208 V and 480 V · 10 kVA to 1.6 MW
Three-phase UPS systems for 208 V and 480 V
A three-phase (3-phase) UPS keeps three-phase loads running when the utility fails. AEC offers eight online double-conversion series for US supplies: towers and modular frames from 10 to 100 kVA at 208 V, and modular systems from 30 to 1,600 kVA at 480 V, 4-wire or 3-wire, with lithium or VRLA batteries. Choose the supply first, then the power.
Side by side
Every AEC three-phase UPS.
From the 2026 catalog. Click a series for its models, runtimes and drawings.
| Series | Supply | Power | Type | Battery | Efficiency |
|---|---|---|---|---|---|
| ETHERNO | 208 V | 10–30 kVA | Tower | Lithium LiFePO4 | up to 94% |
| AUREON | 208 V | 10–30 kVA | Tower | VRLA | up to 94% |
| RADIANT | 208 V | 15–90 kVA | Modular, N+X | VRLA | up to 94% |
| RADIANT-IB | 208 V | 20–100 kVA | Modular, N+X | VRLA | up to 94% |
| CIRRO-IB | 480 V, 4-wire | 30–150 kVA | Modular, N+X | VRLA | up to 96% |
| CIRRO | 480 V, 4-wire | 60–1,600 kVA | Modular, N+X | VRLA | up to 97% |
| INFINITE | 480 V, 3-wire | 100–600 kVA | Modular, N+1 | Lithium LiFePO4 or VRLA | up to 97.3% |
| INFINITE 1.5MW | 480 V, 3-wire | 750–1,500 kVA | Modular, N+1 | Lithium LiFePO4 or VRLA | up to 97.5% |
The supply decides
208 V, 480 V 4-wire or 480 V 3-wire.
208Y/120 V is the three-phase supply of most US commercial buildings and server rooms: ETHERNO, AUREON, RADIANT and RADIANT-IB, 10 to 100 kVA.
480Y/277 V, 4-wire carries the neutral: CIRRO-IB and CIRRO, 30 to 1,600 kVA.
480 V, 3-wire (delta, no neutral) is common in industry: INFINITE, 100 to 600 kVA, and INFINITE 1.5MW, 750 to 1,500 kVA, with silicon carbide modules.
More: 208 V or 480 V UPS · when a transformer is needed · modular UPS and N+X
Current per phase
How many amps at each size?
| UPS | at 208 V | at 480 V |
|---|---|---|
| 10 kVA | 28 A | 12 A |
| 30 kVA | 83 A | 36 A |
| 60 kVA | 167 A | 72 A |
| 100 kVA | 278 A | 120 A |
| 300 kVA | 833 A | 361 A |
| 600 kVA | 1,665 A | 722 A |
kVA × 1,000 ÷ (√3 × V), at full load. The breakers and cables follow the UPS's own input current: see UPS amps from kVA.
Questions
Questions people ask
What is a three-phase UPS?
A UPS that takes and delivers three-phase power: three lines 120 degrees apart, at 208 V or 480 V in the United States. It carries larger loads than a single-phase UPS with less current per conductor, which is why server rooms, data centers, hospitals and factories use it.
Single-phase or three-phase UPS?
Single-phase for loads up to about 20 kVA on 120 V or 120/240 V circuits; three-phase when the panel is three-phase or the load is larger. AEC three-phase UPS start at 10 kVA.
208 V or 480 V?
208 V (208Y/120 V) suits server rooms and buildings that distribute at 208 V; 480 V suits large loads and data centers, with less than half the current for the same power. The UPS follows the panel it is connected to.
What is the difference between 480 V 3-wire and 4-wire?
A 4-wire supply carries the neutral, a 3-wire (delta) supply does not. CIRRO is built for 480 V 4-wire, INFINITE for 480 V 3-wire: pick the UPS by the supply on site.
How many amps does a three-phase UPS draw?
Current per phase = kVA × 1,000 ÷ (√3 × voltage): a 30 kVA UPS carries about 83 A per phase at 208 V and 36 A at 480 V, at full load and unity power factor.
Modular or tower?
A tower UPS is one unit of fixed size; a modular UPS holds power modules in a frame, so it grows by adding modules and stays on line when one is swapped (N+1). AEC offers both.
Which three-phase UPS?
Send the supply, the load in kW and the minutes you need: we answer with the series, the model and the batteries.