Room fit
UPS room fit: will it fit, and where
Pick an AEC UPS and give the room: Room fit places it to the inch with its clearances, NEC 110.26 working space, door swing, cable entry and breaker reach, and says what fails and how to fix it. Every figure comes from the AEC US manual of that series.
Room fit
Loading Room fit…
Questions
What people ask
How much working space does a UPS need in front?
3 ft in front of equipment up to 150 V to ground, under NEC 110.26(A)(1). From 151 to 600 V, 3 ft with nothing grounded opposite, 3.5 ft facing a grounded wall, 4 ft facing other live equipment. At least 30 in wide or the width of the equipment, and 6.5 ft high. Room fit draws it and checks it.
How high can the UPS breakers be?
NEC 240.24(A): the center of the handle in its highest position no more than 6 ft 7 in above the floor. Room fit marks that line on the front view and checks every breaker it knows the height of.
Does Room fit check the way in?
Yes: every door, corridor and elevator between the truck and the room, against the cabinet's size and weight as it travels.
Can I get the layout as a PDF or for CAD?
Yes, with the project: ask AEC and an engineer sends the PDF layout and the plan for CAD.
For the model itself, the sizing tool; for the batteries, battery runtime.
Room fit for a project
Send the room and the load: we place the UPS and its batteries and send the layout.