Guide

Growing a modular UPS: frames, modules and N+1

A modular UPS grows by filling the empty slots of its frame, so the frame bought on day one sets how far the system can grow with N+1 intact. An AEC CIRRO 800 frame can start with three 100 kVA modules and grow to eight in the same 31.5 × 39.4 in footprint; a CIRRO 600 frame of the same size stops at six.

Data center, black-and-white photograph

How far does each AEC frame grow?

Every modular frame in the 2026 catalog, with the module it takes, its slots and its weight empty and full. Modules of different series do not fit each other's frames.

FrameModuleSlotsGrowsSize (W × D × H)Weight, empty → full
CIRRO 36060 kVA660 → 360 kVA23.6 × 39.4 × 78.7 in559.4 → 1,088.4 lb
CIRRO 600100 kVA6100 → 600 kVA31.5 × 39.4 × 78.7 in892.9 → 1,514.5 lb
CIRRO 800100 kVA8700 → 800 kVA as catalog models; any count as frame + modules31.5 × 39.4 × 78.7 in1,073.6 → 1,902.4 lb
CIRRO 1200100 kVA12900 → 1,200 kVA47.2 × 43.3 × 78.7 in1,375.7 → 2,618.9 lb
CIRRO 1600100 kVA161,300 → 1,600 kVA63 × 39.4 × 78.7 in2,138.5 → 3,796.1 lb
INFINITE 100100 kVA1 + 1100 kVA, then N+123.6 × 39.4 × 81.4 in287.9 → 571.3 lb
INFINITE 200100 kVA2 + 1200 kVA, then N+1; up to 3 frames, 600 kVA23.6 × 39.4 × 81.4 in308 → 710.4 lb
INFINITE 1.5MW125 kVA12750 → 1,500 kVA70.9 × 39.4 × 78.7 in4,674 → 6,170.7 lb

Two pairs of frames share one cabinet. The CIRRO 600 and 800 are the same 31.5 × 39.4 × 78.7 in box with 6 or 8 slots; the INFINITE 100 and 200 are the same 23.6 × 39.4 × 81.4 in box with 1 + 1 or 2 + 1. Choosing the larger of each pair costs no floor space, about 181 lb more on the CIRRO and 20 lb on the INFINITE, and adds two slots or one.

The frames also differ in what they bring. The CIRRO 600 and 800 have four breakers inside (main input, output, bypass input and maintenance bypass); the CIRRO 1200 and 1600 have none, so the switchgear outside must be planned with the room. Modular UPS and N+X explains how the modules share the load and how a hot swap is done.

At what load does N+1 end, module by module?

N+1 holds as long as the load fits on all the modules but one. For 100 kVA CIRRO modules, the load where it ends is (modules − 1) × 100 kW. The RADIANT-IB manual's sizing method, which holds for any frame, also keeps the load at or below 80 % of what is left with one module out, so that start-up currents and growth have room:

100 kVA modules installedN+1 holds up toWith the 80 % marginFits in
2100 kW80 kWCIRRO 600, 800, 1200, 1600
3200 kW160 kWCIRRO 600, 800, 1200, 1600
4300 kW240 kWCIRRO 600, 800, 1200, 1600
5400 kW320 kWCIRRO 600, 800, 1200, 1600
6500 kW400 kWCIRRO 600 (full), 800, 1200, 1600
7600 kW480 kWCIRRO 800, 1200, 1600
8700 kW560 kWCIRRO 800 (full), 1200, 1600
121,100 kW880 kWCIRRO 1200 (full), 1600
161,500 kW1,200 kWCIRRO 1600 (full)

The CIRRO 360 follows the same rule in 60 kW steps: with all six of its 60 kVA modules, N+1 holds up to 300 kW, or 240 kW with the margin. The INFINITE 1.5MW frame, in 125 kW steps, holds N+1 up to 1,375 kW with all 12 slots filled; the catalog's largest N+1 model, the INF15-1250+1, is 11 modules for 1,250 kW.

Worked example: 150 kW today, 450 kW in five years

A 480 V data hall draws 150 kW now and is planned for 450 kW, with N+1 and the 80 % margin at every step. On 100 kVA CIRRO modules:

  1. Day one, 150 kW. With one module out, the load must fit on modules at 80 %: 150 ÷ 80 = 1.9, so 2 modules carry it and 3 are installed.
  2. Year five, 450 kW. 450 ÷ 80 = 5.6, so 6 modules carry it with one out and 7 are installed: one more slot than the CIRRO 600 has.
  3. The frame. A CIRRO 800 frame with 3 modules on day one, growing to 7, the CIR800-7X100, with one slot still free. It stands in the same footprint as a CIRRO 600.
  4. What a CIRRO 600 would have given. Full at six modules, the CIR600-6X100 keeps plain N+1 at 450 kW, each module at 75 %, but at 90 % with one module out, past the margin. A second frame in parallel would then be the only way on.

Weights grow with the modules: about 103.6 lb per 100 kVA CIRRO module. The CIRRO 800 frame goes from 1,073.6 lb empty to 1,798.8 lb as a CIR800-7X100, about 209 lb/ft² on its 8.6 ft² footprint. Check the floor for the final weight, not the day-one one.

How does an INFINITE system grow?

INFINITE grows in two ways. Inside a frame: the 100 kVA frame takes one module and one spare, the 200 kVA frame two modules and one spare. Then in parallel: up to three 200 kVA frames, 600 kVA, as the INF-600 in the catalog.

  • A load that may pass 100 kW within the life of the UPS belongs on the 200 kVA frame from the start: the 100 kVA frame cannot take a second working module, and the larger frame stands in the same space.
  • The INF-200+1 is the 200 kVA frame full: three modules, N+1 up to 200 kW, 710.4 lb. Past 200 kW the next step is a second frame in parallel.
  • INFINITE 1.5MW grows in one frame of 12 slots, from the INF15-750 with six modules to the INF15-1500 with twelve, and up to 8 frames in parallel.

Does the battery grow with the frame?

Not by itself. Adding modules adds power and no stored energy: the same battery behind more kW gives a shorter runtime. Size the battery bank, its cables and its breaker for the frame's final power, or the added modules arrive without their runtime.

  • CIRRO takes an external VRLA bank on a 480 V DC bus: 40 blocks of 12 V by default, selectable from 30 to 50 on the 600 to 1,600 kVA frames.
  • INFINITE takes lead-acid (30 to 50 blocks) or L6 lithium cabinets, which grow module by module like the UPS; see sizing an L6 lithium battery.
  • INFINITE 1.5MW takes 4, 6 or 8 L6 cabinets, 80, 120 or 160 modules: 4 cabinets carry up to 800 kW, 6 up to 1,200 kW.

Which mistakes stop a frame growing early?

  • Buying the smallest frame that fits today. The CIRRO 600 and 800, and the INFINITE 100 and 200, take the same floor space. The smaller one ends growth two slots or one module sooner.
  • Wiring for day one. Feeders, breakers and battery cables sized for three modules have to be pulled again for seven.
  • Losing N+1 without noticing. Set an alarm at the load where N+1 ends for the modules installed, from the table above, and add a module before it is reached. N+1 redundancy covers what N+1 does and does not protect.
  • Counting on a free slot that is not there. A full frame, like the CIR600-6X100, can only grow by a second frame in parallel.

The UPS sizing tool picks the frame and module count for a load with N+1, and the room fit tool checks the frame, its battery and the clearances in your room.

Questions people ask

How do you add capacity to a modular UPS?

By sliding more power modules into the empty slots of the frame. An AEC CIRRO 800 frame takes up to eight 100 kVA modules; an INFINITE 200 kVA frame takes two working modules and one spare.

When does N+1 end in a modular UPS?

When the load no longer fits on all the modules but one: with 100 kVA modules, at (modules − 1) × 100 kW. With the 80 % margin AEC's sizing method keeps, at 80 % of that: 400 kW for six modules.

Should I buy a bigger modular frame than I need today?

Yes, often: the CIRRO 600 and 800 frames are the same 31.5 × 39.4 × 78.7 in cabinet with six or eight slots, so the larger one keeps two more slots for growth in the same floor space.

Does adding UPS modules increase battery runtime?

No. Modules add power, not minutes. The battery must be sized for the frame's final power, or each module added shortens the runtime at the new load.

Talk to an engineer

Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.