What does one L6 module give?
| L6-MOD-50LI | Value |
|---|---|
| Cells | 18 × 3.2 V LiFePO4, 57.6 V |
| Capacity, energy | 50 Ah, 2.88 kWh nominal |
| Output (its own DC/DC converter) | 10 kW |
| Rating used for runtime | 10 kW for 15 minutes, about 2.5 kWh to the load |
| Size, weight | 8.8 × 26.2 × 6.0 in, 81.6 lb |
| Per cabinet | up to 20 modules: 58 kWh nominal, 200 kW |
Two numbers set the count, the 10 kW and the 2.5 kWh. Dividing the energy you need by the nominal 2.88 kWh gives too few modules: a module delivers about 2.5 kWh in a 15-minute discharge. Lithium LiFePO4 explains why.
How many modules for your load and minutes?
The L6 manual gives the rule: modules = the larger of load kW ÷ 10 and load kWh ÷ 2.5, rounded up, with the kWh at the load being kW × minutes ÷ 60. Then 20 modules to a cabinet.
| Load | 15 min: modules | Cabinets | 30 min: modules | Cabinets |
|---|---|---|---|---|
| 50 kW | 5 | 1 | 10 | 1 |
| 100 kW | 10 | 1 | 20 | 1 |
| 150 kW | 15 | 1 | 30 | 2 |
| 200 kW | 20 | 1 | 40 | 2 |
| 300 kW | 30 | 2 | 60 | 3 |
| 400 kW | 40 | 2 | 80 | 4 |
| 600 kW | 60 | 3 | 120 | 6 |
Below 15 minutes the power count wins: 200 kW for 10 minutes is still 20 modules, because 20 modules are what deliver 200 kW. A cabinet's 20 modules are therefore also a ceiling of 200 kW: a 400 kW load cannot run on one cabinet, however short the runtime asked.
Which INFINITE bundles does the catalog list?
The 2026 catalog sells the INFINITE with its L6 cabinets as one model. Their runtimes follow the same 10 kW rating, at the start of battery life:
| Model | L6 modules | At full load | At half load | Weight |
|---|---|---|---|---|
| INF-100+L6-CAB-10x50LI | 10 | 15 min at 100 kW | 30 min | 1,808 lb |
| INF-100+L6-CAB-20x50LI | 20 | 30 min at 100 kW | 60 min | 2,623.8 lb |
| INF-200+L6-CAB-20x50LI | 20 | 15 min at 200 kW | 30 min | 2,762.9 lb |
| INF-400+2xL6-CAB-20x50LI | 40 | 15 min at 400 kW | 30 min | 5,525.7 lb |
| INF-600+3xL6-CAB-20x50LI | 60 | 15 min at 600 kW | 30 min | 8,597.2 lb |
The N+1 versions, INF-100+1 and INF-200+1 with one 20-module cabinet, keep the same minutes: the spare power module adds no energy. INFINITE 1.5MW works with 4, 6 or 8 L6 cabinets, 80, 120 or 160 modules: 4 cabinets carry up to 800 kW and 6 up to 1,200 kW.
How does the battery grow later?
Module by module, with the load on. The INF-100+L6-CAB-10x50LI ships its cabinet half full: ten more 50 Ah modules in the same cabinet double its runtime, from 15 to 30 minutes at 100 kW, with no new floor space. New modules work beside old ones, each on its own DC/DC converter, and cabinets share current within 3 %. Past one cabinet, up to 15 cabinets form one system: a master with the touchscreen and up to 14 slaves.
What does the room need?
| Item | L6 cabinet |
|---|---|
| Size (W × D × H) | 23.6 × 33.5 × 78.7 in (600 × 850 × 2000 mm) |
| Weight | 2,171.6 lb with 20 modules, 1,355.8 lb with 10, 540 lb empty |
| Floor load, full | about 395 lb/ft² on its 5.5 ft² |
| Clearances | 31.5 in in front and behind, 19.7 in above; cabinets bolt side by side |
| Floor | concrete or another non-combustible floor |
| Cables | from the top only |
| Temperature | 32–104 °F, best 68–86 °F (20–30 °C) |
- Working space. Keep the NEC 110.26 working space in front of the cabinets as well as the 31.5 in clearance: the breakers and the modules are behind the front door.
- Delivery. The cabinet travels empty, 540 lb, and each module in its own carton. A module is 81.6 lb: two people, and a lifting platform above 3.3 ft.
- DC cables. With the INFINITE, connect +, − and PE and leave the N busbar unconnected: the INFINITE is a 3-wire UPS. The manual sizes + and − at 2 × 250 kcmil each for runs up to 16 ft; for longer runs or loads near the cabinet's rating, ask AEC.
- Several cabinets. One cabinet wires straight to the INFINITE; several go through the L6-COMBINER, 15.7 × 33.5 × 78.7 in and 308.6 lb, for up to 8 cabinets and 4,000 A.
What mistakes come up most?
- Dividing by 2.88 kWh. At 15 minutes a module gives about 2.5 kWh: 200 kW for 15 minutes is 20 modules, not 18.
- One cabinet for a large load. A cabinet delivers at most 200 kW, whatever the minutes.
- Forgetting the floor. A full cabinet loads the floor at about 395 lb/ft²: check the slab, or the stand on a raised floor.
- Sizing for the UPS today. If the INFINITE will gain a module or a frame, plan the free slots and the cable route for the final kW.
For the choice between lithium and lead-acid, read lithium vs VRLA. The L6 lithium page has the module and cabinet in detail, and the room fit tool places the cabinets beside the UPS in your room.