Technology · isolation

Isolation transformers in UPS systems, explained

An isolation transformer separates a UPS output from its input: no conductor runs straight through. It gives the load its own neutral and ground, changes the voltage when needed and filters part of the noise. Most modern UPS are built without one and add it only where the installation needs it.

What it does

Four jobs, one transformer.

  • Galvanic isolation. Input and output share no conductor; energy crosses only through the magnetic core.
  • A new neutral and ground bond. The secondary makes a separately derived system, grounded where it is installed (NFPA 70, Article 250.30).
  • Voltage change. 480 V in, 208/120 V out, or 208 V in, 120/240 V out, with the ratio of the windings.
  • Less common-mode noise. Disturbances between the lines and ground are kept away from the load, which matters to some medical, laboratory and audio equipment.

Transformer-based or transformerless

Why most UPS have none inside.

A transformer adds weight, floor space and losses. Modern online double-conversion UPS make their output with the inverter alone and are more efficient without one; an APC white paper on the subject (Schneider Electric, “The role of isolation transformers in data center UPS systems”) concludes that a transformer belongs where the installation needs it, not in every UPS.

In the AEC range, the split-phase FERRUS SP and FERRUS SP RT carry an integrated isolation transformer; for the others, a transformer is added where the installation needs one.

When you need one

Four cases, and the AEC answer.

If none of these applies, a transformerless UPS is the efficient choice.

Your installationWhy a transformerWith AEC
120/240 V split-phase loadsTwo 120 V legs and a neutral, isolated from the supplyFERRUS SP and FERRUS SP RT: integrated isolation transformer, 6 to 20 kVA
480 V supply, 208/120 V loadsA different voltage and a neutral at the loadINFINITE (480 V 3-wire) or CIRRO (480 V 4-wire) with a transformer after the UPS, or a 208 V UPS on a 208 V panel
3-wire supply, loads that need a neutralThe supply has no neutral to pass onA transformer after the UPS makes one; our engineers size it with the UPS
Medical or laboratory equipmentLow leakage current and a separately derived system, as the equipment or the engineer requiresTell us the equipment: we answer with the UPS and the isolation it needs

More on supplies: 208 V or 480 V · three-phase UPS · 120/240 V split-phase UPS · UPS for hospitals and clinics

How does a transformer make a separately derived system?

In a transformerless UPS the output neutral is the input neutral: the neutral-to-ground bond is upstream, at the service or at the transformer that feeds the building. With an isolation transformer the secondary is a new source. Under NEC 250.30 its neutral is bonded to ground once, at the transformer or at the first disconnecting means after it, through a system bonding jumper, and a grounding electrode conductor ties it to the building's grounding electrode system. A ground fault on the secondary then returns through that bond, and the secondary's overcurrent devices clear it.

Where does the transformer go?

After the UPS, often inside a power distribution unit near the racks: it isolates the load from the inverter and from the bypass alike, steps 480 V down to 208/120 V and makes the neutral for the 120 V loads. This is the usual place. On the bypass line, when the bypass is fed at another voltage, or the design wants it isolated too. On the rectifier input alone it isolates the rectifier, but the bypass still ties the load to the supply: to isolate the load on every path, the transformer goes after the UPS or feeds both inputs.

How do you size a transformer after a UPS?

  • Rating: at least the UPS's output kVA, so the transformer never limits the UPS.
  • Harmonics: IT power supplies draw non-sinusoidal current; a K-rated transformer, as most data-center PDUs use, carries the extra heating.
  • Inrush: a transformer draws many times its rated current for a few cycles when it is energized. Through the inverter that can pass the UPS's overload limits and send it to bypass: energize large transformers from the bypass or with a soft start, as the commissioning engineer plans.
  • Losses and heat: they add to the UPS's own, in the system's efficiency and in the cooling.
  • Protection: primary and secondary overcurrent devices under NEC 450.3, secondary conductors under 240.21(C).

FERRUS SP: the transformer inside

FERRUS SP (tower, 6–20 kVA) and FERRUS SP RT (rack or tower, 6–10 kVA) give 120/240 V split phase: two 120 V legs and a neutral, for panels with both 120 V and 240 V loads. Both carry the isolation transformer inside, at up to 93% efficiency, and the tower adds a manual maintenance bypass. For more runtime, BB4US cabinets (192 Vdc) extend the 6–10 kVA towers.

Mistakes to avoid

  • Two neutral-to-ground bonds. Bonding the secondary neutral at the transformer and again at a panel downstream puts neutral current on the grounding conductors (NEC 250.6, 250.30).
  • No bond at all. A floating secondary neutral lets the 120 V legs drift with the load, and a ground fault may not clear.
  • Forgetting the bypass. If the transformer is on one path only, the load loses its isolation, or its voltage, when the UPS goes to bypass.

Questions

Questions people ask

What does an isolation transformer do in a UPS?

It separates the output from the input galvanically: no conductor runs straight through. That lets the output have its own neutral and ground bond (a separately derived system), change the voltage (480 V in, 208/120 V out), and keeps much of the common-mode noise of the supply away from the load.

Do I need a UPS with an isolation transformer?

Not for most IT loads on a 4-wire supply: modern online UPS are transformerless and more efficient. You need one when the load needs a neutral the supply does not have, a different voltage than the supply, a separately derived system by design, or very low leakage current (some medical and laboratory equipment).

Transformer-based or transformerless UPS?

Transformerless UPS are smaller, lighter and more efficient; transformer-based UPS isolate and can change voltage inside the cabinet. Today most large UPS are transformerless and a transformer is added outside, only where the installation needs one.

Which AEC UPS has an isolation transformer?

FERRUS SP and FERRUS SP RT, the 120/240 V split-phase UPS, have an integrated isolation transformer, according to the 2026 catalog. The three-phase series are transformerless.

Can a 480 V UPS feed 208/120 V loads?

Yes, through a transformer after the UPS (often inside a power distribution unit). A 3-wire 480 V UPS such as INFINITE has no neutral on its output, so 120 V loads always need one; a 4-wire 480 V UPS such as CIRRO carries the neutral but still needs a transformer to reach 208/120 V.

Not sure you need one?

Send us the one-line or the supply and the loads: our engineers say whether a transformer is needed and where it goes.