Operating guide
RADIANT · CIRRO, step by step
4 RADIANT · CIRRO procedures from the user manual, with the real screen at every step: read the UPS: cabinet, then one module; look at the waveforms; start the UPS (normal mode); shut the UPS down. Section numbers refer to the manual.
Daily use
Read the UPS: cabinet, then one moduleWhere each reading lives.§4.2.2–4.2.3 (pp. 37–40) · 4 steps
From the home page, open the Cabinet menu.
Press: Cabinet
You should see Bypass, Main, Output, Load and Battery tabs.
Home page Open Battery: capacity, remaining time and temperatures.
Press: Battery
You should see Voltage, current, capacity, remain time, temperatures.
Cabinet — Bypass Open the Module menu: one power module at a time.
Press: Module
You should see Input, Output, Load and Information tabs.
Cabinet — Battery Information: bus and battery voltage, charger, fan and capacitor hours, temperatures.
Press: Information
Why In the module list, green is the module you are viewing; black is a connected module.
Module — Input
Look at the waveformsOutput voltage, output current and bypass voltage.§4.2.7 (p. 54) · 4 steps
Open Scope.
Press: Scope
You should see The output voltage waveform; yellow = A, green = B, red = C.
Home page Switch to the output current.
Press: Output Current
Scope — Output Voltage And the bypass voltage.
Press: Bypass Voltage
Scope — Output Current Read the bypass voltage waveform of the three phases.
Press: Waveform
Why The pictures are flat: the display is not connected to a UPS.
Scope — Bypass Voltage
Start and stop
Start the UPS (normal mode)Breakers in order; the rectifiers and the inverters start by themselves; then the battery.§5.1.1 (p. 55) · 7 steps
All breakers open. The commissioning engineer starts the UPS after the installation is complete. Check the phase rotation of the cables (§3.7.4, p. 26).
Caution During this procedure the output terminals become live. If loads are connected, check with their users that it is safe; otherwise isolate them from the UPS output.
Home page RADIANT-IB and CIRRO-IB: close the Output (Q4), Input (Q1) and Bypass input (Q2) breakers one by one; where the cabinet has only the manual bypass breaker, close the external input and external bypass input breakers (§5.1.1 step 2). RADIANT 15–90 kVA: the Bypass and Output breakers in the frame and the external output breaker, then the external main input breaker and the Input breaker; CIRRO 60–1,600 kVA: the upstream feeders, the Bypass Input and Output breakers, then the Main Input breaker.
You should see The touchscreen lights and shows the home page; the rectifiers start, and after about 30 s the static bypass closes (§5.1.1 steps 3–5).
Home page Open Log: every event of the start-up is there (§5.1.1 note). CIRRO 60–1,600 kVA: check that there is no fault; if there is, stop and call AEC service.
Press: Log
Home page Wait: the inverters start by themselves. After about 90 s the UPS transfers from bypass to inverter (§5.1.1 step 6). RADIANT 15–90 kVA: about one minute; CIRRO 60–1,600 kVA: if they do not start, use Control → Function → ON/OFF Control.
Press: Energy flow
You should see Status indicator steady green (Table 4-1, p. 34); the energy flow runs from the main input through rectifier and inverter to the output.
Home page Close the external battery breaker: the UPS starts charging the batteries (§5.1.1 step 7). Then open Cabinet.
Press: Cabinet
Home page Battery tab.
Press: Battery
Cabinet — Bypass Check that the battery is connected and charging. Then close the external main output breaker, and the branch breakers one by one (§5.1.1 step 8). CIRRO 60–1,600 kVA: measure 480 V ± 2 V, 60 Hz ± 0.1 Hz first; the largest load first.
Press: Battery number and status
Why Every event of the start-up is in the Log (§5.1.1 note).
Cabinet — Battery
Shut the UPS downLoads off first, then EPO or the breakers.§5.2 (p. 56), §5.5 (p. 59) · 4 steps
Shut down or transfer the loads first.
Caution Shutting the UPS down switches off everything it feeds.
Home page In an emergency, a long press on EPO on the front panel cuts the load power: rectifier, inverter, static bypass and battery stop (Table 4-3 p. 35, §5.5 p. 59). To stop only the inverters and keep the load on the bypass, use Control → Function → ON/OFF Control instead.
Press: Control
Home page ON/OFF Control is the way to stop only the inverters (the display asks for confirmation; this button is not in the manuals).
Press: ON/OFF Control
Control — Function Open the external battery breaker, then the main input breaker and the bypass input breaker (internal or external) one by one. The display goes off completely (§5.2, p. 56).
Why If the UPS was on maintenance bypass, open the maintenance bypass breaker too (§5.2 note).
Control — Function
28 more RADIANT · CIRRO procedures, settings, commissioning, parallel systems and service, with the full display simulator, are in the AEC partner portal.
Alarms and buzzer
| What you see | Buzzer | Meaning and what to do |
|---|---|---|
| Status indicator steady green | Silent | Normal operation (Table 4-1, p. 34). |
| General alarm (for example an AC fault) | Two short beeps and one long beep (Table 4-2, p. 34) | A warning: orange text on the home page (p. 36), yellow in the Log (p. 50). Read the Log and look the event up. RADIANT-IB and CIRRO-IB have a green / red status indicator only (Table 4-1); the yellow indicator of RADIANT 15–90 kVA and CIRRO 60–1,600 kVA: AEC product data, not in an available manual. |
| Status indicator steady red — serious fault (for example a blown fuse or a hardware failure) | Continuous tone (Table 4-2, p. 34) | Red text on the home page (p. 36) and in the Log (p. 50). Note the event and call AEC service; do not restart repeatedly. |
| Lost N+X Redundant | Alarm | No X redundant power module in the system (p. 47): check the modules in Module; replace or reinsert the failed one. |
Troubleshooting
Communication Abnormal (home page)
- The display does not read the UPS. All the simulator's pictures show it: they come from a display not connected to a UPS.
- On a UPS: call AEC service.
Utility Abnormal
- Utility voltage or frequency outside the limits: the rectifier shuts down and the UPS runs on battery.
- Check the input voltage.
Bypass Volt Abnormal
- Bypass voltage or frequency outside the limits; it resets when the bypass returns to normal.
- First clear related alarms (bypass breaker open, Bypass Sequence Error, Input Neutral Lost).
- Check the bypass breaker and supply; if it recurs, AEC service can widen the bypass window (Set → Sys Set).
Bypass Sequence Error
- Bypass phase sequence reversed: check that the input power cables are connected correctly.
Byp Freq Over Track
- Bypass frequency outside the tracking limit: the inverter does not synchronize.
- Check the bypass supply. To return to the inverter, use Manual Transfer to Inverter (the output can be interrupted).
Battery Not Connected
- Check the battery breaker and cables.
- If the BCB status input (IP1) is not valid, the UPS reports the battery as not connected.
Battery Volt Low
- About 3 minutes of full-load runtime remain: shut the loads down in order.
Battery EOD / EOD Sys Inhibited
- The inverter stopped at end of discharge; the output stays off until the utility returns.
Battery Reverse
- Battery cables connected the wrong way.
Battery Test Fail / Battery Maintenance Fail
- Check that the UPS is normal with no alarm and the battery is above 90 % of float voltage; for Battery Maintenance Fail also that the load is above 25 % (p. 47).
Module On Less
- The capacity of the running modules is less than the load: reduce the load or add modules.
Output Over Load / Inverter Overload Tout
- Module above 100 % of its nominal rating (the CIRRO-IB manual prints 150 %, p. 46): check the load per phase (Cabinet → Load); in a parallel system, check the load balance.
- After a timeout the load moves to bypass, and back to the inverter 2 minutes after the load falls below 95 %.
Exceed Tx Times Lmt
- Too many transfers in one hour: the load stays on bypass. It returns within one hour, or clear the fault by hand. Check the load.
Output Short Circuit
- Check the loads, the output cables and terminals; then Control → Function → Fault Clear.
On UPS Inhibited
- Transfer to inverter blocked: module capacity too small for the load, rectifier not ready, or bypass voltage abnormal.
Rectifier Over Temp. / Inverter Over Temp.
- Module too hot: check the room temperature, the ventilation, the fans (and for the rectifier, the input voltage).
Inlet Over Temp. / Ambient Over Temp
- Keep the room within 32–104 °F (0–40 °C); air conditioning may be needed.
Outlet Temp Error
- Outlet temperature of a module above the limit: check the fans, the air path and the room temperature. Call AEC service.
Bypass Over Temp.
- Check the bypass load, the room temperature (below 104 °F / 40 °C) and the bypass fans.
Fan Fail / Bypass Fan Fail
- At least one fan of a module or of the bypass module failed.
Input Volt Detect Fail
- Input voltage of a module abnormal: check the input cables, fuses and the utility.
Battery Volt Detect Fail
- Battery voltage abnormal: check the batteries and battery fuses.
Bypass Volt Detect Fail
- Check that the bypass breaker is closed and good, and the bypass cables.
Input Curr Unbalance
- Input currents differ by more than 40 % of rating between phases: check the input voltage. Call AEC service.
Input Over Curr Tout
- Input over current for too long: the UPS moves to battery. Check whether the input voltage is low and the load high.
Input Neutral Lost
- Input neutral lost or not detected. A 3-pole breaker is recommended between the supply and the UPS.
Power Share Fail
- Output current of the modules out of balance: AEC service adjusts the module output voltage.
REC CAN Fail / INV IO CAN Fail / INV DATA CAN Fail / Sync Pulse Fail
- Communication between modules abnormal: check the communication cables.
Bypass CAN Fail
- Bus between the bypass module and the frame abnormal: check the connector and signal cable.
Parallel Cable Error
- Parallel cable missing, loose or not in a ring: check the parallel cables.
INV IGBT Driver Block
- Inverter IGBTs stopped: check that the power modules are fully inserted. Call AEC service.
Module ID Duplicate
- Two modules have the same ID: call AEC service to set the IDs in sequence.
Rectifier Fail / Inverter Fail / INV Bridge Fail / Bypass Module Fail / REC Soft Start Fail
- Hardware fault: call AEC service.
Firmware Error / System Setting Error
- Reserved to AEC service: call AEC service.
Fan / Capacitor / Battery / Bypass Fan Expired
- The service life is reached: replace the part, then reset its timer (Control → Function: Bypass Fan Time Reset, Clear Battery History Data).
Dust Filter Expired
- Clean or replace the dust filter, then Control → Function → Reset Dust Filter.
UPS Locked
- Manual shutdown of power modules is not allowed.
Practice
Follow it on the display.
Short guided tours on the real RADIANT · CIRRO display.

Home page
Shut the UPS down
Shut down or transfer the loads first.
You see
Shutting the UPS down switches off everything it feeds.
Need a technician?
AEC service supports commissioning, maintenance and 24/7 after-sales: tell us the UPS and what it shows.