Three-phase 208 V UPS
RADIANT modular UPS, 15–90 kVA, 208 V
RADIANT is AEC's modular online UPS with N+X redundancy for three-phase 208 V loads from 15 to 90 kVA, with an external VRLA battery bank. Power modules of 15 kVA go into one frame, up to six, and the VRLA bank is external, sized to the minutes the load needs.
Drag to turnIn 3D
Look around the RADIANT
Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.
Rendered from AEC's 3D model of the RADIANT 15–90 kVA. The full 3D view zooms in, opens the unit and names every part.
Hands on
Open the RADIANT yourself.
Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.
Efficiency
How efficient is the RADIANT at your load?
The RADIANT in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
The display
The RADIANT display.
The real touchscreen, from the user manual: pick a main page, or touch the screen as on the UPS.

RADIANT · CIRRO · the real screen
Home
The home page after the welcome window: status bar, output voltage gauges, battery bars, energy flow and warning information, with the main menu on the left.
What is what
Inside the RADIANT, part by part.
Each number is named in the list under its picture: the front with its door open and the rear, side by side.
Front, door open

- Bypass input breakerFeeds the static bypass in the bypass module from the bypass input terminals.
- Maintenance bypass breakerConnects the bypass input straight to the output, around the whole UPS, for service. Normally OFF.
- Main input breakerFeeds the rectifiers of the power modules from the main input terminals.
- Output breakerConnects the inverters and the static bypass to the output terminals and the load.
- Back of the touchscreenOn the inside of the upper door.
- Lower door, perforatedAir in; behind it the bypass module and the six module slots.
Rear

- Terminal boxThe power terminals, behind the rear protective cover; cables enter from the top.
- Rear grilleAir out: front to back cooling.
- Casters (4)Lock them once the frame is in place.
Overview
Key facts
- Power range
- 15–90 kVA
- Technology
- 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger
- Input / Output
- 208/120 V three-phase
- Battery
- external VRLA (battery bank sized separately)
- Display
- 7-inch color touchscreen
- Comms
- RS-232, EPO and USB, standard
- Power factor
- 1.0 (kVA = kW)
- Network card
- SNMP-M (SNMP)
- Warranty
- 3 years on UPS · 2 years on VRLA batteries
- Quality system
- ISO 9001:2015, the group's quality system (SGS)
Models
Which RADIANT fits your load?
6 models for the US market, from the 2026 catalog. Pick the power, open a model for its full datasheet.






Options and parts for RADIANT
- RAD-PWR-15Power Module 15 kVA — RADIANT15.8" W × 19.5" D × 3.4" H (400 × 495 × 86 mm) · 30.5 lb (13.9 kg)
- RAD90-FRAMERADIANT 90 kVA Frame — no power module, 6 module slots incl. 4 breakers17.4" W × 33.1" D × 59.4" H (442 × 840 × 1,510 mm) · 207.5 lb (94.1 kg)
Datasheet
RADIANT datasheet.
Every model side by side. Filter by power, keep only what differs, print it or take it as CSV.
| Model | RAD90-1X15 | RAD90-2X15 | RAD90-3X15 | RAD90-4X15 | RAD90-5X15 | RAD90-6X15 |
|---|---|---|---|---|---|---|
| Power | ||||||
| Rated power (kVA) | 15 | 30 | 45 | 60 | 75 | 90 |
| Active power (kW) | 15 | 30 | 45 | 60 | 75 | 90 |
| Output power factor | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
| Electrical | ||||||
| Input / output | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X |
| Efficiency, up to | 94% | 94% | 94% | 94% | 94% | 94% |
| Battery DC bus | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC |
| Battery and runtime | ||||||
| Battery type | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank | External battery bank | External battery bank | External battery bank | External battery bank | External battery bank |
| Mechanical | ||||||
| Form factor | Modular Rack 19" | Modular Rack 19" | Modular Rack 19" | Modular Rack 19" | Modular Rack 19" | Modular Rack 19" |
| Dimensions W × D × H | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) |
| Net weight | 238 lb (108 kg) | 268.5 lb (121.8 kg) | 299 lb (135.7 kg) | 329.5 lb (149.5 kg) | 360 lb (163.4 kg) | 390.5 lb (177.2 kg) |
| Footprint | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) |
From the AEC 2026 catalog. Efficiency is the catalog's “up to” figure; weights are the unit alone, without batteries outside it. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The RADIANT documents in English, as PDF.
Catalogs and datasheets
Installation
What does the RADIANT need in the room?
From the AEC US user manual of the RADIANT. Where the manual gives no distance, none is printed here: ask AEC.
- Clearances
- Front: 36 in (914 mm) working space, doors fully open. Rear, sides and top: AEC has not published a distance (keep the rear reachable for the terminals and the top free for air).
- Wiring
- Hardwired: an electrician connects it to the panel.
- Cable entry
- Top of the rear terminal box; Bottom, into the rear terminal box (On a raised floor, a pedestal made for the frame's point load)
- Breakers and terminals
- The four breakers (input, bypass, output, maintenance) are on the breaker panel behind the upper front door; the power terminals at the top of the rear.
- Door
- Upper door hinged on the right seen from the front (from the photo); the lower door lifts off.
- Space to pull a module
- Keep at least 19.5 in (495 mm) free in front to slide a module out.
Install and run it:RADIANT installation and operation manualRADIANT and CIRRO touch screen guide
Plan it:Size it for your loadRoom fitRADIANT compared with other makersWarranty terms
Replacing another brand's UPS?Type its model number: the AEC match
RADIANT: quick answers
Questions people ask
What sizes does RADIANT come in?
15 to 90 kVA, in 6 models of the 2026 catalog for the US, from the RAD90-1X15 (15 kVA) to the RAD90-6X15 (90 kVA). The datasheet on this page gives every one.
What supply does RADIANT need?
208/120 V three-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.
What batteries does RADIANT use?
External VRLA (battery bank sized separately). The battery bus is 240 V DC on every model.
What warranty does RADIANT have?
3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.
How is RADIANT monitored over the network?
With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.
What is the output current of each RADIANT model?How much heat does each RADIANT model give off?Which RADIANT models fit through a standard door?All 8 questions
Also in 208V three-phase UPS:ETHERNOAUREONRADIANT-IBCompare the range
The RADIANT for your project
Send the load, the voltage and the minutes. We reply with the RADIANT model that fits, its batteries and the lead time.