Example designs

UPS example designs: office, hospital, data center, plant.

A small office, a medium office, a hospital, a data center and a plant: each as an electrical plan to scale and a single-line diagram, with AEC equipment at its catalog size.

Illustrations, not customer installations, and not for construction: AEC equipment is drawn from the catalog's dimensions and weights, everything else is by others and drawn for scale only. Ratings are nominal; the engineer of record designs every project, and our engineers size the AEC part of it.

Example design 1 of 5

Small office, 120 V

A 2,000 ft² office suite: the network rack on a 2U lithium LUMINA, the reception desk on a FERRUS tower.

8877665544332211AABBCCDDEEFF 123ABOPEN OFFICE101CONFERENCE102OPEN OFFICE103RECEPTION100BREAK ROOM104IT 105OFFICE1061320'-0"18'-0"8'-0"10'-0"56'-0"16'-0"8'-0"12'-0"36'-0"1FLOOR PLAN, SUITE 100SCALE: 1/4" = 1'-0"016'N R1P13'-0"12UPS-1 (2U) IN R1TRAY 12"8'-0"12'-0"2ENLARGED PLAN, IT 105SCALE: 1/2" = 1'-0"04' UPS-1 LUMINAPDUSERVERFIREWALLSWITCHPATCH PANELSWITCHPATCH PANEL 1102030423RACK R1SCALE: 3/4" = 1'-0"02' EQUIPMENT SCHEDULE TAGDESCRIPTIONMODELRATINGW × D × H (IN)WEIGHT UPS-1UPS, ONLINE, 2U RACK, LITHIUMLUM3000RT-2U-LI3 KVA / 120 V17.24 × 22.44 × 3.4338 LBUPS-2UPS, ONLINE, TOWERFER2000-4X92 KVA / 120 V7.48 × 12.56 × 15.7536 LBR1IT RACK, 42U (BY OTHERS)——24 × 42 × 84—P1PANELBOARD 120/240 V (BY OTHERS)—200 A MAIN20 × 6 × 48— KEYNOTES1.UPS-1 IN RACK R1 ON THE RAIL KIT SUPPLIED, AT THE BOTTOM OF THE RACK; RACK R1 3'-0" CLEAR IN FRONT AND BEHIND.2.PANEL P1: WORKING SPACE PER NEC 110.26, 3'-0" DEEP, 30" WIDE, 6'-6" HIGH.3.UPS-2 UNDER THE RECEPTION DESK: VENTS CLEAR; POS, PC AND PHONE SYSTEM ON ITS OUTLETS. AEC UPS USA4872 SW 72 AVENUEMIAMI, FL 33155 PROJECTSMALL OFFICESUITE 100, 120/240 V ILLUSTRATIVE ONLYNOT FOR CONSTRUCTIONEXAMPLE DESIGN, NOT A CUSTOMER SITE REVISIONS REVDESCRIPTIONDATE 0FOR ILLUSTRATION2026-11-25 LEGEND AEC EQUIPMENT, CATALOG SIZEBY OTHERS, FOR SCALEIT RACK 24" × 42"WORKING SPACE, NEC 110.26WALL FRONT OF EQUIPMENT CABLE TRAY KEYNOTE COLUMN GRID DRAWNAEC UPS USA ENG.DATE2026-11-25SCALEAS NOTED SHEET TITLEFLOOR PLAN, IT ROOM,RACK ELEVATION SHEETE-101
Drag to pan · scroll or pinch to zoom · tap equipment

Example design 2 of 5

Medium office, 208 V

A 5,400 ft² office floor: a server room with six racks on one 30 kVA ETHERNO tower, lithium inside.

8877665544332211AABBCCDDEEFF 1234ABCOPEN OFFICE201CONFERENCE202SERVER203ELEC.204LOBBY200COPY205OFFICES206MDPCP-11230'-0"30'-0"30'-0"90'-0"30'-0"30'-0"60'-0"1PARTIAL SECOND FLOOR PLANSCALE: 3/16" = 1'-0"020'N UPS-1R1R2R3R4R5R6COLD AISLETRAY 18"1216'-0"22'-0"4'-7"2ENLARGED PLAN, SERVER 203SCALE: 3/8" = 1'-0"08' EQUIPMENT SCHEDULE TAGDESCRIPTIONMODELRATINGW × D × H (IN)WEIGHT UPS-1UPS, ONLINE, TOWER, 3 LITHIUM MODULES INSIDEETH30-3X50A-LI30 KVA / 30 KW, 208 V12.6 × 39.1 × 49.2485 LBR1–R6IT RACKS (BY OTHERS)——24 × 42 × 84—MDPMAIN DISTRIBUTION PANEL (BY OTHERS)—800 A, 208Y/120 V——CP-1CRITICAL PANEL ON UPS (BY OTHERS)—225 A, 208Y/120 V—— KEYNOTES1.UPS-1 ETHERNO: LITHIUM MODULES INSIDE THE TOWER, NO BATTERY ROOM. 3'-6" CLEAR AT THE FRONT FOR SERVICE AND MODULE SWAPS.2.RACKS IN TWO ROWS, FRONTS TO THE COLD AISLE; RACK PDUS FED FROM CP-1. AEC UPS USA4872 SW 72 AVENUEMIAMI, FL 33155 PROJECTMEDIUM OFFICESECOND FLOOR, 208Y/120 V ILLUSTRATIVE ONLYNOT FOR CONSTRUCTIONEXAMPLE DESIGN, NOT A CUSTOMER SITE REVISIONS REVDESCRIPTIONDATE 0FOR ILLUSTRATION2026-11-25 LEGEND AEC EQUIPMENT, CATALOG SIZEBY OTHERS, FOR SCALEIT RACK 24" × 42"WORKING SPACE, NEC 110.26WALL FRONT OF EQUIPMENT CABLE TRAY KEYNOTE COLUMN GRID DRAWNAEC UPS USA ENG.DATE2026-11-25SCALEAS NOTED SHEET TITLEPARTIAL FLOOR PLAN,SERVER ROOM SHEETE-101
Drag to pan · scroll or pinch to zoom · tap equipment

Example design 3 of 5

Hospital, critical branch, 480 V

An emergency electrical room: three transfer switches for the essential system, and a 200 kVA INFINITE on lithium for the critical branch.

8877665544332211AABBCCDDEEFF 123ABUPS-1BC-1MBP-1ATS-CRATS-LSATS-EQ225 KVAT-1CDPLS-1CR-1EQ-14'-0" (480 V)4'-0"4'-0"3'-0" WORKING SPACECABLE TRAY 24" ABOVEEMERGENCY ELECTRICAL ROOMB-1101234520'-0"20'-0"40'-0"24'-0"6'-8"1ENLARGED PLAN, EMERGENCY ELECTRICAL ROOM B-110SCALE: 3/8" = 1'-0"08'N KEYNOTES1.UPS-1, BC-1 AND MBP-1 IN ONE LINE-UP, FRONTACCESS. BC-1 WEIGHS 2,172 LB: CONFIRM FLOORLOADING.2.ATS-CR, ATS-LS, ATS-EQ: THE CRITICAL, LIFESAFETY AND EQUIPMENT BRANCHES OF THE ESSENTIALELECTRICAL SYSTEM, KEPT SEPARATE.3.T-1 STEPS THE UPS OUTPUT DOWN TO 208Y/120 V FORTHE CRITICAL CARE PANELS.4.BRANCH PANELS IN SEPARATE ENCLOSURES ANDRACEWAYS, AS NEC 517 REQUIRES.5.DOORS OPEN OUTWARD WITH LISTED PANIC HARDWARE(NEC 110.26(C)(3)). EQUIPMENT SCHEDULE TAGDESCRIPTIONMODELRATINGW × D × H (IN)WEIGHT UPS-1UPS, MODULAR, SIC, 2 × 100 KVA MODULESINF-200200 KVA, 480 V 3W23.62 × 39.37 × 81.42591 LBBC-1LITHIUM BATTERY CABINET, 20 × 50 AH, BMSL6-CAB-20x50LI~58 KWH23.6 × 33.5 × 78.72,172 LBMBP-1MAINTENANCE BYPASS PANEL (BY OTHERS)—350 A, 480 V——ATS-CR/LS/EQTRANSFER SWITCHES, EES BRANCHES (BY OTHERS)—480Y/277 V——T-1TRANSFORMER 480 V – 208Y/120 V (BY OTHERS)—225 KVA—— AEC UPS USA4872 SW 72 AVENUEMIAMI, FL 33155 PROJECTHOSPITALCRITICAL CARE WING ILLUSTRATIVE ONLYNOT FOR CONSTRUCTIONEXAMPLE DESIGN, NOT A CUSTOMER SITE REVISIONS REVDESCRIPTIONDATE 0FOR ILLUSTRATION2026-11-25 LEGEND AEC EQUIPMENT, CATALOG SIZEBY OTHERS, FOR SCALEIT RACK 24" × 42"WORKING SPACE, NEC 110.26WALL FRONT OF EQUIPMENT CABLE TRAY KEYNOTE COLUMN GRID DRAWNAEC UPS USA ENG.DATE2026-11-25SCALE3/8" = 1'-0" SHEET TITLEENLARGED PLAN,EMERGENCY ELEC. ROOM SHEETE-102
Drag to pan · scroll or pinch to zoom · tap equipment

Example design 4 of 5

Data center, 2N, 480 V

Two complete UPS systems, A and B, each able to carry the whole 300 kW hall: INFINITE on lithium, side by side in one room.

8877665544332211AABBCCDDEEFF 123ABUPS-A1UPS-A2BC-A1BC-A2MBP-ASWBD-A4'-0" WORKING SPACEUPS-B1UPS-B2BC-B1BC-B2MBP-BSWBD-B4'-0" WORKING SPACEPDU-A1PDU-B1UPS AND BATTERY ROOME-100PDUE-101TRAY A 24"TRAY B 24"1123SIDE ASIDE B39'-0"9'-0"48'-0"30'-0"4'-0"1ENLARGED PLAN, UPS AND BATTERY ROOM E-100SCALE: 3/8" = 1'-0"08'N KEYNOTES1.SIDE A AND SIDE B: TWO COMPLETE UPS SYSTEMS(2N); EACH CARRIES THE WHOLE CRITICAL LOAD.2.LITHIUM CABINETS NEXT TO THEIR UPS: BMS,SMOKE DETECTOR. CONFIRM FLOOR LOADING.3.A AND B CABLES IN SEPARATE TRAYS AND PATHSTO THE PDUS.4.DOORS OPEN OUTWARD WITH LISTED PANICHARDWARE (NEC 110.26(C)(3)). E-100DATA HALL, 120 RACKSA/B2KEY PLANSCALE: 1/32" = 1'-0"064' EQUIPMENT SCHEDULE TAGDESCRIPTIONMODELRATINGW × D × H (IN)WEIGHT UPS-A1/A2, B1/B2UPS, MODULAR, SIC: 2 × 200 KVA CABINETS PER SIDEINF-400 (×2)400 KVA PER SIDE23.62 × 39.37 × 81.42 (×4)2,365 LB TOTALBC-A1/A2, B1/B2LITHIUM BATTERY CABINETS, 20 × 50 AH, BMSL6-CAB-20x50LI~58 KWH EACH23.6 × 33.5 × 78.7 (×4)8,686 LB TOTALMBP-A, MBP-BMAINTENANCE BYPASS (BY OTHERS)—700 A, 480 V——SWBD-A, SWBD-BUPS OUTPUT SWITCHBOARDS (BY OTHERS)—800 A, 480 V——PDU-A1, PDU-B1POWER DISTRIBUTION UNITS (BY OTHERS)—480 – 208Y/120 V—— AEC UPS USA4872 SW 72 AVENUEMIAMI, FL 33155 PROJECTDATA CENTERDATA HALL 1, 2N ILLUSTRATIVE ONLYNOT FOR CONSTRUCTIONEXAMPLE DESIGN, NOT A CUSTOMER SITE REVISIONS REVDESCRIPTIONDATE 0FOR ILLUSTRATION2026-11-25 LEGEND AEC EQUIPMENT, CATALOG SIZEBY OTHERS, FOR SCALEIT RACK 24" × 42"WORKING SPACE, NEC 110.26WALL FRONT OF EQUIPMENT CABLE TRAY KEYNOTE COLUMN GRID DRAWNAEC UPS USA ENG.DATE2026-11-25SCALEAS NOTED SHEET TITLEENLARGED PLAN,UPS AND BATTERY ROOM SHEETE-103
Drag to pan · scroll or pinch to zoom · tap equipment

Example design 5 of 5

Industrial plant, 480 V, 800 kVA

A process plant's control power: one CIRRO 800 frame with eight 100 kVA modules, VRLA racks in their own battery room.

8877665544332211AABBCCDDEEFF 123ABCIRRO 800UPS-1MBP-1SWBD-1MSBMCC-C4'-0" WORKING SPACE4'-0" WORKING SPACEBR-1BR-2BR-3BR-4EWUPS ROOMP-120BATTERY ROOMP-121CABLE TRAY 30"DC1234530'-0"20'-0"50'-0"32'-0"2'-8"1ENLARGED PLAN, UPS AND BATTERY ROOMSSCALE: 1/4" = 1'-0"016'N KEYNOTES1.UPS-1: ONE CIRRO 800 FRAME, FRONT ACCESS; POWER MODULESHOT-SWAPPABLE.2.EYEWASH (EW) AND SPILL CONTAINMENT IN THE BATTERY ROOM ASTHE CODE REQUIRES FOR VRLA.3.BATTERY ROOM VENTILATION AND TEMPERATURE PER THE BATTERYMANUFACTURER AND THE FIRE CODE.4.MSB AND MCC-C: NORMAL AND MOTOR POWER, NOT ON THE UPS.5.DOORS OPEN OUTWARD WITH LISTED PANIC HARDWARE (NEC110.26(C)(3)). EQUIPMENT SCHEDULE TAGDESCRIPTIONMODELRATINGW × D × H (IN)WEIGHT UPS-1UPS, MODULAR, 8 × 100 KVA MODULES, 4 BREAKERSCIR800-8X100800 KVA, 480 V 4W31.5 × 39.4 × 78.71,902 LBBR-1–4VRLA BATTERY RACKS, SIZED TO THE MINUTESAEC AGMPER RUNTIME——MBP-1MAINTENANCE BYPASS (BY OTHERS)—1600 A——SWBD-1UPS OUTPUT SWITCHBOARD (BY OTHERS)—1600 A, 480 V——MSB, MCC-CSWITCHBOARD AND MOTOR CONTROL (BY OTHERS)—3000 A, 480 V—— AEC UPS USA4872 SW 72 AVENUEMIAMI, FL 33155 PROJECTINDUSTRIAL PLANTPROCESS BUILDING ILLUSTRATIVE ONLYNOT FOR CONSTRUCTIONEXAMPLE DESIGN, NOT A CUSTOMER SITE REVISIONS REVDESCRIPTIONDATE 0FOR ILLUSTRATION2026-11-25 LEGEND AEC EQUIPMENT, CATALOG SIZEBY OTHERS, FOR SCALEIT RACK 24" × 42"WORKING SPACE, NEC 110.26WALL FRONT OF EQUIPMENT CABLE TRAY KEYNOTE COLUMN GRID DRAWNAEC UPS USA ENG.DATE2026-11-25SCALE1/4" = 1'-0" SHEET TITLEENLARGED PLAN,UPS AND BATTERY ROOMS SHEETE-104
Drag to pan · scroll or pinch to zoom · tap equipment

How to read them

The sheets, like a design set.

Each application has the two sheets an electrical design set starts from.

E-1xx · PlansRooms to scale with column grid, dimensions, door swings and the working space in front of the equipment (NEC 110.26); AEC equipment hatched in red at its catalog footprint, the front marked heavy.
E-601 · Single-lineFrom the utility and the generator to the load: transformers, breakers, transfer switches, buses, and the UPS with its rectifier, inverter, battery and static bypass, inside the red dashed line.
Schedules and notesThe equipment schedule with model, rating, size and weight; keynotes on the plan, notes on the one-line; title block with sheet number and revision.
Your projectSend us the plan and the one-line: our engineers return the AEC equipment, its batteries and its footprint for your drawings.

Send us your drawings

The plan, the one-line, the load and the minutes: our engineers answer with the AEC system for it.