Guide

UPS amps: output current from kVA at 120, 208 and 480 V

A UPS's full-load output current is its VA divided by the voltage, and by √3 as well on three phase: a 15 kVA UPS at 208 V carries 41.6 A per phase, a 1.5 kVA UPS at 120 V 12.5 A. Electricians and engineers think in amps and a UPS is rated in kVA; converting one to the other takes one line of arithmetic.

Dry-type transformer

What are the formulas?

  • Single phase, 120 V: amps = VA ÷ 120
  • Split phase, 120/240 V: amps on each leg = VA ÷ 240, with the two legs evenly loaded
  • Three phase: amps per phase = VA ÷ (√3 × line-to-line volts); √3 ≈ 1.732
  • From kW: amps = W ÷ (volts × power factor), with √3 added on three phase. At a power factor of 1.0, as on most AEC series, VA and W give the same current.

A single-phase load on two legs of a 208Y/120 V panel runs at 208 V, not 240: a 5 kVA load there draws 24 A (5,000 ÷ 208), against 20.8 A on a 240 V split-phase panel.

What is the full-load output current?

SupplyUPS ratingAmps
120 V1 / 2 / 3 kVA8.3 / 16.7 / 25.0 A
120/240 V split phase6 / 10 / 20 kVA25.0 / 41.7 / 83.3 A per leg
208 V three-phase10 / 20 / 30 kVA27.8 / 55.5 / 83.3 A per phase
208 V three-phase60 / 90 / 100 kVA166.5 / 249.8 / 277.6 A per phase
480 V three-phase30 / 100 / 150 kVA36.1 / 120.3 / 180.4 A per phase
480 V three-phase200 / 500 / 600 kVA240.6 / 601.4 / 721.7 A per phase
480 V three-phase1,000 / 1,200 / 1,600 kVA1,202.8 / 1,443.4 / 1,924.5 A per phase

The same power at 480 V draws 43 % of the current it would draw at 208 V: smaller cables and breakers, the reason large facilities use 480 V. See 208 V or 480 V. The UPS sizing tool also takes the load in amps.

Does the output current size the input breaker?

The input of a UPS draws more than its output: it covers the UPS losses and recharges the battery after an outage. The installation manual gives the input current and the protective devices the maker recommends, and US practice sizes conductors and breakers for continuous loads at 125 % of the load. The final sizes belong to the engineer of record and the local code.

Worked example: the input of a 20 kVA UPS at 208 V

  1. Output. 55.5 A per phase, from the table above.
  2. Losses. At the catalog's 94 % for ETHERNO, the input takes 20 ÷ 0.94 = 21.3 kW at full load. Taking the input power factor as 1, that is 59.1 A per phase.
  3. Charger. After an outage, the charger draws on top of that until the battery is full; the manual gives the maximum input current with the charge included.
  4. Continuous load. 125 % of 59.1 A is 73.8 A, before the charger: the arithmetic points to the next standard breaker size above it, and the manual's recommended device, which counts the charger, is the one to install.

How much can one phase carry?

A third of the rating. A 20 kVA UPS on a 208Y/120 V output gives 6.67 kVA per phase: about 55.5 A at 120 V to neutral, the same current as the line figure. A 120 V load is connected from one phase to neutral and a 208 V single-phase load across two phases, so a room of single-phase racks must be spread over the three phases. Put 10 kVA of 120 V racks on one phase of that UPS and the phase is overloaded at 150 % while the UPS as a whole sits at 50 %. Balance the circuits on the panel, and read the load per phase on the display, not only the total.

Worked example: a megawatt at 480 V

An INF15-1500 at full load delivers 1,500 kVA at 480 V: 1,804 A per phase. At 97.5 % efficiency and an input power factor above 0.99, its input takes about 1,539 kW, about 1,850 A per phase at 480 V. Its input accepts 408 to 552 V at full load, and the current rises as the voltage falls: at 408 V the same power takes about 2,180 A. Feeders and the generator are sized for the low end of the voltage window, not the nominal.

What about the neutral?

On a 4-wire 208Y/120 V or 480Y/277 V output, balanced three-phase loads leave the neutral almost empty. Single-phase IT loads do not: their power supplies draw harmonic currents, and the third harmonics of the three phases add in the neutral instead of cancelling, so it can carry as much as a phase or more. The NEC counts the neutral as a current-carrying conductor in a 4-wire wye circuit where most of the load is nonlinear (NEC 310.15(E)), and many designers size it larger than the phases. A 3-wire UPS such as INFINITE has no output neutral at all; the transformer downstream creates one.

What current flows from the battery?

The battery current is the load's power divided by the DC bus voltage, plus the inverter's losses. An ETHERNO at 20 kW on its 240 V DC bus draws over 83 A from its lithium modules (20,000 ÷ 240), and more as the voltage falls during the discharge. For an external battery cabinet, that current sets the size of the DC cables and of the battery breaker. On long runs between a three-phase UPS and its bank, AEC's battery compensation kit corrects the string voltage the cable drops.

What mistakes come up in the arithmetic?

  • Using 220 or 240 V for a 208 V three-phase supply, or 1.732 with the line-to-neutral voltage.
  • Reading the per-phase current as the total, or multiplying it by three.
  • Sizing the input from the output current.
  • Forgetting the neutral on a 4-wire system full of single-phase IT loads.

Where is the current of each model?

Every AEC model page answers "What is the output current?" for its own rating and supply, under Quick answers. Start from the list of all models.

Questions people ask

How many amps is a 20 kVA UPS at 208 V?

55.5 A per phase at full load: 20,000 VA ÷ (1.732 × 208 V).

How many amps does a 3 kVA UPS draw at 120 V?

25 A at full output: 3,000 VA ÷ 120 V. The input current is higher while the battery recharges.

How do I convert kVA to amps for a three-phase UPS?

Amps per phase = VA ÷ (√3 × line-to-line voltage). At 480 V, a 500 kVA UPS carries 601.4 A per phase.

Can I size the UPS breaker from the output current?

No. The input current is higher (losses and battery charging), and US practice sizes continuous loads at 125 %. Use the installation manual and the engineer of record.

Talk to an engineer

Tell us the load, the voltage and the minutes you need. We answer with the model and the batteries that fit.