Rack-mount UPS: depth, weight, lithium vs VRLA

A rack-mount UPS sits in the same 19-inch rack as the servers it protects; AEC's 120 V rack units are 2U, from 1 to 3 kVA (LUMINA lithium and FERRUS RT VRLA), and FERRUS SP RT adds 6 and 10 kVA for 120/240 V. Four numbers decide whether one fits: its height in rack units, its depth, its weight, and its runtime.

Data center, black-and-white photograph

Which AEC UPS fit a rack?

ModelPowerHeightDepthWeightRuntime, full / half load
LUM1000RT-2U-LI1 kVA / 900 W2U16.5 in19.6 lb11 / 27 min
LUM3000RT-2U-LI3 kVA / 2.7 kW2U22.4 in37.7 lb11 / 27 min
LUM2200RT-2U-LI2.2 kVA / 1.98 kW2U24.2 in42.1 lb23 / 46 min
FER1000RT-2X91 kVA / 1 kW2U17.3 in41.8 lb4.2 / 10 min
FER3000RT-6X93 kVA / 3 kW2U22.8 in61.7 lb4.2 / 10 min
FERRUS SP RT6 and 10 kVA, 120/240 V6.7 and 8.5 in22.8 in128 and 143 lbwith external battery cabinets

Lithium or VRLA in a rack?

At 3 kVA, the lithium LUMINA weighs 37.7 lb and runs 11 minutes at full load; the VRLA FERRUS RT weighs 61.7 lb and runs 4.2 minutes. The lithium unit is 24 lb lighter and runs about 2.6 times as long, in the same 2U. LUMINA's warranty is five years with the lithium batteries included; FERRUS RT's is three years on the UPS and two on the batteries.

What should you check before mounting it?

  • Depth. Check the rack's usable depth between the rails and leave room behind for the cables and the plugs.
  • Weight low. Mount the UPS and its battery packs at the bottom of the rack, where the weight keeps the rack stable.
  • Rails. LUMINA ships with its rails. Use rails rated for the weight.
  • More runtime. FERRUS RT takes external rack battery packs (24, 48 and 72 V DC, 3.4 to 7 in high); FERRUS SP RT takes the 192 V DC rack cabinet.

How much rack space does a set of minutes take?

A rack unit is 1.75 in. AEC's 2U units are 3.4 in high, and the FERRUS RT packs are 3.4 in (BAT0424RT, 2U), 5.2 in (BAT0848RT, 3U) and 7 in (BAT1272RT, 4U). An example: 2,000 W of network and storage on 3 kVA. The UPS sizing tool reads the minutes of every model and pack at your own load.

Set-upRack spaceWeightMinutes at 2,000 W
LUM3000RT-2U-LI, lithium inside2U37.7 lbabout 19 (74 % load)
FER3000RT-6X9, VRLA inside2U61.7 lbabout 7 (67 % load)
FER3000RT-6X9 with one BAT1272RT pack6U155.9 lbabout 27, from the catalog's estimated table

Per rack unit, lithium gives the most minutes: the LUMINA does in 2U what the VRLA unit needs 6U and more than four times the weight to beat. The VRLA set-up wins on minutes once packs are added, and each pack adds more.

What plugs into what?

The input plug sets the circuit (the FERRUS 3 kVA models have an attached cord with a NEMA L5-30P), and the output receptacles set what plugs in. The LUM3000RT-2U-LI has four NEMA 5-20R and one L5-30R; the FERRUS RT 3 kVA six 5-20R and one L5-30R. A 30 A rack PDU with an L5-30P plug goes into the L5-30R and spreads the UPS output across the whole rack. FERRUS SP RT is hardwired: its output goes to a terminal block, and an electrician wires it to the rack's distribution.

How much heat does it add to the rack?

A rack UPS gives off its losses inside the rack. At 2,000 W, the LUM3000RT-2U-LI at its catalog 92.5 % loses about 162 W, 550 BTU/h; the FER3000RT-6X9 at 93 % about 150 W. That is small next to the 2,000 W of the equipment, which ends up as heat too, but it comes out of one 2U unit at the bottom of the rack. Keep the blanking panels in, so the hot air from the back does not loop round to the front.

Which rack UPS for a 120/240 V panel?

FERRUS SP RT, 6 and 10 kVA, split phase, with an isolation transformer. Its batteries are always external: 16 VRLA blocks at 192 V DC in each BAT16192RT rack cabinet, 5.2 in high and 25 in deep, and more cabinets for more runtime. From the catalog tables, the FERSPRT6000-16X9 with two cabinets runs 14.3 minutes at full load, and with four 34; the 10 kVA model with four cabinets runs 17.9 minutes.

What about the rails?

AEC's RLKT telescopic kit fits 2-post and 4-post 19-inch racks and is rated for 100 lb, enough for any LUMINA, from 19.6 to 42.1 lb. Heavier set-ups, such as a FERRUS RT with packs, need rails or a shelf rated for the weight of each unit, and every pack its own support. Mount the heaviest piece first, at the bottom, and fit the anti-tip feet or bolt the rack down before sliding anything out.

What mistakes come up with rack UPS?

  • Measuring the rack's outside depth instead of the depth between the front and rear rails.
  • Putting the UPS at eye height for its display, high in a rack that then tips when it is slid out.
  • Buying a 3 kVA unit for a rack fed by a 20 A receptacle.
  • Blocking the front or the back: a rack UPS draws air through itself like the servers around it.
  • Counting on the runtime of a new battery when the rack will grow by a third in two years.

Each model page has its full datasheet; or read UPS for offices and small business.

Questions people ask

How many rack units is a 3 kVA UPS?

AEC's 3 kVA rack UPS are 2U: the LUMINA lithium LUM3000RT-2U-LI and the FERRUS RT FER3000RT-6X9 are both 2U, 22.4 and 22.8 in deep.

Is a lithium rack UPS lighter than a VRLA one?

Yes. At 3 kVA the AEC LUMINA lithium weighs 37.7 lb against 61.7 lb for the VRLA FERRUS RT, and runs 11 minutes at full load against 4.2.

Where should a UPS go in a rack?

At the bottom, with its battery packs: the weight low keeps the rack stable. Check the rack's usable depth and leave room for cables behind.

Can a rack UPS stand as a tower?

Yes, if it is built for both: the AEC FERRUS RT is a rack or tower unit, so it can stand on the floor or mount in a 19-inch rack. LUMINA is a 2U rack unit.