Technology · architecture

Modular UPS and N+X redundancy, explained

A modular UPS is a frame of slots and a set of identical power modules: the modules share the load, any one can be swapped with the system running, and one spare module more than the load needs keeps the load on the inverter if a module stops.

Frames and modules

Every modular frame in the catalog.

Modules are hot-swappable and kVA = kW (unity power factor). Modules of different series are not interchangeable.

FrameModuleSlotsFrame powerBatteryNotes
RADIANT 15-9015 kVA690 kVAVRLA, external bank
RADIANT-IB20 kVA5100 kVAVRLA inside, up to 240 × 12 V 9 AhNot interchangeable with the CIRRO-IB module (CIRIB-PWR-30).
CIRRO-IB30 kVA5150 kVAVRLA inside, up to 240 × 12 V 9 AhNot interchangeable with the RADIANT-IB module (RADIB-PWR-20).
CIRRO 36060 kVA6360 kVAExternal
CIRRO 600100 kVA6600 kVAExternalTakes up to 6 × 100 kVA hot-swappable power modules. 480/277 V three-phase, 4-wire. Cabinet 31.5 × 39.4 × 78.7 in (800 × 1000 × 2,000 mm), 893 lb (405 kg). Standard: RS232, USB, RS485, intelligent slot, dry contacts, battery cold start.
CIRRO 800100 kVA8800 kVAExternalTakes up to 8 × 100 kVA hot-swappable power modules. 480/277 V three-phase, 4-wire. Cabinet 31.5 × 39.4 × 78.7 in (800 × 1000 × 2,000 mm), 1,074 lb (487 kg). Standard: RS232, USB, RS485, intelligent slot, dry contacts, battery cold start.
CIRRO 1200100 kVA121,200 kVAExternalTakes up to 12 × 100 kVA hot-swappable power modules. 480/277 V three-phase, 4-wire. Cabinet 47.2 × 43.3 × 78.7 in (1200 × 1100 × 2,000 mm), 1,376 lb (624 kg). Standard: RS232, USB, RS485, intelligent slot, dry contacts, battery cold start.
CIRRO 1600100 kVA161,600 kVAExternalTakes up to 16 × 100 kVA hot-swappable power modules. 480/277 V three-phase, 4-wire. Cabinet 63 × 39.4 × 78.7 in (1600 × 1000 × 2,000 mm), 2,138 lb (970 kg). Standard: RS232, USB, RS485, intelligent slot, dry contacts, battery cold start.
INFINITE100 kVA2 + 1100 / 200 kVAExternal, VRLA or lithiumSiC modules; up to three 200 kVA frames in parallel: 600 kVA in the catalog
INFINITE 1.5MW125 kVA121,500 kVAExternal, L6 lithium or lead-acidSiC modules; 750–1,500 kVA in one frame, up to 8 frames in parallel

How do the modules share the load?

The modules' outputs are paralleled on the frame's output bus, and their controls split the load equally between them, so every module runs at the same share of its rating. At part load the modules not needed can stand by in turn (module sleep, in the RADIANT-IB user manual): fewer modules run closer to their best efficiency, the rotation ages them evenly, and they wake as the load grows.

How many modules do you need?

The RADIANT-IB manual gives the method, and it holds for any frame:

  1. Add up the kW the loads draw, from their data sheets or from measurements.
  2. Divide by the module rating in kW and round up: that is N.
  3. Keep the load at or below about 80 % of what is left with one module out, for start-up currents and growth.
  4. Add one module for N+1, or more for N+X.

The manual's example is 55 kW on 20 kW RADIANT-IB modules: 3 modules for the load, 4 with the 80 % margin, 5 for N+1, a full 100 kVA cabinet. At 480 V, 420 kW on 100 kVA CIRRO modules: 5 carry the load (N). Plain N+1 is 6, a CIR600-6X100, each module at 70 % in normal running and 84 % with one module out, as in the N+1 guide. Keeping the manual's 80 % margin with one module out takes 7, a CIR800-7X100, in an 800 kVA frame with a slot left for growth.

RADIANT, closedRADIANT opened: the power modules in their bays

RADIANT, closed

Hot-swap

Open it, pull a module

Each module carries its own rectifier, inverter and control; the frame holds the static bypass, the breakers and the display. Pulling a module out leaves the others sharing the load, so service happens with the load on the inverter, as long as the remaining modules can carry it.

N + X

Redundancy you can count

N modules carry the load; X are spare. With 60 kVA of load on 15 kVA modules, N is 4: fit 5 and any one module can fail (N+1), fit 6 and two can (N+2). The display shows the state.

CIRRO 600–1600, closedCIRRO opened: 100 kVA power modules stacked in the frame

CIRRO 600–1600, closed

N+1 in one frame, or 2N?

N+1 covers a power module: one can fail or be pulled and the load stays on the inverter. It does not cover what the modules share: the frame's static bypass, its output bus, its breakers and the feed that comes in. 2N does: two complete systems, each able to carry the whole load, on separate feeds to dual-corded loads. The two combine, with N+1 modules inside each side of a 2N design; N+1 redundancy compares the options.

When do frames run in parallel?

When one frame is not enough, for power or for redundancy at frame level: up to three RADIANT-IB or CIRRO-IB cabinets, and the INFINITE and INFINITE 1.5MW frames as the table gives them. On RADIANT-IB the parallel function is an option to confirm with the order. The manual's rules hold for any parallel system:

  • Frames of the same rating, fed from the same bypass source, with main and bypass inputs on the same neutral.
  • Input and output cables of the same length and size on every frame, so the load shares equally in bypass mode, into a common output bus.
  • An external maintenance bypass for the whole system, so each frame can be isolated.
  • Every frame's EPO on the same remote switch.

Why wire the frame for its final size?

Size the frame's breakers and cables for the full frame from the start, so modules can be added later without rewiring. For a 100 kVA RADIANT-IB at 208 V the manual gives a main input current of 348 A and a 450 A external input breaker, whatever the number of modules on day one. The battery follows the same rule: an external bank must carry the frame's final power, or the added modules arrive without their runtime. The CIRRO 1600 frame has no breakers inside at all: external switchgear is required.

What does a hot-swap look like on site?

From the RADIANT-IB manual: check that the remaining modules can carry the load, or transfer to bypass first; take the module out of the system from the panel; after 10 minutes remove its screws and pull it out, two people lifting; push the new one in and it joins the system by itself. Insert modules one at a time, at least 10 s apart, and remove them from the top down so the cabinet cannot tip. The catalog weights: 30.5 lb (13.9 kg) for a 15 kVA RADIANT module, 44 lb (20 kg) for a 20 kVA RADIANT-IB module, 52 lb (23.6 kg) for a 30 kVA CIRRO-IB module, 77 lb (34.9 kg) for a 60 kVA CIRRO module and 103.6 lb (47 kg) for a 100 kVA CIRRO module.

Mistakes to avoid

  • Counting the spare. A five-module frame set up as N+1 is a four-module UPS: the rating that counts is the one with a module out.
  • Not telling the UPS. Set the number of redundant modules on the panel, so it raises an alarm when redundancy is lost.
  • Open slots. Free slots stay closed with their covers until modules go in.
  • The smallest frame that fits today. A frame full on day one has no room for N+1 or growth without a second frame in parallel.

Which modular series fits your supply?

The supply narrows the table first. On a 208 V panel: RADIANT or RADIANT-IB. On 480/277 V 4-wire: CIRRO-IB or CIRRO. On 480 V 3-wire, with no neutral: INFINITE or INFINITE 1.5MW. 208 V or 480 V explains the choice, and the sizing tool starts from your load and supply.

INFINITE

Inside the module.

From the INFINITE catalog: front and rear of the 100 kVA SiC module. Click to enlarge.

INFINITE module, frontFront panel of the 100 kVA power module.
INFINITE module, rearRear connections of the 100 kVA power module.
Circuit topologyThe SiC power stage of the module.

Talk to an engineer

Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.