Technology
How AEC UPS systems work.
Seven deep dives with the catalog's figures, the app's diagrams and the real displays: online double conversion, LiFePO4 lithium, modular redundancy, efficiency, monitoring, isolation transformers and the history of the power switch. Open the cabinets, switch the operating modes and read the curves.





Short answers
What do these articles answer?
What does online double conversion mean? The rectifier and the inverter run all the time, so the load is always fed by the inverter and nothing transfers when the utility fails: 0 ms. Every AEC UPS works this way.
Is a lithium UPS battery safe? AEC uses lithium iron phosphate (LiFePO4), the lithium chemistry least prone to thermal runaway, in 50 Ah modules each watched by a battery management system and each on its own DC/DC converter.
What is N+1 redundancy in a modular UPS? One power module more than the load needs: a module can fail or be swapped while the others carry the load on the inverter.
How much does UPS efficiency save? Losses are the load times (1 ÷ efficiency − 1): at a steady 100 kW, 96 % loses 4.2 kW, about 36,500 kWh a year, and 97.5 % loses 2.6 kW.
How is a UPS monitored over the network? With a network card (SNMP v1, v2c and v3, Modbus TCP), a dry-contact relay card for alarms, or the UPS's own touchscreen.
Which power semiconductors do AEC UPS use? 3-level IGBTs in FERRUS, ETHERNO, AUREON, RADIANT and CIRRO, and silicon carbide (SiC) in INFINITE, the last two steps of a line that began with the thyristor in 1957.
When does a UPS need an isolation transformer? When the load needs galvanic isolation from the supply, a new neutral, or a different voltage, such as 208/120 V loads behind a 480 V UPS.
Talk to an engineer
Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.