INFINITE · 480V three-phase UPS
INF-400+2xL6-CAB-20x50LI INFINITE 400 kVA, 480V three-phase UPS
The AEC INFINITE INF-400+2xL6-CAB-20x50LI is a 400 kVA / 400 kW online double-conversion UPS for 480 V three-phase loads, built on four 100 kVA power modules, with two external L6 lithium cabinets of 20 LiFePO4 modules: 15 minutes at full load, 30 at half load. Kept at 80 % of its rating, it carries loads up to 320 kW.
3-wire · Delta480 V 3-wire, delta: three phases and ground, no neutral
Series picture. The INF-400 is 2 × 200 kVA frames.
The same on every INFINITE:Open the INFINITE: modules and door, from the catalog's photosThe INFINITE display
Runtime
INFINITE 400 kVA · 2 L6 cabinets, 40 lithium modules at your load.
The same chart as the INFINITE page: this model in bold, the other set-ups faded behind it to compare. 2026 catalog, new batteries.
At 50 % of the rating
INFINITE 400 kVA
This model 2 L6 cabinets, 40 lithium modules30 minINFINITE 100 kVA N+1
1 L6 cabinet, 20 lithium modules60 minINFINITE 100 kVA
half L6 cabinet, 10 modules30 min1 L6 cabinet, 20 lithium modules60 minINFINITE 200 kVA N+1
1 L6 cabinet, 20 lithium modules30 minINFINITE 200 kVA
1 L6 cabinet, 20 lithium modules30 minINFINITE 600 kVA
3 L6 cabinets, 60 lithium modules30 minTable: this model at 25, 50, 75 and 100 % load
| Model | 25% load | 50% load | 75% load | 100% load |
|---|---|---|---|---|
| INFINITE 400 kVA · 2 L6 cabinets, 40 lithium modulesINF-400+2xL6-CAB-20x50LI | 60 min | 30 min | 20 min | 15 min |
Load by load
The INF-400+2xL6-CAB-20x50LI at 25, 50, 75 and 100 % load.
Its 400 kW rating in four steps, worked out from its own catalog figures.
| Load | On battery | Output current per phase, at 480 V | Load on each of its 4 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|---|
| 25 % of the INF-400+2xL6-CAB-20x50LI, 100 kW | 60 min on battery | 120 A per phase | 25 % on each module | 96.9 % efficient | 3.2 kW of heat | 10,920 BTU/h to cool |
| 50 % of the INF-400+2xL6-CAB-20x50LI, 200 kW | 30 min on battery | 241 A per phase | 50 % on each module | 97.3 % efficient | 5.5 kW of heat | 18,940 BTU/h to cool |
| 75 % of the INF-400+2xL6-CAB-20x50LI, 300 kW | 20 min on battery | 361 A per phase | 75 % on each module | 97.3 % efficient | 8.3 kW of heat | 28,400 BTU/h to cool |
| 100 % of the INF-400+2xL6-CAB-20x50LI, 400 kW | 15 min on battery | 481 A per phase | 100 % on each module | 97.3 % efficient | 11 kW of heat | 37,870 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Runtime from the rating of its 50 Ah lithium modules, 10 kW for 15 minutes each, at the start of battery life.
Efficiency
How efficient is the INF-400+2xL6-CAB-20x50LI at your load?
The INF-400+2xL6-CAB-20x50LI in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
Sizing
What load fits the INF-400+2xL6-CAB-20x50LI?
At 80 % load the INF-400+2xL6-CAB-20x50LI's runtime table gives about 19 min on battery, with new batteries.
At 200 kW, half its rating, it runs 30 min.
At the same 200 kW, the other INFINITE models:
- INF-600+3xL6-CAB-20x50LI: 45.6 min on battery, at 33 % of its rating.
Past the 80 % headroom at the same 200 kW:
- INF-200: 100 % of its rating.
- INF-200+1: 100 % of its rating.
- INF-200+1+L6-CAB-20x50LI: 100 % of its rating.
- INF-200+L6-CAB-20x50LI: 100 % of its rating.
Its two L6 cabinets hold 40 modules of 50 Ah, each rated 10 kW for 15 minutes (2.5 kWh usable in that discharge, of 2.88 kWh nominal): 100 kWh usable in all and up to 400 kW of discharge, so the INF-400+2xL6-CAB-20x50LI's minutes at any load are 100 kWh divided by the load.
With its cabinets, the INF-400+2xL6-CAB-20x50LI weighs 5,526 lb, against 1,183 lb for the INF-400 frame alone: plan the floor for the batteries too.
From the 2026 catalog
What is the INF-400+2xL6-CAB-20x50LI?
The code INF-400+2xL6-CAB-20x50LI orders these catalog items, shipped in 44 cartons:
- 1 × INF-400: 400 kVA UPS, 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm), 1,182.5 lb (536.4 kg)
- 2 × L6-CAB-20x50LI: L6 lithium cabinet with 20 LiFePO4 modules of 50 Ah, 23.6 × 33.5 × 78.7 in (599 × 851 × 1,999 mm), 2,171.6 lb (985 kg) each
Floor area of its 4 cabinets, before clearances: 23.9 ft² (2.22 m²).
- Architecture: 4 × 100 kVA hot-swappable power modules in 2 × 200 kVA frames.
- Bundled with 2 × L6-CAB-20X50LI lithium battery cabinets (20 × LiFePO4 50 Ah modules each; integrated BMS, smoke detector).
Its other catalog lines are those of the INF-100, of the same series: see them on its page.
Installation
The INF-400+2xL6-CAB-20x50LI takes the clearances, wiring, cable entry and breakers of every INFINITE model, from its AEC US user manual: see them on the INFINITE page.
Place the INF-400+2xL6-CAB-20x50LI in your room, to the inch, with Room fit
Datasheet
INF-400+2xL6-CAB-20x50LI datasheet.
The INF-400+2xL6-CAB-20x50LI in the AEC 2026 catalog, figure by figure. Compare it with every INFINITE model.
| Parameter | INF-400+2xL6-CAB-20x50LI |
|---|---|
| Power | |
| Rated power (kVA) | 400 |
| Active power (kW) | 400 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 3-wire (delta) |
| Topology | Online double conversion, modular |
| Efficiency, up to | 97.3% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | Lithium LiFePO4 |
| Battery configuration | External L6 lithium cabinets |
| Mechanical | |
| Form factor | Modular |
| Net weight | 5,525.7 lb (2,506.4 kg) |
| Common to every INFINITE | |
| Battery, INF-400+2xL6-CAB-20x50LI | external, two AEC L6 lithium cabinets of 20 × 50 Ah modules, included in the set |
| Technology, display, communications, warranty | As on the INF-100 datasheet |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
The INFINITE manuals and catalogs cover every model of the series, this one included: download them from the INFINITE page.
Quick answers
INF-400+2xL6-CAB-20x50LI: what people ask
How long does the INF-400+2xL6-CAB-20x50LI run on battery?
15 min at 100 % load (400 kW), 30 min at 50 % load (200 kW), 2 h 30 min at 10 % load (40 kW). They come from the rating of its 50 Ah lithium modules, 10 kW for 15 minutes each, at the start of battery life. These minutes divide the modules' energy by the load; a battery gives less in a fast discharge, so take the light-load figures as an upper bound, and the INF-400+2xL6-CAB-20x50LI chart above gives the minutes at any load in between.
What is the output current of the INF-400+2xL6-CAB-20x50LI?
481.1 A per phase at full load: 400 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the INF-400+2xL6-CAB-20x50LI from its installation manual and the local electrical code, not from this figure alone.
How much heat does the INF-400+2xL6-CAB-20x50LI give off?
About 11 kW, 37,870 BTU/h, at full load, where it is 97.3% efficient. Plan the room's cooling for a little more than that: the INF-400+2xL6-CAB-20x50LI is less efficient at part load and while its battery recharges.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
INFINITE
Other INFINITE models
By power, the INF-400+2xL6-CAB-20x50LI is number 3 of 4 in the INFINITE series, which runs from 100 to 600 kVA. One size down are the INF-200, INF-200+1, INF-200+1+L6-CAB-20x50LI and INF-200+L6-CAB-20x50LI, all 200 kVA less. One size up are the INF-600 and INF-600+3xL6-CAB-20x50LI, all 200 kVA more. The same 400 kVA also comes as INF-400 (external VRLA bank or L6 lithium cabinets, 4,343 lb lighter); the INF-400+2xL6-CAB-20x50LI has external L6 lithium cabinets.
Every INFINITE model side by side (13)
| Model | Power | Power against this model | Net weight | Weight against this model | Battery configuration |
|---|---|---|---|---|---|
| INF-100 | 100 kVA | 300 kVA less | 452 lb | 5,074 lb lighter | External VRLA bank or L6 lithium cabinets |
| INF-100+1 | 100 kVA | 300 kVA less | 571 lb | 4,954 lb lighter | External VRLA bank or L6 lithium cabinets |
| INF-100+1+L6-CAB-20x50LI | 100 kVA | 300 kVA less | 2,743 lb | 2,783 lb lighter | External L6 lithium cabinets |
| INF-100+L6-CAB-10x50LI | 100 kVA | 300 kVA less | 1,808 lb | 3,718 lb lighter | External L6 lithium cabinets |
| INF-100+L6-CAB-20x50LI | 100 kVA | 300 kVA less | 2,624 lb | 2,902 lb lighter | External L6 lithium cabinets |
| INF-200 | 200 kVA | 200 kVA less | 591 lb | 4,934 lb lighter | External VRLA bank or L6 lithium cabinets |
| INF-200+1 | 200 kVA | 200 kVA less | 710 lb | 4,815 lb lighter | External VRLA bank or L6 lithium cabinets |
| INF-200+1+L6-CAB-20x50LI | 200 kVA | 200 kVA less | 2,882 lb | 2,644 lb lighter | External L6 lithium cabinets |
| INF-200+L6-CAB-20x50LI | 200 kVA | 200 kVA less | 2,763 lb | 2,763 lb lighter | External L6 lithium cabinets |
| INF-400 | 400 kVA | the same power | 1,183 lb | 4,343 lb lighter | External VRLA bank or L6 lithium cabinets |
| INF-400+2xL6-CAB-20x50LI | 400 kVA | this page | 5,526 lb | this page | External L6 lithium cabinets |
| INF-600 | 600 kVA | 200 kVA more | 1,774 lb | 3,752 lb lighter | External VRLA bank or L6 lithium cabinets |
| INF-600+3xL6-CAB-20x50LI | 600 kVA | 200 kVA more | 8,597 lb | 3,072 lb heavier | External L6 lithium cabinets |
The INF-400+2xL6-CAB-20x50LI for your project
Send the load, the voltage and the minutes you need from the INF-400+2xL6-CAB-20x50LI. We reply with the configuration, the batteries and the lead time.