FERRUS SP RT · 120/240V split-phase UPS

FERSPRT10000-16X9 FERRUS SP RT 10 kVA, 120/240V split-phase UPS

VRLA10 kVAOnline double conversion

The AEC FERRUS SP RT FERSPRT10000-16X9 is a 10 kVA / 10 kW online double-conversion UPS for 120/240 V split-phase loads, with a 3U rack cabinet of 16 × 12 V 9 Ah VRLA blocks, expandable with more cabinets. Kept at 80 % of its rating, it carries loads up to 8 kW.

10 kVA / 10 kWRating
17.3 × 22.8 × 8.5 inW × D × H
143 lbWeight
VRLA, 3U cabinet includedBattery
AEC FERRUS SP RT UPS, series picture

Series picture.

Load by load

The FERSPRT10000-16X9 at 25, 50, 75 and 100 % load.

Its 10 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current on each legEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the FERSPRT10000-16X9, 2.5 kW10.4 A on each leg90.8 % efficient253 W of heat860 BTU/h to cool
50 % of the FERSPRT10000-16X9, 5.0 kW20.8 A on each leg92.8 % efficient388 W of heat1,320 BTU/h to cool
75 % of the FERSPRT10000-16X9, 7.5 kW31.3 A on each leg93.0 % efficient565 W of heat1,930 BTU/h to cool
100 % of the FERSPRT10000-16X9, 10 kW41.7 A on each leg92.8 % efficient776 W of heat2,650 BTU/h to cool

Current = kVA × load ÷ volts.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the FERSPRT10000-16X9?

  • Input / Output: 120/240 V split-phase
  • Efficiency: Up to 93%
  • Form: rack or tower, with an integrated isolation transformer
  • Battery: 16 × 12 V 9 Ah VRLA blocks included, in their own rack cabinet
  • Output: hardwired terminal block
  • Rack space: 5U for the UPS and 3U for its battery cabinet, 8U in all

Size and floor

How big it is

17.3" W × 22.8" D × 8.5" H (439 × 579 × 216 mm); 143 lb (64.9 kg) net. The catalog gives 143 lb (64.9 kg) for the FERSPRT10000-16X9, 123.6 lb (56.1 kg) for its 3U battery cabinet BAT16192RT, and 266.6 lb (120.9 kg) for the two together (FERSPRT10000-16X9+BAT16192RT).

2.7 ft²footprint (0.25 m²)
52 lb/ft²floor load of the cabinet alone
Rack/tower, 19-inch rackform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 17.3″22.8″8.5″

Datasheet

FERSPRT10000-16X9 datasheet.

The FERSPRT10000-16X9 in the AEC 2026 catalog, figure by figure. Compare it with every FERRUS SP RT model.

FERSPRT10000-16X9 datasheet
ParameterFERSPRT10000-16X9
Power
Rated power (kVA)10
Active power (kW)10
Output power factor1.0
Electrical
Input / output120/240 V split-phase
TopologyOnline Double Conversion
Efficiency, up to93%
Battery DC bus192 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configuration3U rack cabinet with 16 × 12 V 9 Ah VRLA, included (UPS 5U + cabinet 3U, 8U in all); more cabinets can be added
Mechanical
Form factorRack/tower, 19-inch rack
Dimensions W × D × H17.3 × 22.8 × 8.5 in (439 × 579 × 216 mm)
Net weight143 lb (64.9 kg)
Footprint2.7 ft² (0.25 m²)
Common to every FERRUS SP RT
BatteryVRLA: each UPS comes with a 3U rack cabinet of 16 × 12 V 9 Ah blocks; more cabinets can be added
Network cardSNMP-M (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

FERSPRT10000-16X9: what people ask

What is the output current of the FERSPRT10000-16X9?

41.7 A on each line at 240 V at full load: 10 kVA ÷ 240 V. Size the input breaker and the cables of the FERSPRT10000-16X9 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the FERSPRT10000-16X9 give off?

About 776 W, 2,650 BTU/h, at full load, where it is 92.8% efficient. Plan the room's cooling for a little more than that: the FERSPRT10000-16X9 is less efficient at part load and while its battery recharges.

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

FERRUS SP RT

Other FERRUS SP RT models

The FERRUS SP RT series, with pictures

By power, the FERSPRT10000-16X9 is the largest in the FERRUS SP RT series, which runs from 6 to 10 kVA. One size down is the FERSPRT6000-16X9 (4 kVA less; 15 lb lighter; 3U rack cabinet with 16 × 12 V 9 Ah VRLA, included (UPS 4U + cabinet 3U, 7U in all); more cabinets can be added).

Every FERRUS SP RT model side by side (2)
FERRUS SP RT models side by side
ModelPowerPower against this modelNet weightWeight against this modelBattery configuration
FERSPRT6000-16X96 kVA4 kVA less128 lb15 lb lighter3U rack cabinet with 16 × 12 V 9 Ah VRLA, included (UPS 4U + cabinet 3U, 7U in all); more cabinets can be added
FERSPRT10000-16X910 kVAthis page143 lbthis page3U rack cabinet with 16 × 12 V 9 Ah VRLA, included (UPS 5U + cabinet 3U, 8U in all); more cabinets can be added

The FERSPRT10000-16X9 for your project

Send the load, the voltage and the minutes you need from the FERSPRT10000-16X9. We reply with the configuration, the batteries and the lead time.