, with their busbars.
  2. Battery breakerConnects the internal battery trays to the DC bus of the power modules.
  3. Output, maintenance and input breakersLeft to right: output to the load; maintenance bypass, normally OFF, around the whole UPS for service; main input to the rectifiers.
  4. Terminal coverBehind it the power terminals.
  5. Rear doorsTwo: the breakers and the power terminals are reached from the rear.
  6. Touchscreen7-inch, on the front door.

Overview

Key facts

Power range
30–150 kVA
Technology
3-level IGBT; unity power factor (kVA = kW); 40 A settable charger
Input / Output
480/277 V three-phase, 4-wire
Battery
internal hot-swappable VRLA, up to 240 × 12V 9Ah (240 pcs)
Display
7-inch color touchscreen
Comms
RS-232, EPO and USB, standard
Power factor
1.0 (kVA = kW)
Network card
SNMP-M (SNMP)
Warranty
3 years on UPS · 2 years on VRLA batteries
Quality system
ISO 9001:2015, the group's quality system (SGS)

Models

Which CIRRO-IB fits your load?

5 models for the US market, from the 2026 catalog. Pick the power, open a model for its full datasheet.

Options and parts for CIRRO-IB

  • CIRIB-BATTR-10x9ABattery Tray incl. 10 × 12 V 9 Ah
  • CIRIB-BATTR-EMPTYBattery Tray empty
  • CIRIB-FRAMECIRRO-IB 150 kVA Frame — no power module, no battery trays, 5 module slots23.6" W × 39.4" D × 78.7" H (600 × 1,000 × 2,000 mm) · 616 lb (279.4 kg)
  • CIRIB-PWR-30Power Module 30 kVA — CIRRO-IB17.3" W × 26.7" D × 3.4" H (440 × 678 × 85 mm) · 52 lb (23.6 kg)

Datasheet

CIRRO-IB datasheet.

Every model side by side. Filter by power, keep only what differs, print it or take it as CSV.

CIRRO-IB datasheet, 5 models
ModelCIRIB150-1X30CIRIB150-2X30CIRIB150-3X30CIRIB150-4X30CIRIB150-5X30
Power
Rated power (kVA)306090120150
Active power (kW)306090120150
Output power factor1.01.01.01.01.0
Electrical
Input / output480 V three-phase, 4-wire (3P+N)480 V three-phase, 4-wire (3P+N)480 V three-phase, 4-wire (3P+N)480 V three-phase, 4-wire (3P+N)480 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+XOnline double conversion, modular N+XOnline double conversion, modular N+XOnline double conversion, modular N+XOnline double conversion, modular N+X
Efficiency, up to96%96%96%96%96%
Battery DC bus480 V DC480 V DC480 V DC480 V DC480 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)VRLA (sealed lead-acid)VRLA (sealed lead-acid)VRLA (sealed lead-acid)VRLA (sealed lead-acid)
Battery configurationInternal Tray SystemInternal Tray SystemInternal Tray SystemInternal Tray SystemInternal Tray System
Runtime at 50 % load45 min14 min10.5 min6 min6 min
Runtime at 100 % load14 min6 min3 min2 min—
Mechanical
Form factorModularModularModularModularModular
Dimensions W × D × H23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)
Net weight2,191.8 lb (994.2 kg)2,243.8 lb (1,017.8 kg)2,295.8 lb (1,041.4 kg)2,347.8 lb (1,065 kg)2,399.8 lb (1,088.6 kg)
Footprint6.4 ft² (0.60 m²)6.4 ft² (0.60 m²)6.4 ft² (0.60 m²)6.4 ft² (0.60 m²)6.4 ft² (0.60 m²)
Shipping
Cartons2627282930

From the AEC 2026 catalog. Efficiency is the catalog's “up to” figure; runtimes are AEC's runtime tables with new batteries; weights are the unit alone, without batteries outside it. Figures can change: the order confirmation rules.

CIRRO-IB: quick answers

Questions people ask

What sizes does CIRRO-IB come in?

30 to 150 kVA, in 5 models of the 2026 catalog for the US, from the CIRIB150-1X30 (30 kVA) to the CIRIB150-5X30 (150 kVA). The datasheet on this page gives every one.

What supply does CIRRO-IB need?

480/277 V three-phase, 4-wire, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

What batteries does CIRRO-IB use?

Internal hot-swappable VRLA, up to 240 × 12 V 9 Ah blocks. The battery bus is 480 V DC on every model.

What warranty does CIRRO-IB have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

How is CIRRO-IB monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

The CIRRO-IB for your project

Send the load, the voltage and the minutes. We reply with the CIRRO-IB model that fits, its batteries and the lead time.