For specifiers · CSI 26 33 53

AEC INFINITE guide specification

A three-part specification for Section 26 33 53, Static Uninterruptible Power Supply, written from the INFINITE catalog data. Download it for Word, or copy it from this page and edit it to your project.

SECTION 26 33 53 – STATIC UNINTERRUPTIBLE POWER SUPPLY: AEC INFINITE

PART 1 – GENERAL

1.1 SUMMARY

  • A. This Section specifies an online double-conversion uninterruptible power supply (UPS) system, AEC INFINITE series, 100 to 600 kVA, 480 V three-phase, 3-wire (delta), complete with lithium-ion (LiFePO4) batteries in external battery cabinets, controls, monitoring and accessories.
  • B. Related requirements: Division 26 sections for wiring, grounding and overcurrent protection; the battery and the UPS installation per the manufacturer's instructions.

1.2 REFERENCES

  • A. NFPA 70, National Electrical Code (NEC), for the installation.
  • B. The manufacturer's published product data, user manual and single-line diagram, current edition.

1.3 SUBMITTALS

  • A. Product data: the manufacturer's catalog sheet for the selected model, with rating, efficiency, dimensions and weight.
  • B. Battery runtime at the project load, from the manufacturer's published runtime data.
  • C. Operation and maintenance data: the manufacturer's user manual.

1.4 QUALITY ASSURANCE

  • A. Source qualifications: AEC, the UPS brand of the AEC Group. Parent company: Allis Electric Co., Ltd., in power equipment since 1968, listed on the Taiwan Stock Exchange as 1514; the group's quality management system is certified to ISO 9001:2015 (SGS).
  • B. Sales and service in the United States: AEC UPS USA, Miami, Florida, warehouse in Doral, Florida.

1.5 WARRANTY

  • A. Manufacturer's standard warranty: 3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries.

PART 2 – PRODUCTS

2.1 MANUFACTURERS

  • A. Basis-of-design product: AEC INFINITE series (AEC, the UPS brand of the AEC Group), supplied in the United States by AEC UPS USA (https://www.aecups.com).
  • B. Substitutions: as permitted by Division 01.

2.2 SYSTEM DESCRIPTION

  • A. Topology: Online double conversion, modular. The load is supplied by the inverter in normal operation, with automatic static bypass and a manual maintenance bypass.
  • B. Ratings: 100 kVA, 200 kVA, 400 kVA, 600 kVA; output power factor 1.0 (kVA = kW where the factor is 1.0).
  • C. Input and output: 480 V three-phase, 3-wire (delta).
  • D. Efficiency: up to 97.3% (manufacturer's published figure).
  • E. Technology: Silicon-Carbide (SiC) semiconductors; unity power factor; 120 A settable charger; up to 3 frames in parallel (600 kVA).
  • F. Display: 7-inch color touchscreen.
  • G. Comms: RS232, RS485/Modbus, EPO and dry contacts standard; SNMP card optional.
  • H. Battery: external, lead-acid (30–50 blocks) or AEC L6 lithium cabinets.
  • I. Use: 100 to 600 kVA: one 100 or 200 kVA frame, or up to three 200 kVA frames in parallel; above 600 kVA, INFINITE 1.5MW.
  • J. Network card: SNMP-L (SNMP).
  • K. Quality system: ISO 9001:2015, the group's quality system (SGS).

2.3 BATTERY

  • A. Type: VRLA or lithium LiFePO4, external VRLA bank or L6 lithium cabinets.
  • B. Nominal DC bus: 480 V DC.
  • C. Runtime: per the manufacturer's published runtime data for the selected model at the project load; L6 lithium cabinets of 10 or 20 hot-swappable 50 Ah modules with battery management system.

2.4 MODELS

  • INF-100: 100 kVA; 100 kW; VRLA or lithium LiFePO4; 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm); 452.2 lb (205.1 kg).
  • INF-100+1: 100 kVA; 100 kW; VRLA or lithium LiFePO4; 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm); 571.3 lb (259.1 kg).
  • INF-100+1+L6-CAB-20x50LI: 100 kVA; 100 kW; Lithium LiFePO4; 2,742.8 lb (1,244.1 kg).
  • INF-100+L6-CAB-10x50LI: 100 kVA; 100 kW; Lithium LiFePO4; 1,808 lb (820.1 kg).
  • INF-100+L6-CAB-20x50LI: 100 kVA; 100 kW; Lithium LiFePO4; 2,623.8 lb (1,190.1 kg).
  • INF-200: 200 kVA; 200 kW; VRLA or lithium LiFePO4; 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm); 591.3 lb (268.2 kg).
  • INF-200+1: 200 kVA; 200 kW; VRLA or lithium LiFePO4; 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm); 710.4 lb (322.2 kg).
  • INF-200+1+L6-CAB-20x50LI: 200 kVA; 200 kW; Lithium LiFePO4; 2,881.9 lb (1,307.2 kg).
  • INF-200+L6-CAB-20x50LI: 200 kVA; 200 kW; Lithium LiFePO4; 2,762.9 lb (1,253.2 kg).
  • INF-400: 400 kVA; 400 kW; VRLA or lithium LiFePO4; 2 cabinets, each 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm); 1,182.5 lb (536.4 kg).
  • INF-400+2xL6-CAB-20x50LI: 400 kVA; 400 kW; Lithium LiFePO4; 5,525.7 lb (2,506.4 kg).
  • INF-600: 600 kVA; 600 kW; VRLA or lithium LiFePO4; 3 cabinets, each 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm); 1,773.8 lb (804.6 kg).
  • INF-600+3xL6-CAB-20x50LI: 600 kVA; 600 kW; Lithium LiFePO4; 8,597.2 lb (3,899.6 kg).

PART 3 – EXECUTION

3.1 INSTALLATION

  • A. Install according to the manufacturer's instructions and NFPA 70, with the clearances the manufacturer's manual gives for service access and airflow.
  • B. Provide input, bypass, output and battery overcurrent protection and conductors sized to the selected model and the manufacturer's data.

3.2 FIELD QUALITY CONTROL AND START-UP

  • A. Start-up by a technician authorized by the manufacturer: check of wiring and grounding, battery connection, operating modes and alarms.
  • B. Record the readings at start-up and hand them over with the operation and maintenance data.

3.3 DEMONSTRATION

  • A. Train the owner's personnel in normal operation, transfer to and from bypass and maintenance bypass, alarms and the battery.

Edit to the project. Product figures from the AEC 2026 catalog. END OF SECTION 26 33 53.