Technology · power electronics

From thyristor to silicon carbide

Seventy years of the power switch inside a UPS: SCR, bipolar transistors, MOSFET, IGBT, 3-level IGBT and silicon carbide. What each one changed in a typical UPS of its time (input power factor, current distortion, efficiency), and what AEC UPS use today.

1957the first thyristor
3.26 eVSiC band gap
97.5%INFINITE 1.5MW, double conversion

The eras

Seven switches, one story.

Tap an era, or use the arrow keys.

Thyristor (SCR)

1957 · Thyristor (SCR)

The thyristor: the first silicon power switch

General Electric brought out the silicon-controlled rectifier (SCR) in 1957. A gate pulse turns it on, but it turns off only when its current falls to zero. The first static UPS used it as a 6- or 12-pulse rectifier and, with extra commutation circuits, as an inverter driving a heavy output transformer.

Typical UPS of the time: input power factor around 0.8, input current distortion around 30% on a 6-pulse bridge, efficiency in the high 80s.

AEC 1968: Allis Electric is founded in Taipei, building switchboards, motor control and industrial controls.

Side by side

What each generation gained.

The faster and cleaner the switching, the higher the efficiency and the smaller the filters and transformers.

Typical figures per generation, industry-wide (not AEC data)
GenerationYearsSwitching, kHzInput PFTHDiEfficiency
Thyristor rectifier and inverter, transformer1960s–80s0.05–1≈0.8≈30%85–90%
Thyristor rectifier, BJT PWM inverter1970s–80s1–5≈0.8≈30%88–91%
IGBT inverter with output transformer1990s2–100.9–0.958–10%90–93%
IGBT rectifier and inverter, transformerless2000s10–200.99< 5%93–95%
3-level IGBT2010s10–200.99< 3%96–97%
Silicon carbide (SiC)2020s20–1000.99< 3%97.5–99%
INFINITE 1.5MW (AEC)today———97.5%

The heat

Every point of efficiency is heat you do not make.

Losses = load × (1 ÷ efficiency − 1), at the middle of each generation's typical band, with a steady 100 kW load.

Thyristor rectifier and inverter, transformer87.5%
heat14.3
kW lost per 100 kW of load, about 125 MWh a year
Thyristor rectifier, BJT PWM inverter89.5%
heat11.7
kW lost per 100 kW of load, about 103 MWh a year
IGBT inverter with output transformer91.5%
heat9.3
kW lost per 100 kW of load, about 81 MWh a year
IGBT rectifier and inverter, transformerless94%
heat6.4
kW lost per 100 kW of load, about 56 MWh a year
3-level IGBT96.5%
heat3.6
kW lost per 100 kW of load, about 32 MWh a year
Silicon carbide (SiC)98.3%
heat1.8
kW lost per 100 kW of load, about 16 MWh a year

AEC ranges' efficiency, curve by curve

Did you know?

Notes from power electronics.

01

The word thyristor joins thyratron, the gas-filled tube it replaced, and transistor.

02

Silicon carbide was first made in 1891 by Edward Acheson, as an abrasive he called carborundum. Henri Moissan found it in nature, in a meteorite, in 1893: the mineral is named moissanite after him.

03

In 1907 Henry Round saw a silicon carbide crystal glow under voltage: the first light-emitting diode, a hundred years before SiC reached the UPS.

04

At 90% a 1 MW load wastes about 111 kW as heat; at 99%, about 10 kW. The difference is about 885,000 kWh a year, before the air conditioning that removes the heat.

05

A 3-level inverter's output already looks like a staircase: the filter only has to smooth half the step of a 2-level one.

06

AEC is the UPS brand of the AEC Group, which began with switchboards and motor control in 1968; the group's transformers today reach 36 kV and 15,000 kVA.

Films

Power electronics on film.

Our own films, with sound: press play.

Why a 3-level sine wave is cleanerTwo levels against three, drawn live.AEC · 0:13
Where our R&D goesSilicon carbide, three-level IGBT, modular N+X, LiFePO4.AEC · 0:13

Power electronics

Questions people ask

What is the difference between an IGBT and a MOSFET?

Both are driven by a voltage on the gate. A MOSFET conducts like a resistor and switches faster, but its resistance rises steeply with the voltage it blocks; an IGBT conducts like a bipolar transistor, with low losses at high voltage and current, which is why it is the switch of a three-phase UPS's power stages.

What does a 3-level inverter change?

Each switch blocks half the DC bus voltage and the output has three levels instead of two: lower switching losses, half the ripple and a smaller filter. Double conversion goes from the typical 93–95% of 2-level designs to 96–97%.

Why does silicon carbide raise UPS efficiency?

SiC has a band gap of 3.26 eV and a critical field about ten times silicon's: it blocks high voltage in a thin chip, conducts with little resistance and switches fast with low losses. Double-conversion UPS with SiC reach 98–99%.

Are thyristors still used in UPS?

Yes, where a rugged switch at line frequency is needed: the static bypass of every online UPS is a pair of thyristors in anti-parallel, which moves the load to the utility power without a break.

Talk to an engineer

Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.