Questions and answers
FERRUS: questions and answers
7 questions about the AEC FERRUS, from its series page and its 3 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.
No question matches. Try another word, or ask an engineer.
Choosing, sizing and ordering 2 questions
What sizes does FERRUS come in?
1 to 3 kVA, in 3 models of the 2026 catalog for the US, from the FER1000-2X9 (1 kVA) to the FER3000-6X9 (3 kVA). The datasheet on this page gives every one.
Answered on FERRUS
What supply does FERRUS need?
110/120 V, 50–60 Hz, single-phase, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.
Answered on FERRUS
Runtime and batteries 1 question
What batteries does FERRUS use?
Internal VRLA batteries. The battery bus runs from 24 V DC to 72 V DC, by model.
Answered on FERRUS
Installation, size and connections 2 questions
What is the output current of each FERRUS model?
At full load, from the rating and the voltage:
| Model | Output current | Worked out as |
|---|---|---|
| FER1000-2X9 | 8.3 A at 120 V | 1.0 kVA ÷ 120 V |
| FER2000-4X9 | 16.7 A at 120 V | 2.0 kVA ÷ 120 V |
| FER3000-6X9 | 25.0 A at 120 V | 3.0 kVA ÷ 120 V |
Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.
Each model's own page, linked in the table, gives its full answer and data.
How much heat does each FERRUS model give off?
At full load, model by model:
| Model | Heat | BTU/h | Efficiency |
|---|---|---|---|
| FER1000-2X9 | 78 W | 260 | 92.8% |
| FER2000-4X9 | 155 W | 530 | 92.8% |
| FER3000-6X9 | 233 W | 790 | 92.8% |
Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.
Each model's own page, linked in the table, gives its full answer and data.
Communication and monitoring 1 question
How is FERRUS monitored over the network?
With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.
Answered on FERRUS
Warranty, service and maintenance 1 question
What warranty does FERRUS have?
3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.
Answered on FERRUS
By series
Still a question?
Tell us the load, the voltage and the minutes you need: an AEC engineer answers.