FERRUS · 120V single-phase UPS
FER2000-4X9 FERRUS 2 kVA, 120V single-phase UPS
The AEC FERRUS FER2000-4X9 is a 2 kVA / 2 kW online double-conversion UPS for 120 V single-phase loads, with internal VRLA batteries. Kept at 80 % of its rating, it carries loads up to 1.6 kW.

Series picture.
Load by load
The FER2000-4X9 at 25, 50, 75 and 100 % load.
Its 2.0 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current, at 120 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the FER2000-4X9, 500 W | 4.2 A at the output | 89.3 % efficient | 60 W of heat | 200 BTU/h to cool |
| 50 % of the FER2000-4X9, 1.0 kW | 8.3 A at the output | 92.5 % efficient | 81 W of heat | 280 BTU/h to cool |
| 75 % of the FER2000-4X9, 1.5 kW | 12.5 A at the output | 93.0 % efficient | 113 W of heat | 390 BTU/h to cool |
| 100 % of the FER2000-4X9, 2.0 kW | 16.7 A at the output | 92.8 % efficient | 155 W of heat | 530 BTU/h to cool |
Current = kVA × load ÷ volts.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the FER2000-4X9 at your load?
The FER2000-4X9 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the FER2000-4X9?
- Output: 2,000 VA / 2,000 W (unity power factor, kVA = kW).
- Battery: internal VRLA, 4 × 12 V 9 Ah (48 Vdc).
- Outlets: 8× NEMA 5-20R.
The lines every FERRUS shares, from technology to warranty, are in the FERRUS key facts and in the datasheet below.
Size and floor
How big it is
7.5" W × 12.6" D × 15.8" H (190 × 319 × 400 mm); 36.3 lb (16.5 kg) net. It ships in one carton of 13.4 × 21.3 × 18.5 in, 48.5 lb (22 kg) gross.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The FER2000-4X9 takes the clearances, wiring, cable entry and breakers of every FERRUS model, from its AEC US user manual: see them on the FERRUS page.
Place the FER2000-4X9 in your room, to the inch, with Room fit
Datasheet
FER2000-4X9 datasheet.
The FER2000-4X9 in the AEC 2026 catalog, figure by figure. Compare it with every FERRUS model.
| Parameter | FER2000-4X9 |
|---|---|
| Power | |
| Rated power (kVA) | 2 |
| Active power (kW) | 2 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 120 V single-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 93% |
| Battery DC bus | 48 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal |
| Runtime at 50 % load | 10 min |
| Runtime at 100 % load | 4.2 min |
| Mechanical | |
| Form factor | Tower |
| Dimensions W × D × H | 7.5 × 12.6 × 15.8 in (190 × 319 × 400 mm) |
| Net weight | 36.3 lb (16.5 kg) |
| Footprint | 0.7 ft² (0.06 m²) |
| Shipping | |
| Cartons | 1 |
| Shipping weight | 48.5 lb |
| Common to every FERRUS | |
| Technology | 3-level IGBT; MOV surge protection; 8 A settable charger |
| Display | color LCD |
| Comms | RS-232, EPO and USB, standard |
| Battery, FER2000-4X9 | internal VRLA, 4 × 12V 9Ah (48 Vdc) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The FERRUS documents cover every model of the series, this one included. PDF, in English.
Quick answers
FER2000-4X9: what people ask
What is the output current of the FER2000-4X9?
16.7 A at 120 V at full load: 2.0 kVA ÷ 120 V. Size the input breaker and the cables of the FER2000-4X9 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the FER2000-4X9 give off?
About 155 W, 530 BTU/h, at full load, where it is 92.8% efficient. Plan the room's cooling for a little more than that: the FER2000-4X9 is less efficient at part load and while its battery recharges.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
FERRUS
Other FERRUS models
By power, the FER2000-4X9 is number 2 of 3 in the FERRUS series, which runs from 1 to 3 kVA. One size down is the FER1000-2X9 (1 kVA less and 20 lb lighter). One size up is the FER3000-6X9 (1 kVA more and 9 lb heavier).
Every FERRUS model side by side (3)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
|---|---|---|---|---|---|
| FER1000-2X9 | 1 kVA | 1 kVA less | 17 lb | 20 lb lighter | 10 min at 50 % load |
| FER2000-4X9 | 2 kVA | this page | 36 lb | this page | 10 min at 50 % load |
| FER3000-6X9 | 3 kVA | 1 kVA more | 45 lb | 9 lb heavier | 10 min at 50 % load |
The FER2000-4X9 for your project
Send the load, the voltage and the minutes you need from the FER2000-4X9. We reply with the configuration, the batteries and the lead time.