Comparison · Modular three-phase UPS, 208 V

RADIANT against the modular 208 V UPS of the big brands.

13 current models of Xtreme Power, Delta, Toshiba, APC, Vertiv and Eaton are compared here with 9 AEC RADIANT models; at 15 to 30 kVA the AEC RAD90-1X15 has the best efficiency, online, 94 % against 93 % for the Xtreme Power M90C-6S24K.

AEC RADIANT

In short

Why AEC RADIANT

  • RADIANT is modular N+X: 15 kVA power modules, up to six in a 19-inch frame, hot-swappable while the others carry the load; RADIANT-IB adds its VRLA battery trays inside, with 20 kVA modules up to 100 kVA.
  • Both run at a power factor of 1.0 with a 3-level inverter, up to 94 % efficient.

Size by size

Where AEC leads, and where a rival does.

Worked out from the tables below: the AEC figure against the best of the other makers.

15 to 30 kVA

  • Efficiency, online94 %RAD90-1X15 · best rival 93 %, Xtreme Power

40 to 60 kVA

  • Warranty, UPS / battery3 years on UPS · 2 years on VRLA batteriesRAD90-3X15 · best rival 2 yr / 2 yr, Xtreme Power
  • Efficiency, onlineEaton: 97 %
  • Footprint W × DAPC: 21.7 × 33.4 in (550 × 847 mm), VRLA

75 to 100 kVA

  • Footprint W × D23.6 × 39.3 in (599 × 998 mm)RADIB100-5X20, VRLA · best rival 47.2 × 42.1 in (1,199 × 1,069 mm), APC, VRLA
  • Warranty, UPS / battery3 years on UPS · 2 years on VRLA batteriesRAD90-6X15 · best rival 2 yr / 2 yr, Xtreme Power
  • Efficiency, onlineVertiv: 95.7 %

Side by side

Model by model.

The best figure in each column is marked, whoever holds it. Each row is one configuration, with the battery its own datasheet lists for it (the Battery column says which), so runtimes compare those configurations, not the makers. AEC rows first in each size.

15 to 30 kVA

ModelOutputArchitectureBatteryEfficiency, onlineFootprint W × DWarranty, UPS / battery
RAD90-1X15AEC RADIANTDatasheet · Size it for your load15 kWModular, 15 kVA modulesVRLA, external bank94 %17.4 × 33.1 in (442 × 840 mm)3 years on UPS · 2 years on VRLA batteries
RAD90-2X15AEC RADIANTDatasheet · Size it for your load30 kWModular, 15 kVA modulesVRLA, external bank94 %17.4 × 33.1 in (442 × 840 mm)3 years on UPS · 2 years on VRLA batteries
RADIB100-1X20AEC RADIANT-IBDatasheet · Size it for your load20 kWModular, 20 kVA modulesVRLA, inside94 %23.6 × 39.3 in (599 × 998 mm)3 years on UPS · 2 years on VRLA batteries
Xtreme Power1 model at this size24 kWModular, 5 or 8 kW modulesVRLA, inside93 %17.4 × 33.7 in (442 × 856 mm)2 yr / 2 yr
Toshiba2 models at this size18 kW / 27 kWModularExternal92.9 %19.7 × 27 in (500 × 686 mm)3 yr / not stated

40 to 60 kVA

ModelOutputArchitectureBatteryEfficiency, onlineFootprint W × DWarranty, UPS / battery
RAD90-3X15AEC RADIANTDatasheet · Size it for your load45 kWModular, 15 kVA modulesVRLA, external bank94 %17.4 × 33.1 in (442 × 840 mm)3 years on UPS · 2 years on VRLA batteries
RAD90-4X15AEC RADIANTDatasheet · Size it for your load60 kWModular, 15 kVA modulesVRLA, external bank94 %17.4 × 33.1 in (442 × 840 mm)3 years on UPS · 2 years on VRLA batteries
RADIB100-2X20AEC RADIANT-IBDatasheet · Size it for your load40 kWModular, 20 kVA modulesVRLA, inside94 %23.6 × 39.3 in (599 × 998 mm)3 years on UPS · 2 years on VRLA batteries
RADIB100-3X20AEC RADIANT-IBDatasheet · Size it for your load60 kWModular, 20 kVA modulesVRLA, inside94 %23.6 × 39.3 in (599 × 998 mm)3 years on UPS · 2 years on VRLA batteries
Xtreme Power2 models at this size60 kWModular, 15 or 20 kVA modules / Modular, 15 or 20 kW modulesVRLA, inside / External94 %20.3 × 39.4 in (516 × 1,001 mm)2 yr / 2 yr (M90U); 2 yr / not stated (M90LU)
Delta1 model at this size60 kWModular, 15 kVA modulesNot stated, inside95 %23.6 × 33.5 in (600 × 850 mm)not stated / not stated
APC2 models at this size40 kW / 50 kWModular, 25 kW modulesVRLA, inside94.3 % – 94.8 %21.7 × 33.4 in (550 × 847 mm)1 yr / not stated
Vertiv1 model at this size50 kWModular, 15 kW modulesVRLA, inside—23.6 × 40.6 in (599 × 1,031 mm)1 yr / not stated
Eaton1 model at this size60 kWModular, 20 kW modulesVRLA, inside97 %22 × 42 in (559 × 1,067 mm)1 yr / not warranted

75 to 100 kVA

ModelOutputArchitectureBatteryEfficiency, onlineFootprint W × DWarranty, UPS / battery
RAD90-6X15AEC RADIANTDatasheet · Size it for your load90 kWModular, 15 kVA modulesVRLA, external bank94 %17.4 × 33.1 in (442 × 840 mm)3 years on UPS · 2 years on VRLA batteries
RADIB100-5X20AEC RADIANT-IBDatasheet · Size it for your load100 kWModular, 20 kVA modulesVRLA, inside94 %23.6 × 39.3 in (599 × 998 mm)3 years on UPS · 2 years on VRLA batteries
Xtreme Power1 model at this size80 kWModular, 15 or 20 kVA modulesVRLA, inside94 %23.6 × 43.3 in (599 × 1,100 mm)2 yr / 2 yr
APC1 model at this size90 kWModular, 10 kW modulesVRLA, inside—47.2 × 42.1 in (1,199 × 1,069 mm)1 yr / not stated
Vertiv1 model at this size90 kWModular, 30 kW modulesExternal95.7 %23.6 × 40.6 in (599 × 1,031 mm)1 yr / not stated

Rival figures from each maker's own published documents, read 10 Oct 2026 and named model by model under Sources; where two of a maker's documents disagree, the more conservative figure is used. AEC figures from the AEC 2026 catalog. Efficiency is the online (double-conversion) figure, not ECO mode. Runtime is not compared here: these AEC models run on external banks sized to order or have no runtime table published per model. Weights and footprints compared only for units with their batteries inside; a weight marked UPS only leaves the battery cabinets out. Brand and model names are trademarks of their owners; AEC is not affiliated with them and names their models only to compare them.

By maker: AEC vs Xtreme Power · AEC vs Delta · AEC vs Toshiba · AEC vs APC · AEC vs Vertiv · AEC vs Eaton

Questions

What people ask

Which Modular three-phase UPS, 208 V has the best efficiency, online at 15 to 30 kVA?

In this comparison, the AEC RAD90-1X15: 94 %, against 93 % for the Xtreme Power M90C-6S24K, the highest figure among the other makers' models here. Figures from each maker's published documents, read 10 Oct 2026.

Which Modular three-phase UPS, 208 V has the best warranty, UPS / battery at 40 to 60 kVA?

In this comparison, the AEC RAD90-3X15: 3 years on UPS · 2 years on VRLA batteries, against 2 yr / 2 yr for the Xtreme Power M90U-60, the highest figure among the other makers' models here. Figures from each maker's published documents, read 10 Oct 2026.

Which Modular three-phase UPS, 208 V has the best footprint W × D at 75 to 100 kVA?

In this comparison, the AEC RADIB100-5X20: 23.6 × 39.3 in (599 × 998 mm), against 47.2 × 42.1 in (1,199 × 1,069 mm) for the APC SY90K100F, the lowest figure among the other makers' models here. Figures from each maker's published documents, read 10 Oct 2026.

Which makers are compared?

Xtreme Power, Delta, Toshiba, APC, Vertiv, Eaton: 13 current models, with 9 AEC RADIANT models.

Where do the figures come from?

Rival figures from each maker's own published documents, read 10 Oct 2026; each document is named, model by model, under Sources. AEC figures from the AEC 2026 catalog and AEC's runtime tables; a model without a runtime table of its own reads not published. Where a maker's documents disagree, the more conservative figure is used.

Sources

Where the rival figures come from

Xtreme Power: 4 models, documents read 10 Oct 2026
  • M90C-6S24K: xpcc.com/…/m90c-6s; M90C-6S-flyer.pdf (xpcc.com).
  • M90U-60: xpcc.com/…/products/m90u; M90U-flyer.pdf (xpcc.com).
  • M90LU-60: xpcc.com/…/m90lu; M90LU-flyer.pdf (xpcc.com).
  • M90U80-80k: xpcc.com/…/m90u-80; M90U-80-flyer.pdf (xpcc.com).
Toshiba: 2 models, documents read 10 Oct 2026
  • 11A0H020KCXC: toshiba.com/…/1100-tp-series-ups; 1100-TP-Series-UPS-Specifications-scaled.jpg (toshiba.com).
  • 11A0H030KCXC: toshiba.com/…/1100-tp-series-ups; 1100-TP-Series-UPS-Specifications-scaled.jpg (toshiba.com).
Delta: 1 model, documents read 10 Oct 2026
  • DPH-60K-LV: delta-americas.com/…/dph-series-15-kva-105kva-three-phase-modular-ups.
APC: 3 models, documents read 10 Oct 2026
  • GVSUPS40KB5FS: 990-91318H_EN.pdf (productinfo.schneider-electric.com).
  • GVSUPS50KB5FS: 990-91318H_EN.pdf (productinfo.schneider-electric.com); GVSUPS50KB5FS (se.com); Schneider Electric_Galaxy-VS_GVSUPS50KB5FS.pdf (se.com).
  • SY90K100F: SY90K100F (se.com); Schneider Electric_Symmetra-PX_SY90K100F.pdf (se.com); SYPM10KF2 (se.com).
Vertiv: 2 models, documents read 10 Oct 2026
  • APM2 208 V 60 kW frame: vertiv-liebert-apm2-data-sheet-sl-71300.pdf (vertiv.com); limited-warranty-vertiv-three-phase-ac-power-products-sl-71249.pdf (vertiv.com).
  • APM2 208 V 150 kW frame: vertiv-liebert-apm2-data-sheet-sl-71300.pdf (vertiv.com); limited-warranty-vertiv-three-phase-ac-power-products-sl-71249.pdf (vertiv.com).
Eaton: 1 model, documents read 10 Oct 2026
  • 93PM-L 60-3: eaton.com/…/eaton-93pm-ups; eaton-93pm-ups-brochure-BR153033EN.pdf (eaton.com); eaton-93pm-l-60kw-ups-P-164000711.pdf (eaton.com); eaton-three-phase-ups-warranty.pdf (eaton.com).

Send us the model you have

The label or the datasheet of the UPS you have now is enough: we reply with the AEC model, the runtime and the lead time.