FERRUS RT · 120V single-phase UPS
FER3000RT-6X9 FERRUS RT 3 kVA, 120V single-phase UPS
The AEC FERRUS RT FER3000RT-6X9 is a 3 kVA / 3 kW online double-conversion UPS for 120 V single-phase loads, with internal VRLA batteries. Kept at 80 % of its rating, it carries loads up to 2.4 kW.
Drag to turnLoad by load
The FER3000RT-6X9 at 25, 50, 75 and 100 % load.
Its 3.0 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current, at 120 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the FER3000RT-6X9, 750 W | 6.3 A at the output | 89.2 % efficient | 91 W of heat | 310 BTU/h to cool |
| 50 % of the FER3000RT-6X9, 1.5 kW | 12.5 A at the output | 92.5 % efficient | 122 W of heat | 410 BTU/h to cool |
| 75 % of the FER3000RT-6X9, 2.3 kW | 18.8 A at the output | 93.0 % efficient | 169 W of heat | 580 BTU/h to cool |
| 100 % of the FER3000RT-6X9, 3.0 kW | 25.0 A at the output | 92.8 % efficient | 233 W of heat | 790 BTU/h to cool |
Current = kVA × load ÷ volts.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the FER3000RT-6X9 at your load?
The FER3000RT-6X9 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the FER3000RT-6X9?
- Output: 3,000 VA / 3,000 W (unity power factor, kVA = kW).
- Input: attached cord, NEMA L5-30P plug.
- Battery: internal VRLA, 6 × 12 V 9 Ah (72 Vdc).
- Outlets: 6× NEMA 5-20R + 1× NEMA L5-30R.
The lines every FERRUS RT shares, from technology to warranty, are in the FERRUS RT key facts and in the datasheet below.
Size and floor
How big it is
17.3" W × 22.8" D × 3.4" H (439 × 579 × 86 mm); 61.7 lb (28 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The FER3000RT-6X9 takes the clearances, wiring, cable entry and breakers of every FERRUS RT model, from its AEC US user manual: see them on the FERRUS RT page.
Place the FER3000RT-6X9 in your room, to the inch, with Room fit
Datasheet
FER3000RT-6X9 datasheet.
The FER3000RT-6X9 in the AEC 2026 catalog, figure by figure. Compare it with every FERRUS RT model.
| Parameter | FER3000RT-6X9 |
|---|---|
| Power | |
| Rated power (kVA) | 3 |
| Active power (kW) | 3 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 120 V single-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 93% |
| Battery DC bus | 72 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal |
| Runtime at 50 % load | 10 min |
| Runtime at 100 % load | 4.2 min |
| Mechanical | |
| Form factor | Rack 19" |
| Dimensions W × D × H | 17.3 × 22.8 × 3.4 in (439 × 579 × 86 mm) |
| Net weight | 61.7 lb (28 kg) |
| Footprint | 2.7 ft² (0.25 m²) |
| Common to every FERRUS RT | |
| Technology | 3-level IGBT; 8 A settable charger |
| Display | color LCD |
| Comms | RS-232, EPO and USB, standard |
| Battery, FER3000RT-6X9 | internal VRLA, 6 × 12V 9Ah (72 Vdc) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The FERRUS RT documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
FER3000RT-6X9: what people ask
What is the output current of the FER3000RT-6X9?
25.0 A at 120 V at full load: 3.0 kVA ÷ 120 V. Size the input breaker and the cables of the FER3000RT-6X9 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the FER3000RT-6X9 give off?
About 233 W, 790 BTU/h, at full load, where it is 92.8% efficient. Plan the room's cooling for a little more than that: the FER3000RT-6X9 is less efficient at part load and while its battery recharges.
How many rack units does the FER3000RT-6X9 take?
2U of a 19-inch rack: 3.4 in high, 22.8 in deep. Check the rack's usable depth, rails and rear clearance for the cables.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
FERRUS RT
Other FERRUS RT models
By power, the FER3000RT-6X9 is the largest in the FERRUS RT series, which runs from 1 to 3 kVA. One size down is the FER2000RT-4X9 (1 kVA less and 10 lb lighter).
Every FERRUS RT model side by side (4)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
|---|---|---|---|---|---|
| FER1000RT-2X9 | 1 kVA | 2 kVA less | 42 lb | 20 lb lighter | 10 min at 50 % load |
| FER1500RT-4X9 | 1.5 kVA | 1.5 kVA less | 49 lb | 13 lb lighter | 14.3 min at 50 % load |
| FER2000RT-4X9 | 2 kVA | 1 kVA less | 52 lb | 10 lb lighter | 10 min at 50 % load |
| FER3000RT-6X9 | 3 kVA | this page | 62 lb | this page | 10 min at 50 % load |
The FER3000RT-6X9 for your project
Send the load, the voltage and the minutes you need from the FER3000RT-6X9. We reply with the configuration, the batteries and the lead time.