Operating guide

INFINITE, step by step

5 INFINITE procedures from the user manual, with the real screen at every step: shut the UPS down; daily check of the readings; read a fault: current list, history, waveforms; silence the buzzer; to maintenance bypass and back. Section numbers refer to the manual.

Daily use

Shut the UPS downLoads off, inverter OFF, switches open, wait for the screen to go dark.§5.1.4 (p. 85) · 5 steps
  1. Turn off the user loads.

    Caution With an abnormal bypass, an inverter shutdown cuts the output: the load must be able to lose power.

    Mains inverter output (normal)
  2. Tap the Inverter ON/OFF icon.

    Press: Inverter ON / OFF

    You should see “Confirm to power off?”

    Why Or hold the two OFF buttons on the operation panel for 3 s.

    Mains inverter output (normal)
  3. Tap Single OFF (Parallel OFF on a parallel system, Figure 5-5).

    Press: Single OFF

    You should see Inverter indicator off, bypass indicator green: Bypass output.

    Inverter OFF
  4. If only the inverter had to stop, you are done: the load is on bypass. For a full shutdown go on.

    Bypass output — inverter off
  5. Open the external battery switch, the mains switch, the bypass switch and the output switch, in that order. Wait until the touch screen and every LED are off.

    You should see The output stops; the touch screen and every LED go dark.

    Caution Dangerous voltage remains inside: wait 10–15 minutes and check with a meter before you open covers (§5.1.4, §1.5).

Daily check of the readingsMains, bypass, battery, rectifier, inverter and output from the diagram.§6.3 (Table 6-1, p. 95) · 12 steps
  1. From the main page, tap Mains.

    Press: Mains information

    You should see Phase and line voltage, current, frequency.

    Mains inverter output (normal)
  2. Back.

    Press: Back

    Mains info
  3. Tap Bypass.

    Press: Bypass information

    Mains inverter output (normal)
  4. Back.

    Press: Back

    Bypass info
  5. Tap Battery: voltage, currents, remaining capacity and time, status.

    Press: Battery information

    Why On mains the status reads Floating charge (or Equalized charge after a discharge).

    Mains inverter output (normal)
  6. Back.

    Press: Back

    Battery info
  7. Tap Rectifier: each power module's input side.

    Press: Rectifier information

    Mains inverter output (normal)
  8. Module-1 picks another module.

    Press: Module-1

    Rectifier info
  9. Back.

    Press: Back

    Rectifier info
  10. Tap Inverter: each module's output, load rate and power.

    Press: Inverter information

    Why The modules should share the load evenly; one far off points to a module problem.

    Mains inverter output (normal)
  11. Back.

    Press: Back

    Inverter info
  12. Tap Output: the total output, load rate and power factor.

    Press: Output information

    Mains inverter output (normal)
Read a fault: current list, history, waveformsFrom the alarm icon to the history record and wave capture.§6.2, §6.4 (Table 6-2), §2.11 · 10 steps
  1. The alarm icon is red: tap it.

    Press: Current fault

    You should see Current abnormal: each fault with date and time.

    Fault protection — no output
  2. Open Info manage (magnifier).

    Press: Info manage

    Current abnormal
  3. History record: what happened before and after.

    Press: History record

    Info manage
  4. Scroll to older records.

    Press: Scroll down

    Why “recover” lines show when each event ended.

    History record
  5. Back to Info manage.

    Press: Back

    History record
  6. Smart wave capture: the waveforms saved at the fault.

    Press: Smart wave capture

    Info manage
  7. Pick the capture with the fault's time — here 01, a mains power down.

    Press: Capture 01

    You should see The waveforms around the event: the mains voltages fall to zero at the cursor, the bus voltage holds.

    Smart wave capture
  8. Untick a signal to read the others more easily; Back returns to the list.

    Press: Back

    Wave capture 01 — mains power down
  9. Before calling service, export the records (Record manage) and note the S/N (Device info).

    Press: Back

    Smart wave capture
  10. Device info: model and S/N.

    Press: Device info

    Info manage
Silence the buzzerWhat can be silenced and what cannot.§6.2.2 (p. 95) · 4 steps
  1. A fault sounds the buzzer. Read it first: tap the alarm icon.

    Press: Current fault

    Fault protection — no output
  2. Back to the main page.

    Press: Home

    Current abnormal
  3. Tap the buzzer icon to turn the buzzer off.

    Press: Buzzer

    You should hear Silent — until a new fault occurs, which turns it back on.

    Caution A continuous beep cannot be silenced from the icon: it stops only when its cause is removed (EPO, output faults, overload protection, system and cabinet faults — Alarms tab).

    Fault protection — no output
  4. Tap it again to turn the buzzer back on.

    Press: Buzzer

    Fault protection — no output

Commissioning & service

To maintenance bypass and backWithout dropping the load.§7.1.1 – 7.1.2 (pp. 116–118) · 9 steps
  1. Inverter off first: tap Inverter ON/OFF.

    Press: Inverter ON / OFF

    Caution With an abnormal bypass this cuts the output: the load must be able to lose power.

    Mains inverter output (normal)
  2. Single OFF (Parallel OFF on a parallel system).

    Press: Single OFF

    You should see Inverter indicator off, bypass indicator green: Bypass output.

    Inverter OFF
  3. Check the inverter is off, then close the external maintenance bypass switch.

    Bypass output — inverter off
  4. The screen shows “Maintenance bypass open”: the load is on the maintenance bypass.

    Maintenance bypass output
  5. Open the external battery switch, utility switch, bypass switch and output switch, one by one. Wait until screen and LEDs are off; after 10–15 minutes (§1.5, p. 13; §5.1.4), check with a meter, then maintenance can start.

    Caution Never close the output switch in this state. The maintenance bypass is a separate source: the output side can carry lethal voltage.

    Maintenance bypass output
  6. Return: the bypass input must be normal. Close the bypass switch and the mains switch: the touch screen lights up, still showing the maintenance bypass. Bypass module ready switch locked; close the external battery switch (no “Not allow to connect battery” alarm first).

    Maintenance bypass output
  7. Close the output switch: the Output icon on the main page lights. When the bypass indicator is green, open the maintenance bypass switch: the message disappears and the beeping stops.

    Bypass output — inverter off
  8. Lock the ready switches of all power modules. When their run indicators flash green slowly, start the inverter: Inverter ON/OFF.

    Press: Inverter ON / OFF

    Bypass output — inverter off
  9. Single ON (Parallel ON on a parallel system).

    Press: Single ON

    You should see The DC/AC indicator turns green; about 10 s later the bypass indicator goes off: inverter output.

    Inverter ON — single system

38 more INFINITE procedures, settings, commissioning, parallel systems and service, with the full display simulator, are in the AEC partner portal.

Alarms and buzzer

Fault informationBuzzer & lampsWhat it blocks / means
Mains overvoltage / under-voltage / unbalance / over- or underfrequency / power down / phase loss / phase sequence abnormal / large mains harmonic component / mains flash drop / mains PFC overload protection / large mains DC componentSlow beep · rectifier LED red · Mains icon red · yellow lampMains supply not allowed: the UPS runs on battery. Check the input voltage and wiring.
Battery reverse connection / overvoltage / charger overcurrent / battery circuit abnormal / under-voltage protection / overloadRapid beep · battery LED red · Battery icon red · yellow lampBattery power not allowed. Check polarity, battery switch and cells.
Bypass overvoltage / under-voltage / unbalance / over- or underfrequency / power down / phase loss / phase sequence abnormal / large bypass harmonic componentsSlow beep · bypass LED red · Bypass icon red · yellow lampBypass output not allowed: the inverter cannot transfer to bypass. Check the bypass window (Output setting → Bypass range).
ECO power down fast detection / overvoltage / under-voltage / over- or underfrequency; WECO under-voltageSlow beep · yellow lampECO (W-ECO) output not allowed: the load goes to inverter.
Inverter output fault / output short circuit / inverter over- or under-voltage / low output PF / large output DC componentContinuous beep · inverter LED red · Output icon red · red lampInverter output not allowed. Check the output for short circuits and the load.
Output circuit abnormalSlow beep · inverter LED red · Output icon red · red lampOutput circuit problem; no protection action.
System fault / System bypass fault / System inverter fault / System EPO on / EPO onContinuous beep · red lampSystem fault. With System EPO on or EPO on, bypass and inverter output are not allowed: clear EPO1/EPO2 and restart (see “Emergency power off and clearing it”).
Bypass SCR abnormalContinuous beep · bypass LED red · Bypass icon red · red lampBypass output not allowed; if OUT.2 (SCR short-circuit) drives a shunt trip, the bypass breaker opens.
Bypass overload protection / inverter overload protectionContinuous beep · load LED red · Output icon red · red lampBypass overload protection: no bypass and no inverter output; inverter overload protection: no inverter output. Reduce the load.
Parallel cable abnormal / parallel system master permissions faultContinuous beep · red lampParallel cable abnormal: inverter output not allowed — check the parallel cables. Master permissions fault: no protection action.
External maintenance bypass enabled (system fault)Continuous beep · red lampInverter output not allowed while the maintenance bypass is closed. The same event as an input dry contact gives a slow beep and yellow lamp (below).
System battery charge disabled / system battery discharge disabledRapid beep · battery LED red · Battery icon red · red lampCharging or discharging blocked by an input dry contact.
Bypass overtemperatureContinuous beep · bypass LED red · Bypass icon red · red lampBypass output depends on “Bypass output allowed when over-temperature”.
Cabinet fault / inverter output overcurrent / rectifier or inverter fault self-locking / battery overload protection / battery discharge protection / UPS faultContinuous beep · red lampCabinet fault: call AEC service.
Cabinet overtemperature / battery high or low temperature / battery under-voltage alarm / backup time insufficientRapid beep · yellow lampCabinet pre-alarm: the UPS still runs. Check ventilation, battery temperature, remaining time.
Output overload alarmRapid beep · load LED red · Output icon red · yellow lampOverload pre-alarm: reduce the load before overload protection.
Output frequency out of range / bypass auxiliary power abnormal / bypass overtemperature alarm / partial power module PFC abnormal / battery power-on auto start disabledRapid beep · yellow lampCabinet pre-alarm.
Battery not connected / auxiliary power abnormalSlow beep · yellow lampCabinet alarm: check the battery switch.
Bypass installation not readySlow beep · bypass LED red · Bypass icon red · yellow lampBypass output not allowed: check the bypass module and its ready switch.
Bypass module offlineSlow beep · bypass LED red · Bypass icon redBypass output not allowed: the bypass module does not communicate.
Setting / battery parameter mismatch, module or cabinet count mismatch, system card not ready / flash abnormal / slot address repeat, system card on/off status not synchronized with master card, master/backup card parameters out of sync, output state out of syncSlow beep · yellow lampCabinet alarm: settings or cards do not agree.
Current mode is bypass output / fan dedustingSlow beep · yellow lampCabinet alarm: information on the running state (the inverter is off and the bypass feeds the load, or the fans are dedusting).
Power-on failure: load too large to invert output, load unknown waiting for common inversion, PFC / INV / CCM software inconsistent, module hardware or version inconsistent, key parameter mismatch, parallel cabinet address conflict, module version inconsistentSlow beep · yellow lampStatic startup not allowed. Compare module versions (Device info p. 3) and parallel addresses.
Component failure: bypass / cabinet / system card NTC, bypass or cabinet fan abnormal, parallel cable 1/2 alarm, bypass 1/2 or monitoring card installation not ready, dry contact expansion card offlineSlow beep · yellow lampA component failed: call service.
Communication abnormal: inner sync / equalized-current / display CAN, inter-cabinet CAN, BMS communication fault, internal SCIRapid beep · yellow lampInternal or parallel communication lost; BMS fault = check the BMS card and RJ45 to the lithium cabinet.
Smart mode: generator mode enable / charge prohibited, only one BSC system detected, load above safety load, no (insufficient) module / cabinet / system card redundancy, self-load faults, inverter and bypass out of syncSlow beep · yellow lampSmart mode alarm: information on the running mode and redundancy.
Input dry contact: battery abnormal / grounding abnormal / battery switch offRapid beep · battery LED red · Battery icon red · yellow lampReported by an input dry contact.
Input dry contact: bypass switch disconnectedSlow beep · bypass LED red · Bypass icon red · yellow lampThe bypass switch is open.
Input dry contact: output switch disconnectedSlow beep · yellow lampThe output switch is open.
Input dry contact: battery charge disabled / battery discharge disabledRapid beep · battery LED red · Battery icon red · yellow lampCharging or discharging turned off by an input dry contact.
Input dry contact: generator mode / SPD abnormal / external maintenance bypass enabled / environmental smog abnormal / mains abnormalSlow beep · yellow lampReported by an input dry contact.
Power module 1/2/3 offline, system card 1/2 offlineSlow beep · yellow lampOffline alarm state: the module or card is not seen by the system.

Troubleshooting

Mains is normal but the UPS runs on battery, the buzzer beeps intermittently
  • Poor contact in the mains connections or sockets feeding the UPS.
Closing the mains or power switch blows the fuse or trips the breaker
  • Input or output wiring wrong, e.g. a live wire swapped with ground (chassis).
The UPS outputs 480 V but stays on bypass
  • Load above the UPS rating: reduce it or use a larger UPS.
  • A temporary bypass caused by a load inrush that recovers on its own is normal.
Output normal after start-up, but stops as soon as the load is started
  • Severe overload or a short circuit in the output (adapter sockets, damaged equipment).
  • Loads not started largest first: restart the UPS, then start loads from the largest to the smallest.
The UPS shuts down by itself after a while
  • Battery under-voltage protection at the end of a discharge: normal. When mains returns the UPS restarts and charges.
  • If mains stays off a long time, open the battery switch to protect the battery, then restart the UPS and recharge fully when mains returns.
After long running the buzzer beeps continuously and the screen shows battery under-voltage
  • A low utility voltage kept the UPS on battery until the under-voltage protection: check the utility. Recharge the battery fully as soon as possible: a battery left at under-voltage loses life.
Output fine on mains, nothing on battery
  • Battery faulty or seriously damaged.
  • Charger fault: the battery never charged.
  • Battery wiring loose or poor terminal contact.
  • Battery switch open.
  • After a severe overload the UPS was not restarted and stayed on bypass.
Continuous beep, the UPS goes to bypass
  • Read the fault on the touch screen (Current fault).
Mains present but the buzzer beeps intermittently
  • Mains voltage or frequency outside the UPS's input range.
UPS fine after a mains failure but the user equipment stops
  • Poor grounding of the installation.
System fault (emergency measure, §7.8.1)
  • Switch the inverter off; if needed turn off the user load and open the UPS input/output switches to prevent further damage; call service.
The fault indicator of a power module is on
  • The power module is faulty and isolates itself; the system normally keeps running with less redundancy. Set its ready switch to unlocked, remove it and call AEC service. Wait 10–15 min and measure before opening it.
  • Never reinsert a removed faulty module, and never clear alarms by pulling modules.

Practice

Follow it on the display.

Short guided tours on the real INFINITE display.

Mains inverter output (normal)

Mains inverter output (normal)

Shut the UPS down

Step 1 of 5

Turn off the user loads.

With an abnormal bypass, an inverter shutdown cuts the output: the load must be able to lose power.

Need a technician?