Operating guide
LUMINA, step by step
6 LUMINA procedures from the user manual, with the real screen at every step: start the UPS; shut the UPS down; battery test; a mains failure, start to finish; read a fault code; EPO — emergency power off. Section numbers refer to the manual.
Daily use
Start the UPSFrom a cold, unplugged UPS to loads running on clean power.§4.1, §4.2 · 6 steps
Before starting (§4.1), check: input and output installed correctly, the input matches the rated input power, no short circuit on the output and the load within the UPS capacity, the computers and other loads switched off, the battery voltage normal.
You should see LCD dark — the UPS is off and unplugged.
Caution Inductive loads are not recommended on the output (e.g. motors): the mains generally feeds those directly (§4.1).
Connect the UPS to the mains socket (§4.2 step 1).
Press: Rear: Input
You should see The LCD stays dark until ON is pressed.
Why The UPS only starts on a deliberate press of ON.
Press and hold ON for 1 second, then let go (§4.2 step 2).
Press: ON (hold 1 s)
You should see The LCD lights: OUTPUT 120 Vac, the mains icon, the battery gauge full, the load gauge empty.
You should hear Silent.
Why The 1 s hold stops the UPS being switched on by a bump on the panel.
Wait about 10 seconds until the UPS works steadily (§4.2 step 3).
You should see The mains icon stays lit, no FAULT, no triangle.
Start the loads one by one — the biggest first, then the smaller ones.
You should see The load gauge fills: three bars at about 55 %.
Why Starting a big load last could trip the overload protection (§4.2).
Check the input: press SELECT (short presses) until INPUT and Vac light.
Press: SELECT
You should see INPUT 120 Vac — the mains voltage reaching the UPS.
Shut the UPS downLoads off, cool-down, OFF, unplug.§4.3 · 5 steps
Switch the loads off (§4.3 step 1).
You should see Load gauge empty.
Let the UPS run with no load for about 10 minutes.
Why It carries the heat out of the UPS before it stops (§4.3).
Press and hold OFF for 1 second. The manual says OFF 1 s turns the UPS off (§4.3 step 2); on mains the unit first transfers to bypass.
Press: OFF (hold 1 s)
You should see Mains icon off, bypass icon on: OUTPUT now follows the mains voltage. The output is still live, but unprotected.
Caution On bypass a mains failure drops the load at once: the battery is no longer behind it.
Press and hold OFF for 1 second again: from bypass the UPS switches the output off.
Press: OFF (hold 1 s)
You should see Bypass icon off, the LCD goes dark: no output.
Unplug the mains socket (§4.3 step 3).
Press: Rear: Input
Caution Dangerous voltage can remain inside the UPS after it is off (§5.1.1).
Power problems & alarms
Battery testA short run on battery, started by hand.§2.2.2 · 3 steps
The UPS must be on and running on mains.
You should see Mains icon lit.
Press and hold ON for 3 seconds.
Press: ON (hold 3 s)
You should see The mains icon goes off and the battery icon lights.
Why It proves the battery can carry the load before a real outage needs it.
Wait a few seconds: the test ends by itself.
You should see The mains icon returns.
A mains failure, start to finishTransfer, silence, low battery, end of battery, return of the mains.§2.2.2, §5.4, Table 5-2 · 6 steps
The mains fails.
You should see Battery icon on, mains icon off, INPUT reads 0. The output continues with no break (transfer time 0 ms).
You should hear Intermittent beep.
Silence the alarm: press and hold ON for 3 seconds.
Press: ON (hold 3 s)
You should see The mute icon (crossed speaker) lights.
You should hear Silent.
Cancel the silence: hold ON 3 s again.
Press: ON (hold 3 s)
You should see The mute icon goes off.
You should hear Intermittent beep again.
The battery runs down. Watch the battery gauge.
You should see Battery bars all off, the battery outline flashing.
You should hear Rapid beep, every 0.2 s.
Caution Save your work and shut the computers down now.
At the end of the battery the UPS stops to protect it.
You should see LCD dark: battery low-voltage protection.
The mains comes back: move nothing — the UPS restarts by itself and recharges the battery.
You should see LCD on, mains icon lit, the battery gauge starts to climb.
Faults
Read a fault codeFAULT and the triangle are lit: find which fault it is.§2.3.1, §5.4 · 3 steps
A fault appears.
You should see Warning triangle lit and the bypass icon — the inverter output is closed (Table 5-2) and the mains feeds the load through the bypass (Table 5-1 #5). FAULT lights with the code, on the fault page.
You should hear Long beep.
Press SELECT until the fault code shows (it is the last page).
Press: SELECT
You should see TMP with FAULT lit (Fig 2-15): over-temperature. Nothing else in the value area is lit.
Act on the code: for TMP check the cooling fan and that the air vents are not blocked; let the UPS cool. The Fault codes tab lists all seven codes and what to check.
Why The code points to the cause much faster than guessing (§5.4).
EPO — emergency power offOutput closed by the EPO connector, and how to recover.§2.2.4, Table 5-2 · 5 steps
The two pins of the EPO connector are joined.
You should see The triangle lit and no mode icon: bypass and inverter output both closed.
You should hear Long beep.
Press SELECT until the code shows.
Press: SELECT
You should see EPO.
Separate the two EPO pins (§2.2.4).
Press: Rear: EPO connector
You should see The EPO connector no longer outlined in red.
Switch the UPS off: hold OFF 1 s.
Press: OFF (hold 1 s)
You should see LCD dark.
Start again: hold ON 1 s.
Press: ON (hold 1 s)
You should see Mains icon, output back.
14 more LUMINA procedures, settings, commissioning, parallel systems and service, with the full display simulator, are in the AEC partner portal.
Alarms and buzzer
| On the display | Buzzer | Meaning / what to do |
|---|---|---|
| EPO | Long beep | Emergency power off: bypass and inverter outputs both closed. Separate the EPO pins, switch off and restart. |
| BUS | Long beep | Busbar (DC bus) voltage fault: the inverter output is closed. |
| TMP | Long beep | Over-temperature protection: the inverter output is closed. Check the cooling fan and that the air vents are clear. |
| OUT | Long beep | Output fault: the output stops (Table 5-1 #3). Check for a short circuit on the output or too much load. |
| MIF | Long beep | More than five inverter faults within five minutes: the UPS stays on bypass. Check for inductive load on the output or too much load. |
| BAT | Long beep | Battery fault: battery voltage too low or too high, protection — the battery cannot carry the load (here: no output in a mains failure, no battery test). |
| FAN | Rapid beep (every 0.2 s) | Fan fault: the inverter output is about to protect. Check the cooling fan. |
| Load bars all flashing | Rapid beep (every 0.2 s) | Output overload: the output is about to close — reduce the load. |
| Battery bars all flashing | Slow beep (every 2 s) | Battery voltage too high: check the battery and the charger. |
| Battery bars off, frame flashing | Rapid beep (every 0.2 s) | Battery about to run out: protect the loads and save data. |
| Battery icon, intermittent beep | Intermittent (period not given in the manual) | Mains abnormal, running on battery. Hold ON 3 s to silence. |
Troubleshooting
Mains normal, the UPS outputs but runs on battery and beeps intermittently
- Poor contact in the mains feed or the socket: the input does not get through.
The UPS outputs but stays on bypass (bypass icon always on)
- Load above the rated capacity: reduce it or use a bigger UPS.
- A short transfer to bypass on a load inrush that comes back by itself is normal.
Output normal, but it stops as soon as the load is switched on
- Heavy overload or output short circuit — often a shorted power strip, or an input shorted by a damaged device.
- Loads not started biggest-first: restart the UPS and start them in order.
Running normally, then shuts down after a while
- On battery this is the normal end-of-battery protection; with mains back it restarts and charges.
Long beep, fault triangle on, inverter failure, UPS on bypass (Table 5-1 #5)
- Overload or output short circuit.
- Drive or power transistor failure.
- Main control board failure.
- Over-temperature protection.
Runs normally, but no output when the mains fails
- Battery failure.
- Charger failure: the battery is never charged.
- Battery not connected (the link plug in DC INPUT, §3.5.1), or badly damaged.
Input normal, but the buzzer still beeps intermittently
- Mains voltage or frequency outside the UPS range (see Modes & ratings).
Everything on the panel is off
- Display board wiring loose or faulty.
Practice
Follow it on the display.
Short guided tours on the real LUMINA display.
The display reads OUTPUT 120 Vac
Inverter off and back on
The UPS runs online on mains.
You seeMains icon lit, OUTPUT 120 Vac.
Need a technician?
AEC service supports commissioning, maintenance and 24/7 after-sales: tell us the UPS and what it shows.